Amplifier Setup Procedure CME 2 User Guide
30 Copley Controls
...Setup Procedure, continued:
3
Enter Motor/Feedback/Brake Stop parameters
Click Motor/Feedback to open the Motor/Feedback screen.
To optionally load data from an existing motor data file,
see Load Motor/Feedback/Brake Settings from a File (p. 43) and then skip to
Step 4, Use Calculate to automatically set initial gains and limits (p. 27).
OR
On the Motor tab, modify the appropriate Rotary Motor Setup Parameters (p. 44) or
Linear Motor Setup Parameters (p.45).
On the Feedback tab, as appropriate for each encoder or resolver, verify the parameters
described in Feedback Parameters, Rotary (p. 46) or
Feedback Parameters, Linear (p. 50).
If using a brake, click the Brake/Stop tab to verify Brake/Stop Parameters (p. 52).
4
Use Calculate to automatically set initial gains and limits
Click Calculate to have the software calculate and display initial loop gains and limits.
See The Calculate Function (p. 54).
Load the calculated values into amplifier RAM by clicking OK.
5
Configure digital I/O
Click Input/Output on the Main screen to open the Input/Output screen.
Verify the I/O settings described in Digital Inputs and Outputs (p. 55).
On the Input/Output screen, click Close.
6
Configure the command input
or or or
Click the appropriate button to configure the amplifier’s command input.
For more information see Command Inputs (p. 69).
NOTE: If the amplifier is to run CVM programs or in Camming mode see the relevant
documents.
After setting command input parameters, Click Close.