User's Manual
Table Of Contents
- 1 Introduction
- 2 Installation Guidelines
- 3 HX Indoor Physical Installation
- 4 HX Outdoor Physical Installation
- 5 Appendix A: System Specifications
- 6 Appendix B: Ordering Information
- 7 Appendix C: HX Outdoor Non-Standard Connector Descriptions
- 8 Appendix D: Power Cable Specifications
Corning Optical Communications User Manual I CMA-066-AEN I Page 23
2.4 Fiber Optic Requirements
2.4.1 Authorized Optic Cables
• Only single mode fiber can be used with HX Indoor/Outdoor products,
• All fiber in a given length of fiber must be of the same core diameter.
For HX Indoor models:
• All Bulkhead adapters must be either Single SC APC (Green) adapters.
• All terminations, cross connections or patches must be direct fusion splice or Corning specified patch cords listed
below.
900 microns pathcord for splicing, 2 Meters, 2xSC/APC
Diamond p/n ENC/1045341 Beige boots, 62.5/125/900 MA# 500001057
Diamond p/n ENC/1045340 Black boots, 50/125/900 MA# 500001058
Zipcord patchcord, 4xSC/APC, 50/125/900/2000/4500 micron
Diamond p/n ENC/1045342 Black/Brown boots, 1 Meter MA# 50000105
Diamond p/n ENC/1045343 Black/Brown boots, 3 Meter MA# 500001060
Zipcord patchcord, 4xSC/APC, 62.5/125/900/2000/4500 micron
Diamond p/n ENC/1045344 Beige/Brown boots, 1 Meter MA# 500001061
Diamond p/n ENC/1045345 Beige/Brown boots, 3 Meter MA# 500001062
For HX Outdoor models :
Use Corning OptiTap™ cables:
Part Number Description
434401EB4R2005M-P
OptiTap® to SC/APC 5 meters
434401EB4R2030M-P
OptiTap ®to SC/APC 30 meters
434401EB4R2100M-P
OptiTap® to SC/APC 100 meters