Specifications

57
Conventional Panels
FX2200 Range
The FX2200CF range of conventional panels provide a
simple yet effective installer and end user conventional
fire detection system solution. Available as 2, 4 and
8-zone panels, with the 8-zone panel being configured
for the provision of a repeater panel output as well as
two additional alarm line outputs.
Features
> BOSEC 3rd party approved to latest:
EN54-2 1997, A1: 2006
EN54-4 1997, A1: 2002 and A2: 2006
> Choice of 2, 4 and 8-zone panels
> Single 12V dc battery requirement for 24-hour standby
> Single keypad access code for end user and engineer use
> Selectable fire/fault relay
> Class change facility
> Supports up to 32 detectors on each zone
> ‘Same style’ repeater panel available for 8-zone panel
> Simple ‘one shot’ end user test facility
> Maintenance free poly switch circuit protection
> Custom configured versions available of 2 and 4 zone panel
Technical Specifications
Model FX2202CF FX2204CF FX2208CF
Standards EN54-2 1997, A1: 2006 EN54-4 1997, A1: 2002 & A2: 2006
Number of zones 248
Detectors per zone 32
Number of alarm circuits 24
Alarm circuit load 150mA per circuit 0.3A total 400mA per circuit 0.8A total 500mA per circuit 2A total
End of line devices Detection circuits: EOLM1 monitoring unit. Alarm lines: 6.8K resistor
Auxiliary fire signal 5A 24V dc single pole
/ fault output changeover contacts
Auxiliary dc output 24V dc fused. 30mA
Repeater port No Yes
Mains input voltage 230V ac –10% +15%
System operating voltage 24V dc
Standby duration 24 hours
Battery (sealed lead acid) 1 x 3.2 Ah 2 x 3.2 Ah
Recharge period 24 hours
Panel construction Polycarbonate housing & back box
Cable entries Top: 12 x 20mm entries with blanking plugs - Rear cable entry aperture
Environmental rating IP30. -5°C to +40°C humidity 75% max (non condensing)
Surface dimensions WxHxD (mm) 332 x 270 x 90mm
Product Codes
FX2202CF 2 zone panel
FX2204CF 4 zone panel
FX2208CF 8 zone panel
FXRP2200CF Repeater panel
NOTE: Repeater Panels available on standard 8 zone fire panels and configured on 2 & 4 zone fire panels
110616_Cooper fire catalogue_2010:Layout 1 22/2/10 08:54 Page 57