Specifications

82
Ultimate Conventional Range
Remote annunciator
The main control panel has a built-in annunciator and
additionally supports up to eight remote annunciators.
These have the same control and display layout so as
to match the appearance of the built-in annunciator.
They have two levels of user codes therefore limiting the
operating system programming to authorised personnel.
The annunciator has a 4 line with 64-character backlit LCD
providing easy-to understand system messages and has an
end-user, friendly membrane keypad as well as 5 system status
LEDs for Alarm, Supervisory, Trouble, Silence and ac power.
The annunciator enclosure can be surface or flush mounted.
Features
> 64-character backlit LCD display
(4 lines with 16 characters on each line)
> Membrane Keypad
> Accepts user codes or fire fighter’s key (Optional)
> Larger keypad buttons for system Reset and Silence
> Install up to eight per FACP
> RS-485 interface to panel
> On-board Piezo sounder audibly indicates Alarms,
Troubles and Supervisories
> Five status LEDs for Alarm, Supervisory, Trouble,
Silence and ac power conditions
> Wiring lengths up to 3300 ft. from the FACP
(depending on wire gauge and number of devices on RS485)
Technical Specifications
Standards NFPA 72; UL864
Model ULREP
Max Per System: 8
System Operating Voltage 16 - 26V dc
Standby Current 12 mA max
Alarm Current 30 mA
Wiring Distance 3,300 max. from FACP (depending on wire gauge and number of devices on the RS 485)
Environmental Operating Temperature 32ºF –120ºF (0ºC – 49ºC)
Humidity 10% – 93% non-condensing
Product Codes
ULREP Remote Annunciator
110616_Cooper fire catalogue_2010:Layout 1 22/2/10 08:55 Page 82