User's Manual

RTM Elster AMCO applicative PFS Coronis Systems
Encoder model is then stored in an internal parameter which is in read access only.
Applicative
command
Associated internal
parameters
Description
0x18
0x1D ; 0x1E
Request to read the encoder model parameters
0x98
0x1D ; 0x1E
Encoder model reading response
“encoder model” parameters are accessible by standard reading parameters command (described in §4.2.).
0x1D encoder model on Port A,
0x1E encoder model on Port B,
5.4.6.Encoder Unit (Encoder register only)
Each encoder embeds its unit in an internal parameter and the RTM Elster AMCO reads out this information
after encoder model detection. It stores the unit inside a read only parameter.
The unit parameter contains two important information that are the position of the decimal point and the unit.
ATTENTION:
the unit value will only be given for informative purpose. RTM Elster AMCO does not convert the current
unit to a standard GALLON unit and all operations are processed without taking into account the unit and
the decimal point position, it is up to the user software to convert the information in desired unit.
Applicative
command
Associated internal
parameters
Description
0x18
0x1F ; 0x20
Request to read the unit parameters
0x98
0x1F ; 0x20
Encoder Unit reading response
The MSByte indicates the unit.
The LSByte indicates the number of digits before the decimal point.
Default value is assigned to 0xFFFF.
The table below gives the different possible unit (MSB byte) :
MSB unit value
(hexadecimal)
Unit definition
Elster AMCO
encoder
SENSUS
encoder
0x01 Cubic meters (m
3
) X X
0x11 Cubic meters * 10 X
0x21 Cubic meters * 100 X
0x02 US Gallons * 1000 X
0x03 Imperial gallons X X
0x04 liters X X
0x05 Cubic feet * 100 X
0x06 US gallons X X
0x07 -”K” Multiplier (*1000) X
0x08 Kilo liters X X
0x30 Cubic feet X
0x31 Cubic Inches X
0x32 Cubic Yards X
0x33 Acre feet X
TBD TBD TBD TBD
EVO RTM-UserMan 35