User's Manual

Commissioning the System
P/N 709C011801
Page 61
6.3 Required Pre-Setup Procedures
Perform the pre-setup procedures as follows:
1. Verify that all of the installed devices have been automatically detected:
Click the Config tab. In the Topology Tree.
Verify that the LEDs adjacent to all of the Topology Tree items (ACM, RIMs, OIMs, RAUs, etc.) are colored in any other
color but gray.
If an item is gray, verify the physical connections.
NOTE: You may use the Baseline reset button to set all of the devices currently displayed in the Network Topology pane as
a reference and continue displaying them (in gray) even if communication is lost with a device.
Figure 6-9. Verifying detected Device in Network Topology
Verify all devices are displayed in the tree
2. In the HCM alarms tab, verify that all system alarms are green:
In the Topology Tree, click System Management.
In the HCM Alarms tab, verify all alarms are green.
If any of the alarms are not green, refer to HCM Alarms (on page 126).
If the Installation Failure alarm is red, click on the Info hyperlink. The Installation Failure dialog will appear, listing the
detected faulty connections.
Figure 6-10. Install Fault Details Dialog