Instruction manual

P84662J Page 4 of 28
1.2 SPECIFICATIONS
Approvals:
UL Listed 864 Standard for Control Units for Fire Protective Signaling Systems
Pending: FM
Pending: MEA approved – NYC Dept. of Buildings
Pending: California State Fire Marshall (CSFM) approved
Pending: Fire Protection Bureau (FPB) Chicago
NFPA 72 compliant
Inputs:
120VAC, 50/60Hz, 5.0 Amps Operating Power in Alarm
24VDC Battery Backup Connection
Two (2), 12V or 24V NAC Initiating Circuits (8-33V at 7mA) FWR or DC
Two (2) “Dry” Contact initiating Circuits
Accepts two (2) Class “A” or two (2) Class “B” circuit inputs
Built in battery charger for sealed lead acid or gel type batteries up to a 20 AH.
Batteries larger than 12 AH will not fit inside cabinet, use of an external battery cabinet is necessary.
Outputs:
NAC outputs are 24VDC, 3.0 Amps each, power limited
8 Amps total alarm current for the unit
Capable of four (4), Class "B" circuits
Capable of two (2) Class “A” circuits
Capable of four (4) Class “A” circuits (with optional PS-4CA module)
Capable of one (1) Class “A” circuit and two (2) Class “B” circuits
Temporal (Code 3) or constant voltage output generation
Built-in Wheelock synchronization mode that can be fed to any or all of the output circuits
Input and output can be synchronized with “IN>OUT SYNC” mode (SM, DSM or 2
nd
PS-24-8MC is
required)
Audible silence capability
Filtered and electronically regulated output
3.5 Amp auxiliary power limited output with reset capability. (Removed upon AC loss or alarm. Automatic
reset 30 seconds after AC power returns or the alarm condition is over) or 200 mAmps auxiliary power
limited output which remains on during AC loss or an alarm condition.
Supervision:
Compatible with 12V or 24V (FWR or DC) FACP
Signaling appliance loops are supervised and steered to either IN1 or IN2
2.2K Ohm, 1 Watt (Wheelock Model #MPEOL) End of Line Resistor (EOLR) for supervision of all outputs
AC loss trouble reported over a separate set of contacts (delay of either 30 seconds)
All troubles are reported over the common trouble contacts (AC loss can have a delay of 30 seconds or
170 minutes)
Automatic switchover to standby battery when AC fails
Thermal and short circuit protection with auto reset
Input and output status LED indicators
AC fail supervision
Battery presence and low battery supervision
Ground Fault Detection (60K ohms)
1.3 TERMINOLOGY
CLASS “A” = STYLE Z
CLASS “B” = STYLE Y
FACP = Fire Alarm Control Panel
EOLR = End of Line Resistor
NAC = Notification Appliance Circuit
AH = Ampere/Hour
SM = Wheelock Sync Module with single output.
DSM = Wheelock Dual Sync Module with two outputs.
C = Common
NC = Normally Closed
NO = Normally Open