User guide
Xenus Plus User Guide Xenus Plus Filter
Copley Controls 141
D.2: XTL-FA-01 Edge Filter Specifications
Input
Voltage, maximum
373 Vdc
Current, maximum
20 Adc
Output
Voltage, maximum
373 Vdc
Current, maximum
20 Adc
Peak Current/Peak Current Time
40 Adc for 1 second
Rise/Fall Time
500 ns (typical)
Differential Mode Inductance
82 µH per phase, 162 uH phase-phase (nominal)
Common Mode Inductance
220 µH (nominal)
Nominal Resistance
27 milliohms per leg, 54 milliohms phase-phase (nominal)
Agency Approvals
UL508C, EN60204, RoHS
Weight
1 lb. 11 oz.
D.3: Thermal Considerations
Cooling Requirements
When used with XE2/XP2-230-20/800-1782/800-1808, XEL/XML/XPL-230-18 or XEL/XML/XPL-
230-36 drives, the XTL-FA-01 operates below maximum temperature values, and thus requires no
cooling fan.
When used with XEL/XML/XPL-40 drives running continuous currents greater than 12 Adc,
the XTL-FA-01 should be cooled with an external fan. The fan should have a flow rate of at least
110 CFM. The filter has been tested using the Comair Rotron MD24B2 24 Vdc powered fan.
Fan Mounting Guidelines
Most of the filter’s heat is transferred to ambient air, rather than through the heat plate. Thus, it is
very important to mount the filter and fan in such a way that the fan can blow up through the filter’s
cover slots. Mount the filter on edge and mount the fan below it so that it blows up through the
cover slots.
There is no heatsink option for the XTL-FA-01 edge filter.