TROUBLESHOOTING
IMPORTANT: Only qualified personnel should service internal components or electrical wiring.
Troubleshooting Compressors
Trouble Probable Cause Remedy
Basically the compressor problems can be narrowed down to three areas of checkout.
THE COMPRESSOR WILL
NOT RUN
A. No voltage to the compr
essor ter-
minals.
B. Low voltage
C. Problems in the compressor elec-
trical circuit.
A. Check circuit.
B. Below 90% of nameplate rated
vo
ltage
C. See electrical checkout instruc-
tions.
THE COMPRESSOR STARTS BUT
TRIPS REPE
ATEDLY ON THE
OVERLOAD PROTECTOR
A. Fan / condenser problem.
B. Suction and discharge problem.
C. Voltage.
D. High compressor amperage draw.
A. Check for proper fan operation
an
d clean condenser.
B. Check the compressor suction and
discharge pressures
.
C. Voltage should be within 10% of
the r
ated nameplate voltage.
D. It should never exceed 120% of the
rated nameplate amperage. See
electrical checkout instructions.
THE COMPRESSOR RUNS BUT
WILL NO
T REFRIGERATE
A. Compressor not working A. Check the compressor suctions
and discharge pressures. See
chart on page 17.