4. Replace side panels and restart unit.
5.3 Condenser Fan Motor
The condenser fan motor is sealed at the factory and needs no lubrication. The
motor can be checked in two ways; check for continuity, and check to see that
power is present at the terminal block or terminal strip.
5.4 Condenser Fan Blade
The condenser fan blade pulls air through the condenser. If the blade is damaged or
is not positioned correctly in the condenser shroud, the blade will not pull or push
the correct amount of air to cool the condenser coil, reducing refrigeration effi-
ciency.
5.5 System Leak
Symptoms of a refrigerant leak include a running compressor with a hot suction
line and the compressor running excessively hot, and an increased amp draw by
the compressor. A sweep of the refrigeration system is necessary to determine if
there is a leak.
If there is a leak in the system, it must be evacuated and repaired by an certified
refrigeration technician. The system must then be pulled down to a vacuum and
recharged with the correct level of refrigerant.
6. REFRIGERATION TROUBLESHOOTING
PROBLEM (fault) CAUSE (diagnosis) ACTION (remedy)
1. Compressor will not
start, no humming
noise
A. Line disconnect switch
open
B. Fuse removed/blown
C. Overload protection
tripped
D. Control stuck in open
position
E. Control OFF due to
cold location
F. Wiring improper or
loose
A. Close start or discon-
nect switch
B. Replace fuse
C. Refer to electrical ser-
vicing
D. Repair or replace con-
trol
E. Relocate control
F. Check wiring against
diagram
TROUBLE SHOOTING