Specifications

3
CF3000
The Cooper CF3000 range of panels offer a
high-specification, analogue fire detection panel solution
which is available in a 1, 2 or 4-loop configuration.
It combines sophisticated functionality, yet simple panel
operation with a very aesthetically-pleasing design.
The large capacity, ability to support complex cause and effect
programming and wide range of user-controllable functions
make this panel suitable for a wide range of projects from
sheltered housing to large office developments as well as many
industrial applications.
The CF3000 range of panels provide a large (120mm x 90mm)
touch screen display as the main user element, eliminating the
need for dedicated system push buttons. The user interface is
menu-driven, automatically reconfiguring to suit the chosen
menu option. To enable text updates directly at the panel, the
display converts to a full QWERTY keyboard, enabling
comprehensive text insertion.
The panel also has 96 zone fire LEDs providing additional
information about the extent of any fire activation as well as
a comprehensive set of system status LEDs providing
additional visual information for the end user.
The panels use ‘spur tolerant’ soft addressing to minimise
installation time and remove the potential for error normally
associated with manual addressing.
All of the CF3000 fire detection system components have been
specifically designed to operate as part of an integrated system;
this provides an assurance that the panel, sensors, interfaces
and other ancillaries are all fully compatible with each other
and that the full range of system functionality is supported by
each device.
Analogue panels
Product Codes
CF30001G 1-Loop panel
CF30002G 2-Loop panel
CF30004G 4-Loop panel
CF30001GP 1-Loop panel c/w integral printer
CF30002GP 2-Loop panel c/w integral printer
CF30004GP 4-Loop panel c/w integral printer
CF30001GNC 1-Loop panel c/w network card
CF30002GNC 2-Loop panel c/w network card
CF30004GNC 4-Loop panel c/w network card
CF30001GPNC 1-Loop panel c/w integral printer, network card
CF30002GPNC 2-Loop panel c/w integral printer, network card
CF30004GPNC 4-Loop panel c/w integral printer, network card
NOTE:
Extended battery versions (EB)
Features
> LPCB 3rd party approved to latest:
EN54-2 1997, A1: 2006
EN54-4 1997, A1: 2002 and A2: 2006
> VdS, BOSEC, CNBOP Certified
> Choice of 1, 2 and 4-loop panel options
> Large multi functional touch screen
> Spur tolerant soft addressing
> Short circuit isolators incorporated into each loop device
> Up to 200 addresses per loop
> Fully monitored network capable up to 127 panels
> Network compatible with CF1000 range and CF2000
range of panels
> Optional integral printer
0832-CPD-1061