UL Listed Range Fire Systems
ONE COOPER Every day, thousands of people all over the world use products made by Cooper Industries. As a premier global manufacturing company, we believe that great brands are built on high quality and excellent service. Which is why our brands have earned leading positions in the markets we serve. Cooper Safety specialises in products designed to save lives and protect property in commercial, industrial and residential buildings.
Contents 4 5 7 11 15 19 21 29 41 Introduction Control Panels Repeater Panels Addressable Sensors Conventional Detectors Addressable Pull Stations Horns/Strobes Interfaces Mini Modules 3
About us Cooper Safety Fire Systems Cooper Fire offers a comprehensive range of UL listed fire detection products suitable for a wide range of projects, from a small simple installation to a large complex multi building site. Fire detection systems are marketed under the Cooper Fire, Menvier and JSB brands. Cooper Fire manufacturer a wide range of products and offers complete fire solutions, not just individual components.
UL Product Range ULDF6000 & ULDF6000RM Control Panels Overview Benefits The Menvier ULDF6000 is a high specification analogue, wall or rack mounted, UL Listed fire system available in various loop configurations. It combines sophisticated functionality with simple operation and aesthetically pleasing design.
ULDF6000 & ULDF6000RM Control Panels Technical Specification Code ULDF6000 and ULDF6000RM Discription UL Analgue Control Panel Standards UL864 9th edition Primary Operating Supply 120/240 V, 60 Hz, 2.0 A Supervised Secondary Operating Supply Battery Voltage Dimensions (Plastic) Dimensions (Metal) D2 D2 W W H H 24 V dc Battery Charge Current 1.0 A (max) Battery Derating Factor 0.
UL Product Range ULDF6000PR Passive Repeater Panel 2 x 40 backlit LCD display and 6 supervisory LED’s Overview Features The ULDF6000PR passive repeater panel, is a cost effective system which can be programmed via its informative display to be either fully passive (display only) or semi passive (restricted system control).
ULDF6000PR - Passive Repeater Panel Technical Specification Code ULDF6000PR Description Passive Repeater Panel Standards UL864 9th edition Standard Connections System Indicators LED’s Power on, Alarm, Trouble, Test, Supervisory, Scroll LED’s Mains Input, Supervised Voltage 120 V ac to 240 V ac, 60 Hz Current 35 mA SLC Field Wiring Current 0.354 mA Wiring Gauge 12 (max) AWG Wiring Class Class A Style 7 Ground Fault 0.
UL Product Range ULDPTR6000 Network Repeater Panel, Touch Screen Overview Benefits The ULDPTR6000 repeater panel provides sophisticated ‘touch screen’ functionality yet achieves a simple end-user interface operation within a compact panel design.
ULDPTR6000 Repeater Panel, Touch Screen Technical Specification Code ULDPTR6000 Description Repeater Panel, Touch Screen Standards UL864 9 edition, NFPA 70-72 Mounting the Backbox 270.00 141.80 128.20 th System Indicators LED’s Power on, Alarm, General Trouble, General Supervisory, Power Trouble, System Trouble, Test, NAC Trouble. 120 V ac to 240 V ac, 60 Hz Current 100 mA Network SLC 5 V dv, 11 mA (max) Line impedance 50 ohm (max) 345.00 Voltage 229.
UL Product Range Addressable Sensors Addressable Sensor, Optical (UCAP320) Addressable Sensor, Opto-Heat (UCAPT340) Addressable Sensor, Multi-Mode Heat (UCAH330) Overview Features Photoelectric smoke sensor (opto) is suitable for most applications giving the fastest response to slow burning or smouldering fires which give rise to large visible smoke particles.
Addressable Sensors Technical Specification Code UCAP320 UCAPT340 Description Addressable Sensor, Optical Addressable Sensor, Opto-Heat UCAH330 Addressable Sensor, Multi-Mode Heat Standards UL268 UL268 UL521 Supply Ratings Working Voltage 18 V dc to 30 V dc 18 V dc to 30 V dc 18 V dc to 30 V dc Voltage Waveform Filtered dc +/- 1 V (max), ripple @120Hz Filtered dc +/- 1 V (max), ripple @120Hz Filtered dc +/- 1 V (max), ripple @120Hz Standby Current 220 μA (average) 220 μA (average) 220
UL Product Range UCAB300 Addressable Sensor Base Addressable Sensor, Opto-Heat (UCAPT340) Addressable Sensor, Optical (UCAP320) Overview Features The UCAB300 has been specifically designed to be compatible with UL range of analogue sensors. • Additional space for termination • Dedicated earth terminal • Secure closure This standard base is designed for flexibility, simplicity and speed of installation.
UCAB300 - Analogue Sensor Base Installation Utilising Locking Tab Wiring Hints Mounting base includes an optional feature to prevent the removal of the detector without the use of a tool. • Each terminal is suitable for clamping up to 2 wires. • Clamping of 2 wires of very different diameters under one screw is not commended. • Suitable for mounting to mounting boxes with 50-80mm fixing centres. 1. Remove the standard fit retaining clip. 2.
UL Product Range Conventional Detectors Conventional Detector, Optical (UCPD-2W) Conventional Detector, Opto-Heat (UCPT-2W) Conventional Detector, Multi-Mode Heat (UCHT-2W, UCHTI-2W, UCHR-2W, UCHRI-2W) Overview Features Photoelectric smoke detector (opto) is suitable for most applications giving the fastest response to slow burning or smouldering fires which give rise to large visible smoke particles.
Conventional Detectors Technical Specification Code UCPD-2W UCPT-2W UCHT-2W UCHTI-2W UCHR-2W Description Conventional Detector Conventional Detector Conventional Detector Conventional Detector Conventional Detector Conventional Detector Optical, 2 Wire Opto-Heat, 2 Wire Fixed Heat, 135ºF, 2 Wire Fixed Heat, 194ºF, 2 Wire Rate of Rise & Fixed Heat Rate of Rise & Fixed Heat 135ºF, 2 Wire 194ºF, 2 Wire UL268 UL268 UL521 UL251 UL251 UL251 Working Voltage 15 V dc to 30 V dc 15 V dc
UL Product Range CB2E & CB Conventional Detector Bases Conventional Detector, Optical (UCPD-2W) CB - Wide Base Conventional Detector, Opto-Heat (UCPT-2W) Overview Features The CB2E and CB have been specifically designed to be compatible with UL range of conventional detectors. • Additional space for termination • Dedicated earth terminal • Secure closure Both bases have been designed for flexibility, simplicity and speed of installation.
CB2E & CB - Conventional Detector Bases Installation Utilising Locking Tab Wiring Hints Mounting base includes an optional feature to prevent the removal of the detector without the use of a tool. • Each terminal is suitable for clamping up to 2 wires. • Clamping of 2 wires of very different diameters under one screw is not commended. • Suitable for mounting to mounting boxes with 50-80mm fixing centres. 1. Remove the standard fit retaining clip. 2.
UL Product Range Addressable Pull Stations UMPS-400X - Pull Station, Explosion Proof UMPS-100 / UMPS-100WP / UMPS-200 - Pull Station Overview Features This range of manual pull stations are constructed of high quality, die-cast metal for long lasting performance and may be mounted on a single gang backbox.
Addressable Pull Stations Installation Standard Connection The Series MPS Pull Station may be surface mounted indoors with a separately ordered backbox option or flush mounted on a standard single gang switch plate. In either case be sure to follow local codes and regulations. To comply with ADA standards the Pull Station must be less than 48 inches above the floor for front wheelchair access, and less than 54 inches above the floor for side wheelchair access.
UL Product Range HNR & HNWC Horns HNWC - Horn, Ceiling Mount HNR - Horn, Wall Mount Overview Benefits The UL range of notification devices are designed to exceed your expectations and offer the most polished, feature rich and cost effective solution. • Up to 48% savings in current draw over similar products,with the latest horn/strobe products you can install more appliances per a given circuit.
HNR & HNWC - Horns Dimensions - Wall Technical Specification W D Code HNR HNWC Description Horn, Wall Mounted Horn, Ceiling Mounted Standards UL Standard 1971 & UL Standard 464 UL Standard 1971 & UL Standard 464 90/95/99 dBA) 90/95/99 dBA) Operation 12/24 V dc H Environmental Operating Temperature 0°C to 49°C 0°C to 49°C Humidity (Non Condensing) 0 to 93 %RH 0 to 93 %R Menvier UL fire systems Menvier UL fire systems Compatibility Suitable for use with H (mm) 133 W (mm) 116 D (mm
UL Product Range HSR & HSWC Horn Strobes HSWC - Horn Strobe, Ceiling Mounted HSR - Horn Strobe, Wall Mounted Overview Benefits The UL range of notification devices are designed to exceed your expectations and offer the most polished, feature rich and cost effective solution. • Up to 48% savings in current draw over similar products, with the latest horn/strobe products you can install more appliances per a given circuit.
HSR & HSWC - Horn Strobes Dimensions - Wall Technical Specification W D Code HSR HSWC Description Horn Strobes, Wall Mounted Horn Strobes, Ceiling Mounted Standards UL Standard 464 UL Standard 464 15/1575/30/75/95/110/135/185 cd, 90/95/99 dB(A) 15/30/60/75/95/115/150/177 cd, 90/95/99 dB(A) Opperation 12/24 Vdc H Environmental Operating Temperature 0°C to 49°C 0°C to 49°C Humidity (Non Condensing) 0 to 93 %RH 0 to 93 %RH Menvier UL fire systems Menvier UL fire systems Compatibility
UL Product Range STR & STWC Synchronised Strobes STWC - Synchronised Strobe, Ceiling Mounted STR - Synchronised Strobe, Wall Mounted Overview Benefits The UL range of notification devices are designed to exceed your expectations and offer the most polished, feature rich and cost effective solution. • Up to 48% savings in current draw over similar products, with the latest horn/strobe products you can install more appliances per a given circuit.
STR & STWC - Synchronised Strobes Dimensions - Wall Technical Specification W D Code STR STWC Description Synchronised Strobes, Wall Mounted Synchronised Strobes, Ceiling Mounted Standards UL Standard 1971 UL Standard 1971 15/1575/30/75/95/110/135/185 cd 15/1575/30/75/95/110/135/185 cd Opperation 12/24 Vdc H Environmental Operating Temperature 0°C to 49°C 0°C to 49°C Humidity (Non Condensing) 0 to 93 %RH 0 to 93 %RH Menvier UL fire systems Menvier UL fire systems Compatibility Suit
UL Product Range RSSWP-2475W-FR & RSSWP-2475C-FW Synchronised Strobes, Outdoor RSSWP-2475C-FW Synchronised Strobe, Ceiling Mounted, Outdoor RSSWP-2475-FR Synchronised Strobe, Wall Mounted, Outdoor Overview Benefits The UL range of notification devices are designed to exceed your expectations and offer the most polished, feature rich and cost effective solution.
RSSWP-2475W-FR & RSSWP-2475C-FW - Synchronised Strobes, Outdoor Dimensions W Technical Specification D Code RSSWP-2475W-FR RSSWP-2475C-FW Description Synchronised Strobes, Wall Mounted, Outdoor Synchronised Strobes, Ceiling Mounted, Outdoor Standards UL1638 & UL1971 UL1638 & UL1971 Synchronisation strobe 75 cd Synchronisation strobe 75 cd Operation H Environmental Operating Temperature -40°C to 60°C -40°C to 60°C Humidity (Non Condensing) 0 to 95 %RH 0 to 95 %RH Menvier UL fire systems
UL Product Range ULCS354 4 Way Sounder Controller Unit Overview Features An extensive range of interfaces are available to support the Menvier range of UL control panels, providing solutions for most design requirements. • Quick and simple to install • Avoids the need to wire conventional sounders back to the main panel • 4 separate sounder circuits (0.
ULCS354 - 4 Way Sounder Controller Unit Technical Specification Code ULCS354 Description 4 Way Sounder Controller Unit Standards UL864 9th edition Signalling Line Circuit Installation 1. Remove the cover of the unit. 2. Fit the back-plate in position and pass the wires into it taking care not to damage the circuit board. 3. Connect the unit according to the diagram below. Style 7, Class A, Supervised, Power Limited SLC Current 0.417 mA to 5.
UL Product Range ULCZMU352 Zone Monitor Unit Overview Features An extensive range of interfaces are available to support the Menvier range of UL control panels, providing solutions for most design requirements.
ULCZMU352 - Zone Monitor Unit Technical Specification Code ULCZMU352 Description Zone Mointor Unit Standards UL864 9th edition Signalling Line Circuit Style 7, Class A, Supervised, Power Limited Load Current 4.9 mA to 5.0 mA Supply Voltage 24 V dc Detector Zone Style C, Class B, Supervised, Power Limited Voltage 21 V dc to 26 Vdc, 22.9 V dc (nom) Current (Alarm) 17 mA to 40 mA Line Impendance 2.5 Ω (max) End of Line Resistance 6.6 kΩ Fire Input Trigger 680 Ω Installation 1.
UL Product Range ULCSUM355 Shop Monitor Unit Overview Features An extensive range of interfaces are available to support the Menvier range of UL control panels, providing solutions for most design requirements.
ULCSUM355 - Shop Monitor Unit Technical Specification Code ULCSUM355 Description Shop Mointor Unit Standards UL864 9th edition Signalling Line Circuit Style 7, Class A, Supervised, Power Limited Voltage 24 V dc Current 4.9 mA to 5.0 mA Line Impedance 50 Ω (max) Style C, Class B, Supervised, Power Limited Voltage 21 V dc to 26 V dc, 22.9 V dc (nom) Current (Alarm) 17 mA to 40 mA 2.5 Ω (max) End of Line Resistor 5.6 kΩ Fire Input Trigger 680 Ω 1. Separate the two halves of the unit. 2.
UL Product Range ULCSI350 Spur Isolator Unit Overview Features An extensive range of interfaces are available to support the Menvier range of UL control panels, providing solutions for most design requirements.
ULCSI350 - Spur Isolator Unit Technical Specification Code ULCSI350 Description Spur Isolator Unit Standards UL864 9th edition Signalling Line Circuit Style 7, Class A, Supervised, Power Limited Voltage 24 V dc Current 0.30 mA to 0.33 mA Spur Output Installation 1. Fit the unit in position. 2. Connect the unit according to the diagram below. Note: A spur isolator unit must be used when making spurs from the analogue addressable panel loop.
UL Product Range ULCIO351 3 Channel I/O Unit Overview Features An extensive range of interfaces are available to support the Menvier range of UL control panels, providing solutions for most design requirements.
ULCI0351 - 3 Channel I/O Unit Technical Specification Code ULCIO351 Description 3 Channel I/O Unit Standards UL864 9th edition Signalling Line Circuit Style 7, Class A, Supervised, Power Limited Operating Voltage 24 V dc Current 1.4 mA to 1.36 mA Line Impedance 50 Ω Installation 1. Separate the two halves of the unit. 2. Drill out (or knock out) the required cable entries in the surface mounting back-box. 3. Fit the back-box in position and pass the wires into it. 4.
UL Product Range ULCMIO353 120 V / 230 V Relay Unit Overview Features An extensive range of interfaces are available to support the Menvier range of UL control panels, providing solutions for most design requirements. • Quick and simple to install • Soft addressed • Only takes a single address • Integral short circuit isolator The ULCMIO353 120 V / 230 V relay unit enables simple interfacing between the fire system and other equipment such as nurse call systems or access control systems.
ULCMIO353 - 120 V / 230 V Relay Unit Technical Specification Code ULCMIO353 Description 120 V / 230 V Relay Unit Standards UL864 9th edition Signalling Line Circuit Style 7, Class A, Supervised, Power Limited Voltage 24 V dc Current 335 µA to 395 µA Line Impendance 50 ohm Output 1 (Programmable) Voltage 120 V ac to 230 V ac Contact Rating 1 A Resistive Power Factor 1 Environmental Operating Temperature 0°C to 49°C Humidity (Non Condensing) 0 to 93 %RH Physical Dimensions (W x H x D)
UL Product Range ULMIU872 Micro Zone Monitor Unit Overview Features An extensive range of interfaces are available to support the Menvier range of UL control panels, providing solutions for most design requirements.
ULMIU872 - Micro Zone Monitor Unit Technical Specification Code ULMIU872 Description Zone Mointor Unit Standards UL864 9th edition Installation 1. Fit the box in position using the mounting details below. 2. Connect the unit according to the diagram below. 3. The ULMIU872 module can be fitted inside a junction box. 4. Up to 3 ULMIU872 modules can be fitted inside the FIBOX as per diagram below. Signalling Line Circuit Style 7, Class A, Supervised, Power Limited Voltage 24 V dc Current 4.
UL Product Range ULMCOM & ULMCOM-S Mini Single Channel Output Units ULMCOM-S - Identified by panel as sounder UL approved micro interface Overview Features An extensive range of interfaces are available to support the Menvier range of UL control panels, providing solutions for most design requirements.
ULMCOM & ULMCOM-S - Mini Single Channel Output Units Technical Specification Installation Code ULMCOM and ULMCOM-S Description Single Channel Output Units Standards UL864 9th edition Signalling Line Circuit Style 7, Class A, Supervised, Power Limited Current 0.322 mA (max) Output Relay 1. Fit the box in position using the mounting details below. 2. Connect the unit according to the diagram below. 3. The ULMCOM & ULMCOM-S modules can be fitted inside a junction box. 4.
UL Product Range ULMCIM & ULMCIM-C Mini Single Channel Input Units ULMCIM-C - Identified by panel as callpoint UL approved mico interface Overview Features An extensive range of interfaces are available to support the Menvier range of UL control panels, providing solutions for most design requirements.
ULMCIM & ULMCIM-C - Mini Single Channel Input Units Technical Specification Installation Code ULMCIM and ULMCIM-C Description Single Channel Input Units Standards UL864 9th edition Signalling Line Circuit Style 7, Class A, Supervised, Power Limited Current 332 µA Operating Voltage 24 V dc 1. Fit the box in position using the mounting details below. 2. Connect the unit according to the diagram below. 3. ULMCIM & ULMCIM-S module can be fitted inside a junction box. 4.
UL Product Range Conditions of sale All goods supplied are subject to the company’s general conditions of sale which are available on request. Trade Descriptions All descriptions represent only particulars of the goods to which they apply and do not form part of any contract. The company reserves the right to change specification without prior notification or public announcement. ®2010 Menvier All rights reserved.
Abu Dhabi Cooper Middle East P.O. Box 53234, Karama Villa 4 opp. Govt. Dept. Sports Association, Sector 2-17 Street 6 (off Delma St No.