Specifications

Technical Specifications
Model UBFP2ZBW UBFP4ZBWHMO UBFP8ZBWHMO
Standards EN54-2: 1998 & EN54-4:1998 EN50130-4: 1996 EN500081-1: 1992 & EN61000-2-2: 1994
Number of zones 248
Detectors/sounders per zone 20-20
Alarm circuit load 150mA per zone
End of line devices Active end of line monitoring unit
Auxiliary fire signal/fault o/p 1A 24V dc single pole changeover contacts
HMO facility N/A Yes (all zones)
Mains input voltage 230V ac –10% +15%
System operating voltage 24V dc
Standby duration 24 hours
Battery (sealed lead acid) 1 x 2.1 Ah 12V 1 x 3.2 Ah 12V 2 x 3.2 Ah 12V
Recharge period 24 hours
Panel construction Polycarbonate housing & back box
Cable entries Top: 12 x 20mm entries with blanking plugs, rear cable entry aperture.
Environmental rating IP30. -5°C to +40°C Humidity 75% max (non condensing)
Dims WxHxD (mm) 260 x 212 x 72 332 x 270 x 92
63
Bi-Wire Panels
Bi-Wire Range
The new Cooper range of Bi-Wire panels are designed
with Cooper patented 2 wire technology (Patent Number
GB2293257) and also includes ‘Self-Check’ detector
features. Bi-Wire conventional detectors, sounders, LED
strobes, including relay modules, all share the same zone
wiring, delivering significant cost savings in both cable
and installation costs.
All panels have the facility to flash detector LED’s in a zone to
facilitate the location of any wiring fault in that zone, thereby
simplifying the fault finding process. The 4 and 8 zone panels
provide enhanced features, which includes HMO programming
per zone via the easily accessible DIP switch. If a Zone is
programmed for HMO and a fire occurs in that zone, only the
sounders in that zone will sound, if the fire is cleared within
2 minutes, the panel will reset automatically, otherwise the
sounders in all the zones will operate.
Features
> Available in 2, 4, and 8 zones
> Self-Check features as standard
> Detectors, sounders and relay modules share same wiring
> HMO facility and repeater output on 4 and 8 zone panels
> Class change facility
> Selectable fire/fault relay
> Supports up to 20 sounders and 20 ancillaries per zone
> Detector removal indication as standard
> Maintenance-free poly switch circuit protection
> Weekly test/walk test facility
4 and 8 zone
2 zone
Product Codes
UBFP2ZBW 2 zone panel
UBFP4ZBWHMO 4 zone panel
UBFP8ZBWHMO 8 zone panel
FXRP2200BW Repeater panel