Submittal Sheet
ZR48K5E-TF5
HFC, R-407C, 60Hz, 3- Phase, 200/230 V
Air Conditioning
Production Status:
Mechanical
Available for sale to all U.S. customers. Please check with your local Emerson Climate
Technologies Representative for international availability.
Evap(°F)/Cond(°F)
Capacity
(Btu/hr)
Power (Watts):
Current (Amps):
EER (Btu/Wh):
Mass Flow (lbs/hr):
Sound Power (dBA):
Vibration (mils(peak-peak)):
Record Date:
45 / 130 50 / 100
46800
4180
62400
2800
12.15 9.20
11.20 22.30
680 769
73 Avg 78 Max
2.0 Avg 3.0 Max
2010-11-16
Number of Cylinders: 0 Displ(in^3/Rev):
Displ(ft^3/hr):Bore Size(in):
Stroke(in):
0.00
0.00
Overall Length (in):
Overall Width (in):
Overall Height (in):
9.69
16.94
9.69
Mounting Length (in):
Mounting Width (in):
Mounting Height (in):
3.87
469.71
7.50
7.50
17.17
Suction Size (in):
Discharge Size (in):
Initial Oil Charge (oz):
Oil Recharge (oz):
Net Weight (lbs):
Internal Free Volume (in^3):
Horse Power:
*Overall compressor height on Copeland Brand Product's specified
mounting grommets.
7/8 Stub
1/2 Stub
34
42
69.1
193.0
Electrical
LRA-High*:
LRA-Half Winding:
LRA Low*:
RLA(=MCC/1.4;use for contactor selection):
RLA(=MCC/1.56;use for breaker & wire size selection):
MCC (Amps):
RPM:
Max Operating Current:
UL File No:
UL File Date:
*Low and High refer to the low and high nominal voltage ranges for which the motor is approved.
114.0
3500
24.0 SA-2337
Performance
17.1
15.4
*
17.50
RG(°F)/Liq(°F) 65.0 / 115.0 70.0 / 85.0
Alternate Applications
Refrigerant Freq (Hz) Phase Voltage Application
R-407C HFC 50 3
200/220 Air Conditioning
R-22 HCFC 50 3
200/220 Air Conditioning
R-22 HCFC 60 3
200/230 Air Conditioning
Page 1 Of
1
Public CROPI Public
03/04/2015
Copyright © 2010 Emerson Climate Technologies, Inc. All rights reserved.