Specifications

50
Emergency Voice Communication - Outstations
Typical application schematic
Technical Specifications
Power Supply and Charger
ac input 230Vac +/- 10% 50/60Hz
Internal power supply 14V dc
Supply & battery monitored, open, short, fuses
Protection Deep discharge, short, thermal
Temperature compensation YES
Battery size and type 1 x 12V 4.2Ahr
Mains fuse 240V 2A HRC
Battery fuse 1A PTC
Max charge current 250mA
Inputs
Number of lines 5
Remote enable Short to use
End of line 10kΩ
Outputs
Number 2, fault & in-use
Type Volt free relay
Contact 30V dc 1A
Controls
Buttons 5 Zone keys, 1 acknowledge
Zone LEDs (x5) 1 Line status,1 fault status
Fault LEDs 3, ac, dc general
Outstation Cables
Height 300mm
Width 350mm
Depth 90mm
Weight 6.5kg
110616_Cooper fire catalogue_2010:Layout 1 22/2/10 08:54 Page 50