Specifications

59
Beam Detection/Callpoints
CX Series
Callpoints – CX201 and CX203
> Approved to EN54 -11
> Convenient clip fixed front cover
> One key for test and cover removal
> Available as flush, surface
and weatherproof (IP65)
CX201 CX203
Technical Specifications
Model CX201 CX203
CPD Approval 0832CPD084 0832CPD085
Configuration Series resistor 680Ω
Rating 24V dc
Connection 4-way terminal block
Operating method Glass element with safety film
Test facility Unique key
Construction ABS
IP Rating IP42 IP67
Temp -25°C to +55°C
Dimensions WxHxD (mm) 86x86x20(S) 53(F) 110x110x65
Weight 0.19kg 0.29kg
Beam detection
The Cooper zone powered reflective beam detectors
are specifically designed to function with all Cooper
conventional panels.
Two versions are available, one with a range of up to 50 Metres,
the other with a range of 50 - 100 Metres. The units are extremely
simple to install and require no separate power supply.
Duct probe
The Duct Probe unit is designed for use with the Cooper range of
conventional optical smoke detectors.
The presence of smoke in a ventilation duct is detected by sampling the
airflow through the duct via two sampling tubes . A detector and base are
mounted within the sampling chamber, which is located on the external
skin of the duct, with sample and exhaust probes passing into the duct in
an area of low turbulence. The unit requires a conventional optical detector
and base and is supplied with full fixing instructions.
MBD50R
MDP201
Product Codes
MBD50R Reflective beam detector (5-50 metre range)
MBD100R Reflective beam detector (50-100 metre range)
MDP201 Duct mounting probe
CX201 Callpoint-surface
CX203 Callpoint-weather resistant
CXPC Polycarbonate cover (pk of 10)
UBSG Spare glass (pk of 5)