Specifications

15
Interfaces
Interfaces
An extensive range of interfaces are available for the
Cooper range of analogue panels providing solutions
for most design requirements.
> CSI350 spur isolator available to allow loop spurs of analogue
addressable devices
> CIO351 3-channel 24V-rated input / output unit suitable for
switching low voltage control equipment
> CZMU352 zone monitor unit, to connect zones of suitable
conventional detectors or loop powered beam detectors
> CMIO353 mains-rated input / output unit for switching mains
operated equipment
> CSC354 Sounder circuit controller provides four additional,
programmable, conventional sounder circuits remote from
the main control panel
> CSUM355 shop unit isolator allows the connection of a
conventional detection zone along with two conventional
sounder circuits, ideal for linking small self contained units
onto a main addressable panel. The interface requires a
24V dc power supply
CSI350
Spur Isolator unit
CIO351
3 Channel I/O unit
CZMU352
Zone monitor unit
CMIO353
230V Relay I/O unit
CSC354
4 Way sounder controller
CSUM355
Shop unit monitor
MCIM-C
Single input module
MCOM-S
Single output module
MCIM-C
MCOM-S
MCOM-R
Single channel output
relay module
MCOM-R
MICM-NF
Non-fire input
module
MICM-NF
MIU872
Mini-zone monitor
Product Codes
CSI350 Spur Isolator unit
CIO351 3 Channel I/O unit
CZMU352 Zone monitor unit
CMIO353 230V Relay I/O unit
CSC354 4 Way sounder controller
CSUM355 Shop unit monitor
MIU872 Mini-zone monitor
MCIM-C Single input module
MCOM-S Single output module
MCOM-R Single channel output relay module
MICM-NF Non-fire input module
MCIM Input module
MCOM Output module
A range of micro interfaces modules are also available:
> MIU872 is a compact single zone input, soft addressed, micro
interface, incorporating integral short circuit isolators. It is fully
compatible with the current range of Cooper analogue fire
detection panels. It is suitable for interfacing a zone of up to
20 conventional Cooper detectors onto a Cooper analogue fire
panel. It will operate with any Cooper conventional detector in
configuration with a schottky diode type base.
> MCIM-C is a compact input module used to accept input
signals from external equipment such as beam detectors,
flow switches, valve monitor switches etc.
> MCOM-S is a compact single Channel output unit.
This device is identified as a sounder output by a
Cooper addressable panel. The maximum number
of sounder devices per loop is 60.
> MCOM-R is a compact output module used to control or
signal external equipment which require removal of power for
reset purposes.
> MICM-NF is a compact single Channel input unit. This device
is identified as a non-fire input module by the COOPER
addressable panel. The maximum number of addressable
MICM-NF per loop is 200. Complex cause and effect can
still be achieved using the latest site installer software without
any indication on the panel. However the action will still be
seen in the event log. Ideally suited for non fire applications.
Standard Micro