User's Manual
File : CS-SUP-MUTI-WTHERMAPP-E01.sxw
6.1.2 Parameters specific to the WaveTherm – DALLAS module
N° Description
Size
(in bytes)
Access
right
Default value
Hexa. Decimal
0x25 Parameter A relative to the sensor 1 2 R/W
0xFFFF -
0x26 Parameter B relative to the sensor 1 2 R/W 0xFFFF -
0x27 Parameter A relative to the sensor 2 2 R/W 0xFFFF -
0x28 Parameter B relative to the sensor 2 2 R/W 0xFFFF -
0x23 Measurement period of the threshold detection (in minutes) 1 R/W 0x00 0
0x15 High Threshold Alarm – Sensor 1 2 R/W 0x01A0 26°C
0x16 Low Threshold Alarm – Sensor 1 2 R/W 0x0100 16°C
0x17 High Threshold Excess Time – Sensor 1 (multiple of the measurement
period of threshold detection)
1 R/W 0x04 4
0x18 Low Threshold Excess Time – Sensor 1 (multiple of the measurement
period of threshold detection)
1 R/W 0x04 4
0x2B High Threshold Alarm – Sensor 2 2 R/W 0x01A0 26°C
0x2C Low Threshold Alarm – Sensor 2 2 R/W 0x0100 16°C
0x2D High Threshold Excess Time – Sensor 2 (multiple of the measurement
period of threshold detection)
1 R/W 0x04 4
0x2E Low Threshold Excess Time – Sensor 2 (multiple of the measurement
period of threshold detection)
1 R/W 0x04 4
6.1.3 Parameters specific to the WaveTherm – PT100 module
N° Description
Size
(in bytes)
Access
right
Default value
Hexa. Decimal
0x0C Precision level of the measurement 1 R/W 0x00 0
0x21 Extended Application Status 1 R/W 0x00 0
0x23 Measurement period of the threshold detection (in minutes) 1 R/W 0x00 0
0x15 High Threshold Alarm – Sensor 1 4 R/W 0x0000C041 24°C
0x16 Low Threshold Alarm – Sensor 1 4 R/W 0x0000A041 20°C
0x17 High Threshold Excess Time – Sensor 1 (multiple of the measurement
period of threshold detection)
1 R/W 0x04 4
0x18 Low Threshold Excess Time – Sensor 1 (multiple of the measurement
period of threshold detection)
1 R/W 0x04 4
0x2B High Threshold Alarm – Sensor 2 4 R/W 0x0000C041 24°C
0x2C Low Threshold Alarm – Sensor 2 4 R/W 0x0000A041 20°C
0x2D High Threshold Excess Time – Sensor 2 (multiple of the measurement
period of threshold detection)
1 R/W 0x04 4
0x2E Low Threshold Excess Time – Sensor 2 (multiple of the measurement
period of threshold detection)
1 R/W 0x04 4
0x30
Value of the internal reference resistance very low
(32-bit float in LSB First)
4 R 0x00000000 0 Ω
0x31
Value of the internal reference resistance very high
(32-bit float in LSB First)
4 R 0x00000243 130 Ω
0x32 Coefficients of probe 1 32 R/W - -
0x33 Coefficients of probe 2 32 R/W - -
0x91 Date of probe fault detection on sensor 1 6 R/W 0 0
0x92 Date of probe fault detection on sensor 2 6 R/W 0 0
WaveTherm modules – application handbook page 22 of 65