Specifications

18
Test equipment
LP800 Loop tester
Product Codes
LP800KIT Loop tester
CF800PROG Programmer
The LP800 loop tester is a hardware /software
combination that can be used to test, commission and
fault find a loop of up to 200 Cooper analogue devices
(detectors, sounders, ancillary devices) without having
to connect the loop to the Cooper analogue Fire Panel.
The loop tester is connected between the loop and PC. It allows
the engineer to quickly identify and locate any loop device that
is operating outside its operating conditions by varying the
alarm threshold of any loop device (Alarm, Pre-alarm and fault).
Features
> Pre-addressing: Identifies all Cooper field devices and
determines their address and device type
> Analogue Values: Constantly displays in real time the
analogue value of all cooper loop devices in order to
determine their status
> Test Led: This command operates the LED of any inputs
(detector/call points) as well as controls the outputs of
sounders and output modules
> Device Settings: Analogue values of all devices can be
interpreted according to ranges which can be set and altered
by the user (OK, Pre-alarm, Fire)
> Event Log: A history of events can be stored from the date the
application was started
> Soft addressing: Automatically assigns a new, and potentially
different, address to every device found on the loop
> Powered from 230 Volts main supply
> Support up to 2km of cable including spurs
The loop tester hardware requires a free serial port on the PC,
either internal or via a USB extension, a mains power supply
and a direct connection to the device loop.
The CF800 programmer is a versatile tool to aid the
installation, commissioning, maintenance and servicing
of Cooper addressable devices and fire alarm systems.
Cooper CF800 hand held programmer is designed for
use with all Cooper addressable series 800 devices.
This unit is light, robust and easy to operate using a user friendly
menu structure on 2 x 40 character LCD display. It is powered
from a single PP3 size, heavy duty battery or an external 9 -15
volt supply.
The Programmer has a built in Cooper addressable base as
well as two external loop terminals for use with all other
Cooper ancillary devices.
Features
> Reads addresses
> Writes addresses
> Reads analogue values
> Tests devices
> Deletes addresses
> Programmes the 3 heat settings
(rate of rise, 77°, 92°)
CF800 Programmer