User's Manual
Infrastructure Preparation
MA-860 Installation and Configuration Guide 19
3.5.3 AP Termination
A 50 Ω
ΩΩ
Ω termination is required on each unused AP port. The type of termination is vendor
specific.
Vendor Model
Termination
Cisco 1242 RP-TNC 50 ohm terminators
Aruba AP-70 RP-SMA 50 ohm terminators
Trapeze MP-422 RP-SMA 50 ohm terminators
Colubris MAP-330 RP-SMA 50 ohm terminators
Meru AP-200 RP-SMA 50 ohm terminators
3.5.4 IDF Access Point Planning
MobileAccess recommends that each independent IDF Telecom closet is adequately planned for
installation of the access points to increase the amount of isolation and reduce the amount of RF
leakage between access points.
MobileAccess recommends the following options for access point installation:
• Wall Mounting of MobileAccess supported Access Point
• Rack-Mounting of MobileAccess supported Access Points
Utilizing the mounting hardware distributed from each supported access point vendor, Access
point can be mounted on a wall within the IDF or telecom closet and connected with the
appropriate low-loss jumper cables to the appropriate 860 WLAN module interface ports.
MobileAccess has also found that mounting the access points in a 19” rack system has proven to
be effective against RF leakage between access points. In this configuration,
two access points
can be installed per 19” shelving unit which takes up 1U of space per two access points.