Installation manual
Coopra Advanced Heating Technologies Installation manual 40 EN
20
4.12. Menu structure
By pressing the set/reset button in for longer than 5 seconds, you go to the ‘mode’ menu.
To change the subsequent "Letter" parameter, the user must press the Set/Reset button.
To change the “Range” setting in the parameter, the user must press the “+” or the “–“ button.
Letter Description Range Factory setting Field of application
C
max. set point of central heating 25°C - 90°C 82°C
O
Central heating post-running time 1 - 25 min, CO = 24 hours 5 min
P
Max central heating capacity 33 – 100 % 80 %
H
Type of application
0 = central heating unit
1 = n.a.
2 = for external HWS cylinder 12kOhm
3 = for external HWS cylinder 10kOhm
4 and 5 = all functions are blocked
unit-dependent unit-dependent
d
t
b
Set point for storage HWS cylinder 40°C -70°C 60°C
external storage
vessel
O/b
Basic temperature
External characteristic
10 -70°C 20°C
O/S
Slope
External characteristic
1-100 20
O/d
Day reference temperature 0°C -70°C 20°C
These three settings
are only active when
an external sensor is
connected
r
Factory setting
= Factory setting
= Changed factory setting
If you switch back to the factory setting,
this has no effect on the H, S and P/S
settings
S
Pump speed
00 = automatic
= always high
= always low
00 = automatic
P/S
Maximum pressure jump
= 0.54
= 0.53
= 0.52
= 0.54
In the View mode, you can read the actual values of:
8 = Water pressure (in bar)
1 = Flow temperature (in °C)
2 = Return temperature (in °C)
3 = Inlet cold water temperature / HWS sensor (in °C)
4 = External temperature (in °C)
5 = External cylinder temperature (in °C)
6 = Flue gas temperature (in °C)
7 = Flame signal (in μA DC)
9 = Last interlock
A = Last blocking