Specifications

Xtreme Ice Training Manual
TP00952
October 17, 2005
22
WATER FILL TIME OUT
1. During the fill cycle if the water level does not reach the maximum level in 4 minutes the machine
goes into a delay sequence.
2. After each delay, the machine restarts at the secondary start up.
3. The sequence continues as follows:
S Fill try, 30 min delay, fill try, 30 min delay, fill try, 2 hr delay.
S Fill try, 30 min delay, fill try, 30 min delay, fill try, 2 hr delay.
S Fill try, 30 min delay, fill try, 30 min delay, fill try, 2 hr delay.
S Fill try, 30 min delay, fill try, 30 min delay, fill try, 2 hr delay.
S Fill try, 30 min delay, fill try, 30 min delay, fill try, shut down.
4. During the delay times, the DELAY LED flashes 2 times at 4 second intervals.
5. Once the machine reaches shut down position, all outputs turn off.
6. At the shut down time, the ERROR LED flashes 2 times at 4 second intervals.
7. The machine will not run until the power is cycled.
8. The delay sequence resets after each successful harvest.
Possible Causes
1. Low inlet water pressure
2. Fill valve failure
3. Plugged fill valve screen
4. Pressure tube disconnected or cut
5. Pressure sensor failure
6. Leak in water pan
7. Water pan cap removed
MAXIMUM FREEZE TIME OUT
1. At the beginning of the prechill cycle, the microprocessor starts a timer.
2. If the timer reaches 50 minutes before a harvest cycle can be initiated, the machine enters a delay
sequence.
3. After each delay, the machine restarts at the secondary start up.
4. The delay sequence continues as follows:
S Freeze try, 30 min delay, freeze try, 30 min delay, freeze try, 2 hr delay,
S Freeze try, 30 min delay, freeze try, 30 min delay, freeze try, 2 hr delay,
S Freeze try, 30 min delay, freeze try, 30 min delay, freeze try, 2 hr delay,
S Freeze try, 30 min delay, freeze try, 30 min delay, freeze try, 2 hr delay,
S Freeze try, 30 min delay, freeze try, 30 min delay, freeze try, shut down.
5. During the delay times, the DELAY LED flashes 4 times at 4 second intervals.
6. Once the Machine reaches shut down position all out puts turn off.
7. At the shut down time, the ERROR LED flashes 4 times at 4 second intervals.
8. The machine will not run until the power is cycled.
9. The delay sequence resets after each successful harvest.
Possible Causes
1. Water pump failure
2. Low refrigerant charge
3. Leak in refrigerant lines
4. Compressor failure
5. Hot gas valve leaking
6. Dirty evaporator