D.5.3: Cable Notes
1 Keep the Edge Filter to Xenus Plus cable as short as possible. A typical length is 7 inches.
2 To reduce noise, twisted shielded cable must be used and the signal cables should not be
bundled in the same conduit.
D.5.4: Edge Filter Input (J1) From Drive
Mating Connector
Description
Euro-style, 5 position, 5.0 mm pluggable female terminal block
Manufacturer PN
Wago 721-105/026-047 (Note 1)
Connector Wire Size
22-12 AWG
Recommended Wire
12 AWG, 600 V (Shielded cable used for CE compliance)
Wire Insertion/Extraction Tool
Wago 231-131
Connector and tool are included in Connector Kit XTL-FK.
Note 1: For RoHS compliance, append “/RN01-0000” to the Wago part numbers listed above.
Pin Description
Pin
Signal
Function
1
Frame Ground
Chassis ground and cable shield
2
Phase W
Phase W input from drive
3
Phase V
Phase V input from drive (use for DC motor connection)
4
Phase U
Phase U input from drive (use for DC motor connection)
5
---
No connection
D.5.5: Edge Filter Output (J2) To Motor
Mating Connector
Description
Euro-style, 4 position, 5.0 mm pluggable female terminal block.
Manufacturer PN
Wago: 721-104/026-047 (Note 1)
Connector Wire Size
22-12 AWG
Recommended Wire
12 AWG, 600 V (Shielded cable used for CE compliance)
Wire Insertion/Extraction Tool
Wago: 231-131
Connector and tool are included in Connector Kit XTL-FK.
Note 1: For RoHS compliance, append “/RN01-0000” to the Wago part numbers listed above.
Pin Description
Pin
Signal
Function
1
Ground
Chassis ground and cable shield
2
Phase W
Phase W output to motor
3
Phase V
Phase V output to motor (use for DC motor connection)
4
Phase U
Phase U output to motor (use for DC motor connection)