i-on160EX Security System Engineering Guide
© Cooper Security Ltd. 2010 Every effort has been made to ensure that the contents of this book are correct. However, neither the authors nor Cooper Security Limited accept any liability for loss or damage caused or alleged to be caused directly or indirectly by this book. The contents of this book are subject to change without notice. Printed and published in the U.K. About this Guide This manual applies to software used in the i-on160EX control unit with version 2.00 software.
i-on160 Contents About this Guide ................................................................................... ii Other i-on160EX Publications .................................................................................. ii Introduction ......................................................................................... 1 System Overview ................................................................................. 1 System Design .....................................................
i-on160 “Setting Options” and “Partitions” Menus ................................................ 52 Part Setting or Partitioned System? ........................................................................ 52 Options .............................................................................................................. 54 Full Set Link........................................................................................................ 56 Calendar Set ..........................................
i-on160 Comms .............................................................................................................. 96 Zone Mapping ..................................................................................................... 97 Non-Programmable Functions ............................................................... 97 Alarm Abort ........................................................................................................ 97 Remote Reset (RedCare Reset) .....................
i-on160 Testing a Proximity Tag: ..................................................................................... 148 Sending a Test Call to an ARC Number: ................................................................ 148 Sending a Test Call to a Speech Dialler Number: .................................................... 149 Log .................................................................................................. 150 Viewing the Log.....................................................
i-on160 Introduction System Overview i-on160EX is the control unit for a hybrid wired/wirefree alarm system intended for commercial use. One i-on160EX control unit can operate up to 160 zones by using expanders communicating over a single bus cable. Different types of expander allow either wired or wirefree detectors in the same system. The single bus cable also allows the installer to connect keypads, output modules or extra power supplies wherever they are needed.
Introduction i-on160 Zone Connections The control unit provides connections for up to 10 wired zones. These zones can be either all Closed Circuit (CC) or all Fully Supervised Loop (FSL). The Installer can select the zone wiring type during initial commissioning, or at any time after. Note that the Installer can make the wiring type of the expanders either CC or FSL, independent of the wiring type of the zones on the control unit.
i-on160 Introduction External Bell Output The control unit has one external bell output to drive standard Self-Activating Bell (SAB) or Self-Contained Bell (SCB) modules. Expanders also provide connectors for additional external sounders. See i-on160EX Installation Guide for details of maximum current available for external bells. Extension Loudspeaker Connectors If required the Installer can connect one 16Ohm extension loudspeaker to increase the audibility of setting and unsetting tones.
Introduction i-on160 handled by an i-on160EX control unit depends partly on the density of radio transmitters within a given volume. If there are more than 30 transmitters within 10 meters radius of an expander then some mutual jamming may occur. Please read “Guidance Notes For Radio Alarm System” available from www.coopersecurity.co.uk. Communications The i-on160EX provides a socket for an add-on communication module. To comply with EN50131 you must fit a module.
i-on160 Introduction Partition Mode. In Partition Mode the i-on160EX provides the equivalent of 20, smaller, independent alarm systems. Each system is a “Partition” of the ion160EX. You can allocate any set of zones to each Partition. Each zone can also belong to more than one Partition. Each Partition can have a Full Set level and one Part Set level. During programming the installer can allocate keypads, sounders or outputs to any of the partitions.
i-on160 Basic Programming Procedures Programming Before Installation If you prefer, you can program the control unit before installing the system in its final location. You will need to temporarily connect a keypad to the control unit. It is possible to operate the control unit from battery power (or a 12Vdc supply) without connecting the unit to a mains supply. However, in order to start the control unit processor running you must briefly short the Kick Start pins together after connecting the battery.
i-on160 Basic Programming Procedures If this happens key in a valid user code (not a Set Only user code see note 1). When you key in the last digit of the access code the display shows “Installer Menu” on the top line. The bottom line shows the first option in the Installer menu: Detectors/Devices. (See note 2.) 3. Detectors/Devices > Press u or n to display more options from the menu. Each option appears on the bottom line of the display in turn, for example: 4.
Basic Programming Procedures i-on160 ready for use. If the control unit finds a device missing, or one with an address that has not been added using the Installer Menu then the display shows, for example: FOUND 0, LOST 1 Lost R1-03 The top line of the display shows the number of new devices found, and the number of existing devices missing (lost). The bottom line of the display shows the first in the list of found and lost devices. 4.
i-on160 Basic Programming Procedures Note that this procedure deletes all radio detector identities. Restoring Factory Defaults 1. Enter the Installer Menu. 2. Press n until the bottom line shows System Options: 3. Press Y . The display shows: 4. Press n until the bottom line shows: 5. Press Y . The display shows: 6. Press n until the bottom line shows: 7. Press Y. The display asks for confirmation. 8.
Basic Programming Procedures 11. Press u or n to display the desired wiring type on the bottom line of the display. 12. Press Y to confirm the selection. i-on160 WIRED ZONE TYPE 4-wire CC The system loads all defaults except for the Log. Note: The log is protected and cannot be erased by the Installer or any user. The display briefly shows: Factory defaults restored Followed by: 13. Press X until the display shows: 14. Press Y. The display shows: The control unit scans the bus.
i-on160 Basic Programming Procedures Defaulting Access Codes If the User and/or Installer codes are lost then you can set the installer and Master User codes to their default and delete all the other users, including their tags, remote controls and PAs. 1. If possible, enter the Installer menu. Note: If you cannot enter Installer Menu then the control unit will start a tamper alarm when you open its lid. 2.
Basic Programming Procedures i-on160 10. Enter Installer Menu and then leave it again. The LEDs around the navigation key should now be green. If they glow red then there may be an alert for a missing battery that needs acknowledgement. 11. To force the control unit to check the battery: Press Y, key in 1234 (or 123456 for Grade 3), press Y again. The navigation key LEDs should now glow green.
i-on160 Basic Programming Procedures To move the cursor left or right press u or n respectively. To delete characters press <. Note: If you wish to leave a name or text unchanged then press X. The display leaves the name change screen and restores the name to its previous value. Press Y when you have finished entering text.
i-on160 The System Bus The system bus carries all the data between the control unit and its expanders and keypads. Electrically the bus is a single set of four conductive paths. Two paths carry dc power and two carry data. Physically the bus cable can connect the devices in either daisy-chain or star arrangements – see Figure 2.
i-on160 The System Bus Delete the device information from within the control unit. Each type of device has its own “delete” command in the Installer menu. Reset the bus address on the device to zero. See page 99 for detailed instructions on adding and deleting bus devices. If a bus device is damaged and you suspect it is faulty then you can use the Installer menu to temporarily disable the device.
The System Bus i-on160 R1-02 R1-03 R1-04 K1-51 EXPR-30 MENU MENU A B 1 4 ghi 2 abc 5 jkl 3 def MENU 6 mno 7 pqrs 8 tuv 9 wxyz * 0 # W1-01 A 1 B 4 ghi 2 abc 5 jkl A 1 B 4 ghi 2 abc 3 def 3 def 5 jkl 6 mno 6 mno 7 pqrs 8 tuv 9 wxyz * 0 # K1-52 7 pqrs 8 tuv 9 wxyz * 0 # K1-53 EXPW10 Figure 4. Bus Device Addressing for EXPR-30. Detector Connection Point Addresses Each connection point for a detector has an address.
i-on160 The System Bus P0<00<02 P0<00<03 R1<02<02 P0<00<01 R1<02<03 P0<00<04 R1<02<01 R1<02<04 R1<02<00 EXPR-10 W1-01 K1-51 MENU MENU MENU A 1 B 4 ghi 2 abc 5 jkl 3 def A 1 B 4 ghi 2 abc 3 def 6 mno 7 pqrs 8 tuv 9 wxyz * 0 # 5 jkl 8 tuv 9 wxyz 0 # A R1-02 6 mno 7 pqrs * 1 B K1-52 4 ghi 2 abc 5 jkl 3 def 6 mno 7 pqrs 8 tuv 9 wxyz * 0 # K1-53 EXPW-10 W1<01<00 W1<01<01 W1<01<4 W1<01<02 detectors W1<01<03 Figure 5.
The System Bus i-on160 Other Radio Device Addressing. For radio keypads, radio sirens and WAMs, during the learning process the installer selects a specific radio expander to learn the identity of the radio device. This means that when programming these devices the control unit refers to them by a number containing three groups of characters (similar to the characters the system uses to refer to zones and outputs): Rn-dd-zz Rn-dd The first two groups are the address of the bus device (see page 15).
i-on160 y y y y The System Bus Carrying out a bus scan does not change the bus configuration. Note that on large systems a bus scan may take some minutes. If you are confident that the control unit has already learned all the devices on the bus you do not have to carry out a bus scan (but it may be a useful check). If you have temporarily removed a bus device you can reconnect it to the bus, provided that you carry out a bus scan and do not change its bus address.
The System Bus Zone 2 -> P0<00<02 i-on160 Zone 3 -> P0<00<03 Zone 1 -> P0<00<01 Zone 4 -> P0<00<04 Zone 22 -> R1<02<02 Zone 23 > R1<02<03 Zone 21 -> R1<02<01 Zone 24 -> R1<02<04 Zone 20 -> R1<02<00 W1-01 EXPR-10 MENU MENU A 1 B 4 ghi 2 abc 5 jkl MENU 3 def A 1 B 4 ghi 2 abc 3 def A 1 B 4 ghi 2 abc 3 def 6 mno 7 pqrs 8 tuv 9 wxyz * 0 # K1-51 5 jkl 6 mno 7 pqrs 8 tuv 9 wxyz * 0 # K1-52 5 jkl 6 mno 7 pqrs 8 tuv 9 wxyz * 0 # K1-53 R1-02 EXPW-10 detectors
i-on160 The System Bus Zone 1 -> P0<00<01 ... Zone 4 -> P0<00<04 Zone 20 -> R1<02<00 ... Zone 49 -> R1<02<29 EXPW-10 EXPR-30 W1-01 MENU MENU A B 1 4 ghi 2 abc 5 jkl 3 def A 6 mno B 1 4 ghi MENU 2 abc 5 jkl 3 def A 6 mno B 1 4 ghi 2 abc 5 jkl 3 def 6 mno 7 pqrs 8 tuv 9 wxyz 7 pqrs 8 tuv 9 wxyz 7 pqrs 8 tuv 9 wxyz * 0 # * 0 # * 0 # K1-51 K1-52 R1-02,03,04 Zone 10 -> W1<01<00 ... Zone 14 -> W1<01<04 K1-53 detectors Figure 8. Zone Numbering with EXR-30.
The System Bus i-on160 Processing Priority When several detectors are activated at the same time, the control unit always processes PA and Normal Alarm detectors first, followed by Fire, and then all other alarm types. The control unit always processes alarms before Alerts. Tampers and the Bus Every device that can be attached to the bus has its own anti-tamper switch.
i-on160 Installer Menu Important: Where noted below the defaults listed enable the control unit to comply with EN50131 requirements. If you change those settings then the installation may no longer comply. If the control unit does not comply with EN50131 you must remove any labelling that indicates compliance. MENU Option Factory Default 1 DETECTORS/ DEVICES Detectors Add/Del Detectors Zone 1-160... Delete all Program Zones Zone 1...
The Installer Menu Partitions Loudspeaker Volume Delete Expander Expander 1-01...1-45 Enable Expander Replace Expander Wired Keypads Address Bus Device Edit Keypad Keypad K1-51...K1-99 Name Partitions Key A Key B Key C Key D Delete Keypad Radio Keypads Add/Del Radio Keypad Edit Keypads Name Partitions Key A Key B Key C Key D External Sirens Add/Delete Ext. Siren Edit external siren WAMs Add/Del WAM Edit WAM Page 24 i-on160 Partition 1 Appears only in a partitioned system. Yes (all expanders enabled).
i-on160 2 OUTPUTS Radio outputs Add Outputs Edit Outputs Exp. R1>nn>01...08 Wired outputs Panel The Installer Menu Name O/P R1>00>01 ... O/P R1>00>08 Name Siren Strobe P0>00>01 P0>00>02 P0>00>03 P0>00>04 Type Not Used Type Siren Strobe Siren Strobe Siren Strobe Polarity Normal Polarity Normal Normal Normal Normal Normal Normal Partitions Exp.
The Installer Menu Part Set B Name Exit Mode Settle time i-on160 “Part Set B” Instant Set Exit time 40s Entry time 45s Alarm Response Part Set Final Exit Part Set Entry Route Strobe on Set Internal+Siren Strobe on Unset Part C, D Calendar Set 3 PARTITIONS Appears only if Exit Mode is “Final Door”. This setting is required in order to comply with EN50131. Appears only if Exit Mode is “Timed Exit” or “Silent Set”. The maximum time permitted by EN50131-1 Clause 8.3 is 45 seconds.
i-on160 The Installer Menu 4 SYSTEM OPTIONS Wired Zone type To comply with EN50131 select this option manually during initial power up. Panel Zones All Zones User Access PA keys active Quick Set 2 Wire FSL 2k2/4k7 Quick Omit User code req’d User reset Zone alarms7 No Zone tampers Yes 2 Wire FSL 2k2/4k7 No No This setting is required in order to comply with EN50131.
The Installer Menu i-on160 Panel Loudspeaker Loudspeaker 1 (2) Volume Partitions 01...20 Yes Entry Alarm Delay Enabled Supervision Jamming Force Set Tamper Omit Enabled CSID Code Silence Alerts Mains Fail Delay 0000 Battery 2 5 COMMUNICATIONS ARC Reporting Enabled Off Disabled This setting is required in order to comply with EN50131. User Code 0 minutes This setting is required in order to comply with EN50131.
i-on160 The Installer Menu Restorals Fire: Yes Panic: Yes Burg: Yes Technical Alarm: No Tampers: Yes Set/Unset: Yes (see Note 2) Part Set: Yes(see Note 2) Reset: Yes (see Note 2) Exit timeout: Yes Omit: Yes RF Supervision: Yes RF Jamming: Yes (see Note 2) RF Battery/PSU: Yes (see Note 2) Panel Battery: Yes (see Note 2) Mains Fail: Yes (see Note 2) Faults: Yes (see Note 2) Installer Mode: Yes (see Note 2) User Code Changed: No Date/Time Reset: No Downloading: No Enabled Burg Comms Rearm Disabled 21CN F
The Installer Menu IP Network (Own) Web Server Status Port number IP Address IP Sub-net mask Gateway IP address GPRS i-on160 Disabled 80 192.168.0.100 255.255.255.
i-on160 Speech Dialler The Installer Menu Only visible when suitable communications module fitted PSU Current Locate Bus Device 7 VIEW LOG 8 ABOUT Panel Comms Module Panel Ethernet Zone mapping Zone Numbers Zone Addresses Page 31
i-on160 Installer Menu Options This section contains reference information for the options provided in the Installer Menu. Detectors/Devices Detectors Adding or Deleting Radio Detectors Add a Radio Detector To The System To learn radio detectors select Detectors/Devices - Detectors – Add/Delete Detectors. See page 110 for detailed instructions. To use a radio zone the control unit must learn the identity of the radio detector.
i-on160 Installer Menu Options Default zone If you select this option then the control unit “forgets” the ID of the detector and sets all the zone programming back to default values: Type = Not Used, no attributes. Note: The deletion will take place immediately, and not when you leave Installer Mode. Program Zones You can program each zone's behaviour at any time, whether or not a wired detector is connected, or the control unit has learned the identity of a radio detector.
Installer Menu Options i-on160 Normal Alarm (03). When triggered, a zone programmed as ‘Normal Alarm’ will start an alarm provided the system is set. When the control unit first learns a radio detector the zone type defaults to Normal Alarm. 24 Hour Alarm (04). Activating this zone causes an internal alarm (keypads and speakers) whether the system is set or unset. Final Exit (05). Zones of this type must be the last detector to be activated on exit, or the first to be activated on entry.
i-on160 Installer Menu Options In a Part Setting system the keyswitch can Full Set or unset. As with Momentary keyswitches, you can allocate the zone to one or more Partitions (see above). When the user closes the keyswitch contacts then the control unit sets the allocated Partition. When the user opens the contacts then the control unit unsets the allocated Partition. Notes: 1.
Installer Menu Options i-on160 Use this zone type to monitor the fault output of an external PSU. (This zone type is available for power supplies that do not provide specific fault outputs that can be used by zone types 11, 12 and 13.) If a power supply triggers a zone with this type then the control unit activates any output programmed as “External PSU Fault” and causes an alert that displays “External power fault” on the keypad.
i-on160 Installer Menu Options Chime When enabled by the user, the system gives a non-alarm warning tone when any zones programmed as ‘Chime’ are opened. This facility operates only while the system is unset. Soak Test Use this zone attribute if you want to place under long term test a detector that you suspect is giving false alarms. Zones with this attribute are disabled for 14 days after you return the control unit to user/unset mode.
Installer Menu Options i-on160 (active) the control unit alerts them and pauses the setting procedure. The user can acknowledge the alert by pressing Y and continue setting. You must enable this feature in the System Options – User Access – Quick Omit menu, see page 61. Note: In a Security Grade 3 system this attribute is defaulted to “No”. If you change the attribute to “Yes” the system will no longer comply with Security Grade 3.
i-on160 Installer Menu Options Note: Cooper Security recommend that you remove all power from the system (battery and mains) before disconnecting any device from the bus. Disabling/Enabling Expanders If you suspect that an expander is faulty, and wish to remove it from service temporarily, then use the Installer Menu option Detectors/Devices – Wired Expanders – Enable Device. (There is a similar option for radio expanders.
Installer Menu Options i-on160 Control the response to tampers for the associated partitions. If any associated partition is set then a tamper will cause an unconfirmed alarm. If there is an outstanding unconfirmed alarm then this will cause a confirmed alarm to be generated. When delivered from the factory, or if you restore the control unit to factory settings, then all expanders belong to partition 1.
i-on160 Installer Menu Options The control unit displays the name you give to the keypad when it is reporting faults or other events, making it easier to locate the affected device. Assigning Wired Keypads to Partitions The i-on160EX allows you to assign keypads to any of the partitions. When delivered from the factory, or if you restore the control unit to factory settings, then all keypads belong to partition 1.
Installer Menu Options i-on160 Notes: 1. If you are working on a system with only one keypad (for example when programming a new control unit before installation) then do not delete the keypad you are using. If you do so then power down and up again in order to make the control unit recognise the keypad. 2. DO NOT hold down D and X to delete a keypad from a system while the keypad is still connected to the bus. Always delete keypads from a system first by using the Installer Menu, see page 102.
i-on160 Installer Menu Options To remove a Radio Keypad from the system Select Detectors/Devices – Radio Keypad – ADD/DEL Radio Keypad. Select the radio expander the keypad is allocated to, followed by the device address of the keypad that you want to delete. See page 118 for detailed instructions. See page 18 for a description of radio keypad numbering. Radio Keypad Naming To name a radio keypad select Detectors/Devices – Radio Keypad – Edit Keypads Name. See page 119 for detailed instructions.
Installer Menu Options i-on160 When delivered from the factory, or if you restore the control unit to factory settings, then all radio sirens belong to partition 1. Once you have entered the Partitions option, press u or n to scroll through the list of partitions followed by > or < to allocate/deallocate the radio siren to each partition as necessary.
i-on160 Installer Menu Options Polarity You change the polarity of either output, to suit the type of equipment that the output must work with. There are two options: outputs. Normal. The output is held at +12V while inactive, and at 0V when activated. Inverted. The output is held at 0V while inactive, and at +12V when activated. Partition In a partitioned system you can assign the outputs to any of the partitions.
Installer Menu Options i-on160 Once a receiver has learned an output from the control unit you must set up the output behaviour at the control unit by giving the output a type. You can also give each output a text name. Output Types You can select an output type quickly by keying the number shown in brackets after the type’s name, for example:“04” to select Open/Close, “02” to select Panic Alarm, “19” to select General Fault. The number does not appear on the keypad display.
i-on160 Type: Installer Menu Options Active when: Assign to Partitions? this output type depends on whether DD243 is on or off: DD243 Confirmation Off – The output does not operate. DD243 Confirmation On – The output activates when a second alarm zone is triggered within the period of the confirmation timer, and in the same partition as the first alarm zone to be triggered.
Installer Menu Options i-on160 Type: Active when: Assign to Partitions? Panel Battery Fault (13) The control unit detects a fault with its backup battery, OR a zone of type “External PSU Battery Fault” has been triggered. If the alert was caused by an “External PSU Battery Fault” zone then the control unit deactivates the output when the zone has been restored and a user has acknowledges the fault by entering a valid access code.
i-on160 Installer Menu Options Type: Active when: Assign to Partitions? Zone Omit (System) (18) (Operates only when DD243 is enabled.) In Yes the event of an unconfirmed alarm, the system will rearm itself when the confirmation timer expires. If the zone that caused the unconfirmed alarm is still active at the time of the rearm, the control unit will omit that zone and activate the output. The control unit will restore the zone and output when a user or engineer resets the system.
Installer Menu Options i-on160 Type: Active when: Assign to Partitions? PIR Set Latch (25) The system or partition is set. Inactive when the system or partition is unset or an alarm condition occurs. The output is active for one second when a reset is performed or when the control unit leaves installer mode. Yes Shock Sensor Reset (26) Exit time starts. The output remains active for five seconds. Use this output to reset shock sensors (for example, the "Viper").
i-on160 Installer Menu Options Type: Active when: Assign to Partitions? Part Set D (37) Setting Part Set D. Deactivated on unsetting Part Set D. (Available only in a Part Setting system) No Set Fail (38) A set command fails. Remains active until the user acknowledges the set fail. Yes Zone Follow (39) A specified zone has been triggered. When you select this type for a zone the display shows an extra “Follow” option for the output.
Installer Menu Options i-on160 In the Installer Menu, while programming a user output type, the control unit gives you the following options: Polarity Polarity can be either Normal or Inverted. This option works the same way as described for Wired Outputs – see page 45. Latched Latched can be either Yes or No. No: The output initially changes state when a user operates the output, but then changes state again after a set time. The time is fixed by the “On Time” option, below.
i-on160 Installer Menu Options The Setting Options sub-menu contains all the options to program entry, exit and alarm response for a single alarm system with a Full Set and three Part Set levels. The Partitions sub-menu is divided into twenty partitions. Each partition behaves like a complete, independent, alarm system. However, each partition has only Full Set and one Part Set. Table 2 on the next page shows the layout of both the Setting Options and the Partitions menus.
Installer Menu Options i-on160 Options Note: The default settings for these options are compliant with EN50131, see page 23. Changes to some of the defaults may render the system noncompliant. Name Use this option to give the Full Set, Part Set, or Partition a name. The control unit displays this name to the user during setting. Exit Mode The exit modes available are: Timed Set Use this option to make the system set after a delay. Use the Exit Time menu (see page 55) to choose the delay.
i-on160 Installer Menu Options before the system sets. This may be needed if detectors are being set off by air movements caused by the final door being closed. During this period, the sounders stop and the system sets but the control unit ignores any alarms generated by the detectors. Enter two digits to specify a time in seconds, from 01 to 30. Note: This option is available for Final Door Set exit mode only. Exit Time The exit time can take any value between 10s and 120s.
Installer Menu Options i-on160 as Normal Alarm zones during part set. In a Partitioned system, any Final Exit zones, belonging to the partition, with the Part Set attribute will act as Normal Alarm zones during part set. Part Set Entry Route As This option controls how the system treats Entry Route zones during part set. Entry Route In a Part Setting system, all Entry Route zones with the Part Set B, C or D attributes will continue to act as Entry Routes during part set.
i-on160 Installer Menu Options Each event specifies: A time on the 24 hour clock One or more days of the week An action (setting, part setting or unsetting). A 12 character name as a reminder of the purpose of the event. An exception (see below). Each exception marks a time period when certain events do not apply. An exception has a start time and date, an end time and date, and a name. You link events to exceptions while programming events – see below.
Installer Menu Options i-on160 Add Exception Use this option to create an Exception. During the time specified by the exception none of the linked events will take place. When you add an exception, the control unit guides you through the following steps: Name. Key in a 12 character name. Give the exception a meaningful name that will remind you of its purpose when you are linking events to exceptions. Exception Start Time. Key in the start time in 24 hour format.
i-on160 Installer Menu Options At the end of the calendar set warning time the control unit stops the warning tone, sets the affected partition(s) without any further delay, deactivates any “Autoset Warning” outputs and activates any “Set” outputs. The system logs a calendar set as “system auto set” along with the affected partition number. Deferring Setting. During the calendar set warning time a user can interrupt or cancel the setting process.
Installer Menu Options i-on160 2. If you are unsetting a partition and setting the same partition again then you must program the setting event to occur at least 10 minutes after the unsetting event. System Options This section of the Installer Menu contains a series of options that affect the working of the alarm system as a whole. Note: The default settings for these options are compliant with EN50131, see page 23. Changes to some of the defaults may render the system noncompliant.
i-on160 Installer Menu Options PA Keys Active This option allows users to start an alarm from the keypads by pressing both the Panic Alarm keys at the same time. This option applies to all keypads, both radio and wired, and is not affected by allocating keypads to specific partitions. Yes The PA keys on all keypads are functional. No The PA keys are disabled. Quick Set Note: If you enable the quick set keys the control unit no longer complies with EN50131.
Installer Menu Options i-on160 Note: If a user unsets the system during an alarm, but before the Alarm Abort period has expired, then they can reset the system (see page 97). Zone Tampers Yes The user can reset the system after an alarm caused by a zone’s tamper circuits being triggered. No The installer must reset the system after an alarm caused by a zone’s tamper circuits being triggered. The alarm abort period does not apply. Note: This setting is required for INCERT approval.
i-on160 Installer Menu Options 6.4.5). Entry Keypad Lock This option determines whether the user can unset the system by entering an access code after opening the entry door. Off The user can enter an access code at the keypad after the entry door opens (used for DD243:2004 clause 6.4.4). On The user must unset the system by some means other than the keypad, for example prox tag, remote control or key-switch (used for DD243:2004 clause 6.4.5).
Installer Menu Options i-on160 Confirmed alarm: Control unit waits for Siren Delay, and then starts both internal sounders and external sirens. Both sirens and sounders run for the full siren time. Unconfirmed Reset If you enable alarm confirmation then this option overrides System Options - User Reset – Zone Alarms (see page 61). You may then use the options below: User The user can reset after an unconfirmed alarm. Installer The user cannot reset after an unconfirmed alarm, the installer must do it.
i-on160 Installer Menu Options FSL Zone Resistance Bands tamper 10k mask (fault +alarm) 9k1 alarm 6k9 fault 4k4 normal 2k2 tamper alarm 6k9 normal 2k2 5k tamper tamper Enabled Disabled 0k Masking Figure 9. Resistance bands for FSL detectors Note that an installer can wire resistors to the contacts of a closed circuit loop detector with a Fault (or Trouble) output in order to use FSL signalling (see Fully Supervised Loop Connections in the i-on160EX Installer Guide).
Installer Menu Options i-on160 On a Security Grade 2 system the ability to reset the alert is governed by the System Options - User Reset - System Tampers option, see page 62. When the system is set: Detector output Response Mask (9k1) The control unit treats a masking event as an alarm condition. This will signal an unconfirmed alarm or will confirm an outstanding unconfirmed alarm. The unconfirmed and confirmed events must be from different detectors.
i-on160 Installer Menu Options Select this option: The control unit deletes: User All user access codes, their PAs, prox tags, and remote controls. User 01 access code changes to 1234, and installer access code to 7890 (123456 and 567890 in six digit access codes). This option has the same effect as restoring power to the control unit with the Code Reset pins shorted. Zones All information relating to zones: types, attributes and partitions.
Installer Menu Options i-on160 When logging into the i-on160EX Web Server you must key into the password field the same code as you have programmed into the Installer Code field. Keypad Text If required the installer can key in a text message that appears on the first line of the display in the standby screen. This could be, for example, the name of the installer’s company. See page 12 for hints on editing text.
i-on160 Installer Menu Options twice, three, four or five times, or always. The system re-arms all closed zones, but not detectors that are still sending alarm signals. (Note that this setting is required in order to comply with EN50131.) If the system has rearmed, then when a user enters the system through the Final Exit door the control unit will give an audible internal alarm in place of the normal entry tone. Siren Delay (For part setting systems only.
Installer Menu Options i-on160 Entry Alarm Delay Use this option to determine what the system will do if a user strays from an Entry Route zone during entry. (This option is available to provide compliance with EN 50131-1.) Select “No” to make the system give an alarm immediately if the user strays from an entry route zone during entry. Note: This is not compliant with EN50131.
i-on160 Installer Menu Options remote control button to confirm that they wish to continue setting the system. On The user need only press the remote control button once to complete setting the system. Note: The Confirm and On options will also allow a user with a remote control to set the system if a reset is required after an alarm. If any user is attempting to reset the system from a wired keypad when a remote user tries to set the system, then the control unit will temporarily ignore the remote user.
Installer Menu Options i-on160 No Alert Tones The keypad gives no alert tone. (The red LEDs around the navigation key glow to show that there is an alert.) Mains Fail Delay This option controls the length of time that the control unit waits until starting an alert if the mains supply fails. The values available are 0 to 10 minutes. Note that when the value is set to 0 minutes, mains interruptions of less than 9 seconds will not start an alert.
i-on160 Installer Menu Options Note: Apart from Downloading and IP Network (Own), the above menu items appear only if the appropriate module is fitted. The control unit is designed to alert the user if it fails to complete a programmed communication. If alarm reporting fails then the keypad displays an alert by lighting the red LEDs around the navigation keys. Although the user may acknowledge the alert, the control unit will not remove the alert until communication is completed successfully.
Installer Menu Options i-on160 Phone Book This option appears only when there is an i-sd02 or i-gsm02 module fitted. Use this menu to store two telephone numbers that the control unit uses to report alarms to the ARC. The control unit accepts one telephone number if you choose Single in the Call Mode menu, or two telephone numbers if you select Alternate in the Call Mode menu. The control unit can store telephone numbers up to 31 digits long.
i-on160 Installer Menu Options Report Type To choose the report type to send to the ARC select: Communications – ARC Reporting – Report Type. The report types available are: Fast Format, Contact ID, SIA 1, SIA 2, Scancom SIA 3, Extended SIA 3. Fast Format Channels (See Appendix I for a brief description of Fast Format.
Installer Menu Options i-on160 CID/SIA Events (This menu appears only if you select “Contact ID” or any of the SIA versions in Communications - Report Types. See Appendix I for a description of the CID and SIA formats.) To make programming easier, the i-on160EX groups CID/SIA telegrams together into Report Groups. Table 3 lists the telegrams included in each report group, and the relevant CID/SIA codes.
i-on160 Installer Menu Options System/Partition keyswitch set and unset 409 CS, OS Calendar set deferred - CE System/Partition part set 401 CL System/Partition keyswitch part set 409 CS Reset System/Partition reset 305 OR Exit Timeout Exit timeout and restore 457 EA Omit User zone omit. System zone omit.
Installer Menu Options Downloading failed i-on160 - RU *Notes: 1. The control unit communicates Jamming, Supervision when the system is unset. Restorals When you enable a CID/SIA Report Group, the control unit sends the relevant telegram both when an event occurs, and when the condition causing the event stops. The second transmission of the telegram is also called a “restore”. You can enable or disable restoral reporting by selecting Communications – ARC Reporting – Restorals.
i-on160 Installer Menu Options Dynamic Test Call In dynamic testing the system makes a test call 24 hours after the last alarm communication. To enable dynamic testing select Communications – ARC Reporting – Dynamic Test Call – Enabled. Static Test Call In static testing the system makes a test call either on: Every day at one particular time of day or On the same day of every week, or On one day every month.
Installer Menu Options Report Triggers i-on160 Messages Destinations Phone Book Home message Message 1 Dest 1 Dest 2 Dest 3 Dest 4 Y N Y N Message 2 Dest 1 Dest 2 Dest 3 Dest 4 N N N N Message 3 Dest 1 Dest 2 Dest 3 Dest 4 N N N N Message 4 Dest 1 Dest 2 Dest 3 Dest 4 N Y N Y None Fire Alarm Panic Alarm Burglar Alarm Technical Alarm Tampers Mains Fail Soak Test Fail Dest 1 = Dest 2 = Dest 3 = Dest 4 = Tel No: 12345678 Tel No: 87654321 Tel No: 56781234 Tel No: 21436587 Figure 10.
i-on160 Installer Menu Options “Delete Message?” press Y. Use Lid Tamper This puts the control unit into a special mode where the tamper switch controls the recording and playback of the current message. Use this mode if the control unit is an inconvenient distance from the keypad. 1. Start with the control unit lid off and the tamper switch open. 2. At the keypad select Use Lid Tamper and press Y. 3. At the control unit hold down the tamper switch.
Installer Menu Options i-on160 beginning of each transmission.) Select the message that you wish to program. The display then shows a list of five triggers. Select a trigger and the display shows a list of available alarm events. Select one alarm event for that trigger. When you have selected an alarm event the display shows the list of triggers again. You may program one alarm event for each of the five triggers in the list.
i-on160 Installer Menu Options The control unit sends the text in the Home Message to every telephone number you have programmed for SMS messages. The control unit also sends message 1 to telephone number 1, message 2 to telephone number 2, message 3 to telephone number 3 and message 4 to telephone number 4. When programming SMS you key in the text of each message, link the messages to specific groups of alarms, and then key in the telephone number you want each message to go to.
Installer Menu Options i-on160 Phone Book To program the telephone numbers that the control unit will use for SMS message select Communications – SMS – Phone Book. The bottom line of the display shows the first of a list of phone numbers. Press u and n to scroll to the required phone number followed by Y to select it. Key in the correct digits and then press Y. The display then allows you to give the telephone number a name.
i-on160 Installer Menu Options Audible If the system is unset then the system logs the event. The keypads produce a short audible tone every minute. Entering a valid access code silences the sounders and the display indicates a telephone line fault. The system can be set again with the line fault present. If the system is set then the control unit logs the event but does not give any tone or display. The control unit cancels any programmed siren delay if the line is out of order when an alarm occurs.
Installer Menu Options Gateway Address i-on160 “255.255.255.000”. This number has the same format as the IP address. This is the IP address of the router that connects the local network, to which the i-on160EX is connected, to rest of the Internet (or to a larger network).If necessary, key in the gateway IP address. This number has the same format as the IP address. Notes: 1.
i-on160 Installer Menu Options IP Address This is the module’s own IP address. If you leave it blank the service provider will give the module an IP address using DHCP. (Cooper Security recommend that you leave this field blank.) Port Number If you wish to change the port number used by the module then key in the new port number here. APN Key in the GPRS Access Point Name here. Username Use this option to store the GPRS User ID. Password Use this option to store the GPRS password.
Installer Menu Options Remote Local i-on160 Automatically answer calls coming from a remote PC over the telephone network. You will also need to program "Rings to Answer" and/or "Answer on One Ring", see below. (Note that Secure Callback does not work with this option.) Connect the control unit to a PC (for example a laptop) using a local USB cable. Note: The control unit will leave the Connection Type menu if Downloader does not make a call within 30 minutes.
i-on160 Installer Menu Options Downloader software version. If these items don't match then the system hangs up. If the items do match then the system hangs up and, after a short delay, the system seizes the telephone line and calls the PC using the indicated Downloader Telephone Number. Notes: a) Secure Call Back must be Disabled until the first “attended” upload has been performed. This first upload can be carried out either from User Menu, or from Installer Menu.
Installer Menu Options i-on160 you can key in the port numbers that Downloader “listens” to on the remote PC for the primary and secondary IP addresses. Secure Callback (This option appears only when the i-sd02 or i-gsm02 module is fitted.) Select Downloading - Secure Callback to allow Downloader to use a third callback number (independent of the telephone numbers in the Downloading – Phone Book option). Before making a Downloader connection, the remote PC operator keys in the third callback number.
i-on160 Wired Keypads Installer Menu Options Use this option to test the sounders on the wired keypads. Either: Select “All keypad sounders” to operate all wired keypad sounders on the system at once. OR: Press u or n to select the wired keypads sounders for an individual partition. Note that options for radio sirens will not appear if the control unit has not learned any radio sirens. Select the type of sounder you wish to test and press Y.
Installer Menu Options Partitions i-on160 Use this option to select one or more partitions, and test the zones only within those partitions. Use u or n to scroll up and down the list of partitions. Press < or > to display “Yes” at the end of the bottom line to mark the partition as one you want to test. Expanders Use this option to select an individual expander, and test the zones belonging to just that expander.
i-on160 Installer Menu Options Signal Strengths This option allows you check the received signal strength from all the radio transmitters belonging to the system. The keypad display shows first: the strength of the most recent signal it has received from a transmitter, and second: (in brackets) the minimum strength signal it has received from the transmitter since the records were last reset. The control unit is always recording signal strengths, whether or not you are using the Signal Strength menu.
Installer Menu Options i-on160 Remotes The Test menu allows you to test user’s remote control (you must have the remote control to carry out the test). From the Installer Menu select TestRemotes. The keypad display shows a message asking you to press any button on the remote you wish to test. Press one of the remote’s buttons. The top line of the keypad display shows the remote’s identity, the button you pressed and the remote’s owner.
i-on160 Installer Menu Options During the test call the keypad display will show a sequence of progress messages, for example: Dialling... Connected... Negotiating... Call Successful... (or Call Failed...). If the call fails the keypad display will show a brief message giving the reason for failure. Speech Dialler The Test menu allows you to send a test speech call to any telephone number (not just the ones programmed to receive speech messages in the event of an alarm).
Installer Menu Options i-on160 Press u or n to scroll up or down the list. Press > to turn on the device’s buzzer. (Press < or > to turn it off again.) View Log The control unit keeps a log of the last 1,000 events (for example, alarms and setting/unsetting). You can read the log when the system is completely unset. Note: To comply with EN50131-1:2006 for Grade 2 systems the log is divided internally into two portions: mandatory events and non-mandatory events.
i-on160 Installer Menu Options IP Address This is the IP address the control unit uses when linked by Ethernet to a PC. Subnet Mask This is the subnet mask currently in use by the control unit itself. Gateway Address This is the gateway address being used by the control unit. MAC Address This is the unique MAC address of the control unit pcb. Each control unit pcb will have an individual MAC address.
Installer Menu Options i-on160 reset input of the plug by pins. This allows the user to reset the system using their normal user access code. If the ARC sends the 12v signal to enable the remote reset pin and reverts it back to 0v before the user resets the system, the panel will remember that the remote reset pin was enabled and will still allow the user to reset the system using their normal user access code.
i-on160 Step By Step Programming Procedures The detailed procedures shown in this section are here to help those who are not familiar with the Installer Menu. The procedures do not cover the whole of the Installer Menu. Cooper Security hope that after you have followed these detailed instructions then you will be familiar enough with the Installer Menu to carry out any other programming task.
Step by Step Programming Procedures 2. Apply 12Vdc power to the device (use the 0V and 12V terminals on the keypad connector). 3. Hold down keys D and X at the same time. i-on160 See Note below. After a few seconds you should hear a confirmation tone and the navigation LEDs start flashing. 4. Release the D and X keys. 5. Close the lid, making sure the tamper switch closes. Note: DO NOT hold down D and X to delete a keypad from a system while the keypad is still connected to the bus.
i-on160 Step by Step Programming Procedures for at least three seconds. After three seconds the expander gives a confirmation tone (two beeps) and its display shows the address allocated by the control unit, for example: 1- followed by 03 Note: DO NOT attempt to address two devices at the same time. If you do not wish to accept this bus device number, hold down the Request/Delete Address button for at least three seconds again.
Step by Step Programming Procedures 11. Press X until the keypad display shows: 12. Press Y. After a short time (depending on the number of bus devices fitted to the system) the display shows: The control unit has saved your changes, and left the Installer Menu. i-on160 Leave installer mode? Please wait... i-on160EX 12:43 02/11/2010 To Delete A Keypad or Expander From The Bus: 1. Enter Installer Menu. 2. Press Y. The display shows: 3.
i-on160 8. Step by Step Programming Procedures Press Y . The display asks you to confirm that you want to delete the selected device: Delete Expander Are you sure? Notes: If you change your mind and do NOT wish to delete the device shown then press X. 9. Press Y . The display shows a brief message to confirm the deletion: ...followed by the Delete Expander option. The control unit deletes its record of the expander you selected in step 7, and also defaults the expander’s own record of the bus address.
Step by Step Programming Procedures i-on160 (The rest of these instructions assume you are disabling a wired expander. The instructions are similar but the displays are slightly different for a radio expander.) 4. Press Y . The display shows: 5. Press n until the display shows: 6. Press Y . The display shows the first in a list of the expanders that are currently connected to the bus. 7.
i-on160 Step by Step Programming Procedures with an alert. When a user reads the alert it will show the address of the disabled expander. To enable the expander again, repeat steps 1 to 11, but at step 8 press > or < until the end of the bottom line shows “Yes”. To Replace an Expander: 1. Enter Installer Menu. 2. Press Y. The display shows: 3.
Step by Step Programming Procedures i-on160 Followed by: The navigation keys on the keypad glow red. 10 a) Power down the system (both mains and battery). REPLACE EXPANDER Exp. W1-04 Add b) Remove the old expander. c) Connect the new expander. Note: The new expander must be of the same type as the one you removed. Make sure that you replace an EXP-R30 with an EXP-R30. d) Power up the system (connect the battery, close the control unit lid to ensure the tamper switch is closed, then apply mains power).
i-on160 Step by Step Programming Procedures Note: If you replace a wireless expander then you must teach the identity of the new wireless expander to any receivers or output modules that had previously learned the old wireless expander’s identity. This includes any 762s, 768s or WAMs. Naming Wired and Radio Expanders 1. Enter Installer Menu. 2. Press Y. 3. Press n until the display shows EITHER (if you are adding a wired expander): OR (if you are adding a radio expander): 4. Press Y .
Step by Step Programming Procedures i-on160 Assigning Wired and Radio Expanders to Partitions 1. Enter Installer Menu. 2. Press Y. 3. Press n until the display shows EITHER (if you are adding a wired expander): OR (if you are adding a radio expander): 4. Press Y . (The rest of these instructions assume you are naming a wired expander. The same instructions will also work for a radio expander.) 5. Press n until the display shows: 6. Press Y . 7.
i-on160 Step by Step Programming Procedures Press > or < to allocate or remove partitions as required. 12. Press Y to confirm your changes. 13. Carry on with any other programming that you need to do. DON’T FORGET to leave the Installer Menu in order to save the changes you have made (see page 7 ). Partition 2 Yes Exp. W1-01 Partitions > Changing the Wiring Type of Wired Expanders 1. Enter Installer Menu. 2. Press Y. 3. Press n until the display shows: 4. Press Y . 5. Press n . 6.
Step by Step Programming Procedures (Press X if you wish to change your mind.) i-on160 Wired zone type > 13. Carry on with any other programming that you need to do. DON’T FORGET to leave the Installer Menu in order to save the changes you have made (see page 7 ). Editing Zones Learning radio detectors Note: This example assumes that your radio expander device number is R1-03. The number may be different on the system you are working on. Make sure you use the correct expander device number. 1.
i-on160 Step by Step Programming Procedures the control unit successfully learns the detector. 9. Either: Press X to go back to the list of zones so that you can go on and learn other detectors. ADD/DEL DETECTORS *Zone 021 The control unit stores the identity of the radio detector, but sets the type to “Not Used”. OR: Press Y to carry on giving a name, type and attribute to the detector you have just learned (see page 33 ).
Step by Step Programming Procedures 6. Press u or n keys to show the zone you wish to delete. 7. Press Y. The bottom line of the display shows the first of two options: deleting the detector ID or of defaulting the zone. 8. Press u or n to see each of these choices. i-on160 ADD/DEL DETECTORS *Zone 021 > DELETE Zone 020 Delete Detector ID> DELETE Zone 020 Default Zone If you select “Delete Detector ID” then the control unit “forgets” the ID of the detector, but leaves any zone programming in place.
i-on160 6. Step by Step Programming Procedures Press Y. The display shows a message asking you to confirm your choice. (Press X if you want to change your mind.) 6. Press Y. The display shows a second message asking you to confirm your choice. (Press X if you want to change your mind.) Delete ALL detectors and zone data? Are you sure? Note: The deletion will take place immediately, and not when you leave Installer Mode. 7. Press Y to confirm your choice.
Step by Step Programming Procedures 7. When you have found the zone you wish to edit press Y. The bottom line of the display shows “Name”. 8. i-on160 Zone 041 NU Name > Press u or n to see the Type, Attributes or Partition options for that zone. Press Y to select the option you wish to change. Note: If a zone has the type “Not Used” then the Attributes and Partition options do not appear. When changing the name, see page 12 for hints on how to edit names.
i-on160 9. Step by Step Programming Procedures Press Y to confirm your changes. The bottom line of the display shows the zone you were editing, for example: Zone 041 NU Name > 10. Carry on with any other programming that you need to do. DON’T FORGET to leave the Installer Menu in order to save the changes you have made (see page 7 ). Keypads Naming a Wired Keypad To name a wired keypad: 1. Enter Installer Menu. 2. Press Y. 3. Press n until the display shows: 4. Press Y.
Step by Step Programming Procedures i-on160 Assigning a Wired keypad to Partitions Note: If you selected “Part set mode” during Initial Power-up then you cannot assign a keypad to a partition (see System Options–Restore Defaults–Factory Defaults on page 67 if you want to change the system from Part Setting to Partitions). 1. Enter Installer Menu. 2. Press Y. 3. Press n until the display shows: 4. Press Y. The bottom line of the display shows: 5. Press n until the display shows: 6. Press Y.
i-on160 Step by Step Programming Procedures partitions except partition 1. 11. Press Y to confirm your changes. Keypad K1-53 Partitions 12. Carry on with any other programming that you need to do. DON’T FORGET to leave the Installer Menu in order to save the changes you have made (see page 7 ). > Adding a Radio Keypad To make the control unit learn a Radio Keypad’s identity. 1. Enter Installer Menu. 2. Press Y. 3. Press n until the display shows: 4. Press Y. 5. Press Y.
Step by Step Programming Procedures 10. Fit suitable batteries to the radio keypad. When you fit the final battery the radio keypad transmits its identity to the control unit. When the control unit learns the identity it displays the radio keypad’s signal strength. 11. Press Y. The bottom line of the display shows the keypad’s default name. The “*” at the left of the display shows that the control unit has learned the radio keypad’s identity.
i-on160 9. Step by Step Programming Procedures Press Y. The bottom line of the display asks if you want to delete the selected radio keypad. 10. Press Y. The bottom line of the display asks you to confirm that you want to delete the selected radio keypad. 11. Press Y. The bottom line of the display shows: ADD/DEL RADIO KPD Delete Radio Keypad? ADD/DEL RADIO KPD Are you sure? ADD/DEL RADIO KPD RKP R1-05-02 The control unit has deleted the radio keypad. 12.
Step by Step Programming Procedures 11. Press Y to save the text. 12. Carry on with any other programming that you need to do. DON’T FORGET to leave the Installer Menu in order to save the changes you have made (see page 7 ). i-on160 Bedroom Name > Assigning a Radio Keypad to Partitions The i-on160EX allows you to assign radio keypads to one or more of the partitions.
i-on160 Step by Step Programming Procedures than one Partition. Press u or n to see the other partitions. See page 52 for more information about partitions. If you want to allocate a keypad to all partitions at once: Press u or n until the bottom line shows “All Partitions”. Press > or < until the end of the bottom line shows: Either “Yes” to allocate the keypad to all partitions Or “No” to remove the keypad from all partitions except partition 1. 12. Press Y to confirm your changes. 13.
Step by Step Programming Procedures 9. Press Y. The display shows the Name option. (If you do not want to name the key go to step 13.) 10. To name the key press Y. The bottom line of the display shows the key’s current name. The cursor is on the first character on the left. 11. See page 12 for hints on how to edit names. 12. Press Y to save the text. This example shows how to program keys to set partitions. The same instructions can be adapted to program keys to unset partitions. 13.
i-on160 Step by Step Programming Procedures 20. Repeat steps 8 to 19 for any other keys you wish to edit. 21. Press X to stop editing the keypad. 22. Carry on with any other programming that you need to do. DON’T FORGET to leave the Installer Menu in order to save the changes you have made (see page 7 ). EDIT WIRED KEYPADS Keypad K1-51 > Sirens Adding a Radio Siren (Please read the installation guide for the radio siren.) To make the control unit learn the ID of a radio siren: 1. Enter Installer Menu.
Step by Step Programming Procedures 8. 9. Press u or n keys to show the device address that you want to use for the radio siren, for example: Press Y. 10. Insert the batteries in the external siren. The display shows a message to confirm that the system has learned the radio siren, together with the current signal strength of the siren.
i-on160 Step by Step Programming Procedures by the system 7. Press u or n keys to show the siren you want. 8. Press Y. 9. Press n. SRN02 R1-01-02 Siren 02 10. Press Y. 11. To allocate a radio siren to a partition press > or < until the end of the bottom line shows “Yes”. To remove a radio siren from a partition press > or < until the end of the bottom line shows “No”. You can allocate the radio siren to more than one partition. Press u or n to see the other partitions.
Step by Step Programming Procedures 1. Enter Installer Menu. 2. Press Y. 3. Press n until the bottom line of the display shows: 4. Press Y . 5. Press Y. The bottom line of the display shows the first of the available radio expanders. i-on160 INSTALLER MENU Detectors/Devices > DETECTORS/DEVICES Detectors DETECTORS/DEVICES External Sirens > EXTERNAL SIRENS Add/Del Ext Siren > ADD/DEL EXT SIREN Exp. R1-02 (R30)> Note: This example assumes that your radio expanders are bus devices 02 and 05.
i-on160 Step by Step Programming Procedures WAMs Please read the installation manual for the WAM. You must make sure that the WAM is programmed as Mode 1 BEFORE adding it to the system. The WAM must be powered up in order to make the control unit learn its identity. Adding a WAM To teach the control unit the WAM’s identity: 1. Enter Installer Menu. 2. Press Y. 3. Press n until the display shows: 4. Press Y. 5. Press Y.
Step by Step Programming Procedures i-on160 name (WAM 01). 12. Don’t forget to restore the tamper on the WAM you have just learned. Naming a WAM To give a WAM a meaningful name: 1. Enter Installer Menu. 2. Press Y. 3. Press n until the display shows: 4. Press Y. 5. Press n until the display shows: 6. Press Y . INSTALLER MENU Detectors/Devices > DETECTORS/DEVICES Detectors DETECTORS/DEVICES WAMs 7. Press u or n until the bottom line of the display shows the WAM that you wish to name: 8.
i-on160 Step by Step Programming Procedures Deleting a WAM To remove a WAM from service in the system: 1. Enter Installer Menu. 2. Press Y. 3. Press n until the display shows: 4. Press Y. 5. Press Y. The bottom line of the display shows the first of the available radio expanders. 6. Press u or n to select the radio expander allocated to the WAM you wish to delete. Note: This example assumes that your radio expanders are bus devices 02 and 05.
Step by Step Programming Procedures i-on160 Outputs Adding Radio Outputs To teach the control unit's identity to a 762r, 768r or 769r: 1. Enter Installer Menu. 2. Press n until the display shows: 3. Press Y. 4. Press Y . 5. Press Y. The bottom line of the display shows the first of the available radio expanders, for example: 6. Press u or n to select the expander that you wish allocate the radio keypad to. Note: This example assumes that your radio expanders are bus devices 02 and 05.
i-on160 Step by Step Programming Procedures 13. EITHER: Press Y to carry on and program the output name (see step 10 on page 132 ) OR: Press X to carry on with other programming. DON’T FORGET to leave the Installer Menu in order to save the changes you have made (see page 7 ). Giving a Radio Output a Type: Note: Some output types can be assigned to zones or partitions. If you select those types then the keypad display will show a further menu allowing you to select the appropriate zones or partitions.
Step by Step Programming Procedures 9. Press u or n until the display shows the output you wish to edit, for example: 10. Press Y. If the bottom line of the display shows “Not Used” then the output does not currently have a type assigned to it. Go to step 11. i-on160 EDIT O/P R1>05>03 O/P R1>05>03 > EDIT O/P R1>05>03 Not Used > If the bottom line of the the display shows “Name” then the output already has a type assigned to it. Press n until the bottom line shows “Type”. Go to step 12. 11. Press Y .
i-on160 5. Press n until the display shows: 6. Press Y. Step by Step Programming Procedures The bottom line of the display shows the first of the available radio expanders. 7. Press u or n to select the expander that you wish allocate the radio keypad to. Note: This example assumes that your radio expanders are bus devices 02 and 05. The numbers may be different on the system you are working on. 8. Press Y. The display shows the first in a list of the radio outputs for the select expander.
Step by Step Programming Procedures 4. Press n. 5. Press Y. The display shows the first group of wired outputs available for editing: those on the panel. 6. 7. If required, press u or n until the display shows the expander whose outputs you wish to edit. Press Y. The top line of the display shows the first in a list of the wired outputs on the expander, for example: 8. Press u or n until the display shows the output you wish to edit, for example: 9. Press Y.
i-on160 Step by Step Programming Procedures If you are programming a partitioned system then at this point, for some output types, the top line of the display shows “Partition?”. The bottom line of the display shows “Partition 1 Yes”. This means that the system is asking if you want to allocate the output to Partition 1. You can remove the output from Partition 1 by pressing < or > to change the “Yes” to a “No”. Press u or n to scroll to other Partitions.
Step by Step Programming Procedures 11. See page 12 for hints on how to edit names. 12. Press Y to save the text. 13. Carry on with any other programming that you need to do. DON’T FORGET to leave the Installer Menu in order to save the changes you have made (see page 7 ). Changing the Polarity of a Wired Output: 1. Enter Installer Menu. 2. Press n until the display shows: 3. Press Y. 4. Press n. 5. Press Y. The display shows the first group of wired outputs available for editing: those on the panel.
i-on160 Step by Step Programming Procedures polarity if you scroll down the list. See page 45 for more information on output polarity. 12. Press u or n to change the polarity. O/P W1>01>03 POLAR. Inverted 13. Press Y to confirm the change in polarity. 14. Carry on with any other programming that you need to do. DON’T FORGET to leave the Installer Menu in order to save the changes you have made (see page 7 ).
Step by Step Programming Procedures 9. Press Y. The display shows: 10. Key in the start time of the exception. For example, to start at one minute past midnight: i-on160 EXCEPTION START TIME 00 : 00 EXCEPTION START TIME 00.01 Note that midnight is “00:00” and represents the start of the day. 11. Press Y. The display shows: 12 Key in the start date. For example, if the start date is 02/05 (2nd May), key in: 13. Press Y. The display shows: 14. Key in the end time of the exception.
i-on160 4. Step by Step Programming Procedures Press u until the display shows: (For a part set system the top line of the display shows “Setting Options”.) 5. Press Y. 6. Press Y. PARTITIONS Calendar Set CALENDAR SET Add event The bottom line of the display shows a new event and its default name. The text cursor is on the first character. 7. Key in a name for the event (if required). For example: > > EVENT NAME Event 01 EVENT NAME Mon am unset See page 12 for hints on how to edit names. 8.
Step by Step Programming Procedures b) Press u or n to see the other partitions in the list. Press > to change their state as required. On a part setting system the bottom line of the display shows the current action for the system, for example: a) Press u or n to display the other actions available, for example: On a part setting system the actions available are “Full Set”, “Part Set B”, “Part Set C”, “Part Set D”, “Unset” and “No action”. 14. Press Y.
i-on160 4. Step by Step Programming Procedures Press u until the display shows: (For a part set system the display shows: “Setting Options Calendar Set”.) 5. Press Y. 6. Press n until the display shows: 7. Press Y. The display shows the first item in a list of the available events. 8. Press u or n to see the other events. 9. Press Y. The bottom line of the display shows the first option that you can edit for the selected event (in this case “Name”). 10.
Step by Step Programming Procedures 2. Press n until the display shows: (For a part set system the bottom line of the display shows “Setting Options”.) 3. Press Y. (For a part set system the display shows “Setting Options Full Set”.) 4. Press u until the display shows: (For a part set system the top line of the display shows: “Setting Options”.) 5. Press Y. i-on160 INSTALLER MENU Partitions PARTITIONS Partition 1 Press n until the display shows: 7. Press Y.
i-on160 3. Press n until the display shows: 4. Press Y. 5. Press u until the display shows: 6. Press Y. Step by Step Programming Procedures The display shows a blank CSID seed code. 7. Key in the CSID seed code (for example): 8. Press Y. 9. Carry on with any other programming that you need to do. DON’T FORGET to leave the Installer Menu in order to save the changes you have made (see page 7 ).
Step by Step Programming Procedures g) i-on160 Carry on with any other programming that you need to do. DON’T FORGET to leave the Installer Menu in order to save the changes you have made (see page 7 ). OR IF DD243 Confirmation is OFF then: a) Press n until the display shows: b) Press Y. c) Press > until the display shows: d) Press Y. e) Carry on with any other programming that you need to do. DON’T FORGET to leave the Installer Menu in order to save the changes you have made (see page 7 ).
i-on160 Step by Step Programming Procedures 4. Press < or > to toggle between Chime On or Chime Off. 5. Press n. The display shows: 6. Press Y. The display shows, for example: 7. Trigger the alarm and tamper of each zone. As you trigger the zones the top line of the display shows the number of zones remaining to be tested. The bottom line of the display shows the first in a list of the zones you have selected to test.
Step by Step Programming Procedures i-on160 Press u or n to see other partitions. 8. Press Y to start the test. The display shows for example: 9. Trigger the alarm and tamper of each zone. As you trigger the zones the top line of the display shows the number of zones remaining to test. The bottom line shows the first in a list of zones that you have selected for testing.
i-on160 8. Step by Step Programming Procedures Trigger the alarm and tamper of each zone. As you trigger the zones the top line of the display shows the number of zones remaining to be tested. The bottom line of the display shows the first in a list of the zones that you have selected for testing. 23 Zone(s) to test Zone 020 TA Each zone that you test shows an “A” if you have tested the Alarm contacts and a “T” if you have tested the tamper.
Step by Step Programming Procedures Testing a Radio Panic Alarm: 1. Enter the installer menu and select Test (see steps 1 to 4 in “To start testing” on page 144). 2. Press n until the display shows: 3. Press Y. i-on160 TEST Sirens & Sounders User Panic Alarms Press and hold down both buttons on the PA at the same time. > Press both PA The display instructs you to press both PA buttons. 4.
i-on160 Step by Step Programming Procedures The bottom line of the display shows “Number 1”. There are two numbers to chose from. 4. Press u or n to select the number you wish to call. 5. Press Y. The keypad display shows the progress of the call: “Dialling”, then “Connected”, “Negotiating” followed by “Call Successful”. Check with the receiving centre that the test call arrived. If the call fails the display will show “Call failed” followed by a reason.
Step by Step Programming Procedures i-on160 “Acknowledged”. Playing Messages... Note: If you key in a valid user access code before the speech dialler connects to its first destination then the control unit will cancel the call. Log Viewing the Log 1. Enter Installer Menu. 2. Press u until the display shows: 3. Press Y. The display shows you the most recent log event. 4 Press u or n to scroll through the log. n shows earlier events.
i-on160 Step by Step Programming Procedures display, for example: 6. Press X when you have finished. INSTALLER MENU About > Seeing Which Communications Module Is Currently Installed: 1. Enter Installer Menu. INSTALLER MENU 2. Press u until the display shows: 3. Press Y. 4. Press n. until the display shows: 5. Press Y.
Step by Step Programming Procedures i-on160 blank if you are connecting a PC/laptop directly to the control unit. 12. Press X then n. 13. Press Y. The bottom line of the display shows the MAC address of the plug-on Ethernet module. 14. Press X then n. 15. Press Y. The bottom line of the display shows “OK” if the control unit has successfully connected to a PC by way of an Ethernet cable.
i-on160 Step by Step Programming Procedures 10. Press Y. The bottom line of the display shows the subnet mask currently assigned to the panel webserver. Note that this may have been assigned by DHCP. 11. Press X then n. 12. Press Y. The bottom line of the display shows the gateway address currently assigned to the plug-on Ethernet module. Note that this may have been assigned by DHCP, or this may be blank if you are connecting a PC/laptop directly to the control unit. 13. Press X then n. 14. Press Y.
i-on160 Appendix I: ARC Communication Formats Note: To comply with EN50131 you must fit a communications module. Fast Format Fast Format is the format most widely used in the UK. When using the Fast Format, each message transmitted to the ARC consists of the following: A 4,5 or 6-digit account number. 8 channels of data. Each channel communicates the status of an output, as programmed using the ”Fast Format Channels” option (see page 75 ).
i-on160 Appendix I SIA3: #AAAAAA|Ntihh:mm/idnnn/rinn/CCcc #AAAAAA|AS Extended SIA 3: #AAAAAA|Ntihh:mm/idnnn/rinn/CCcc/AS Where: AAAAAA “N” “ti”hh:mm/ “id”nnn/ 6-digit programmable account code (e.g. 123456). New Event (always N). time (e.g. ti10:23/). user number, if applicable; otherwise not sent (e.g. id123/ or id6/). “ri”nn/ partition no. (e.g. ri12/ or ri3). CC event code (e.g. FA = Fire Alarm). cc zone or keypad number, if applicable; otherwise not sent (e.g. 23 or 5).
i-on160 Appendix II: Programming a Common Area Some commercial premises include two or more separate areas linked by a common area. You can program the i-on160EX to allow users to set each area independently, and then set the common area automatically when the last occupant leaves the premises. The Full Set Link option in Installer Menu Partitions provides this feature. Figure 12 shows a typical example of a commercial building that could use the “Common Area”.
i-on160 Appendix II To avoid false alarms make the alarm response of the common area (Partition 1) Siren + Comms and the other two Partitions Siren only.
Appendix II System Options i-on160 Wired Zone Type DD243 (for UK only) • Confirmation • • • • • Time After Entry Entry keypad Lock Sounder on Siren on Unconfirmed reset Confirmed Reset • Keypad Text Siren Delay Siren Time Force Set CSID Silence Alerts Select FSL if using all wired detectors Confirmation = On 30 mins 2 zones On Unconfirmed Unconfirmed User Installer Enter Name of installer company (default 0 mins) (default 15 mins) Off Enter 4 digit ARC Scantronic reset code (if required) User User Pro
i-on160 Appendix II If either User 02 or 03 opens the Front Door this starts the entry time and tone. The user enters their code or presents a Prox tag to the keypad in their department. The system then unsets their partition and the common area. If the Master user opens the Front Door and enters their code or presents a Prox to a keypad then only P1, the common area, will unset. The keypad then gives the master user the option to unset either Factory or Office or both.
i-on160 Appendix III: Using A WAM As A Repeater Introduction In mode 1 the WAM acts as a repeater for i-on alarm systems. The WAM receives signals from transmitters that are out of range of the radio expander. The WAM repeats these signals and, because the WAM is nearer the expander, the expander can now hear the signals and respond to them. The WAM can learn up to eight detectors. You can also program the WAM to flash a separate blue LED for each transmitter.
i-on160 Appendix III 3. Set the WAM to the Mode 1 (Repeater) 1. Apply power to the WAM. 2. a) Enter programming mode as follows: Make sure the tamper switch has opened. The Red Trouble LED glows. b). Press SELECT. The blue LED 1 glows. The WAM is in menu 1. 3. Use menu 7 to go into mode selection as follows: a) Press SELECT repeatedly until LED 7 glows. b) Press SET. xn The blue LEDs show the current mode. When delivered from the factory the WAM is in mode 1 (LED 1 glowing). 4.
Appendix III 2. Press Y. 3. Press n until the display shows: 4. Press Y. 5. Press Y. The display shows the first in a list of the available radio expanders. i-on160 Detectors/Devices Detectors WAMs Add/Del WAM Exp. R1-02 7. Press Y to select the radio expander you that wish to learn the WAM. ADD/DEL WAM 9. Press Y when the display shows the WAM slot you wish to use.
i-on160 Appendix III Teach the WAM the Identity of the Detectors 1. a) Enter programming mode as follows: Open the tamper switch. The Red Trouble LED glows. b). Press SELECT. The blue LED 1 glows. The WAM is in menu 1. 2. Press SET. If any blue LEDs flash then those channels are already in use. 3. Activate tampers on all transmitters that the WAM needs to learn. Each time the WAM learns a detector a blue LED glows to show the channel that detector is using. 4.
Appendix III 1. Enter programming mode as follows: a) Open the tamper switch. i-on160 The Red Trouble LED glows. b). Press SELECT. The blue LED 1 glows. 2. Press SELECT. The blue LED 2 glows. 3. Press SET. The WAM is in menu 2 – Delete Detectors. If any blue LEDs flash then those channels are in use. 4. If necessary, press SELECT to select the detector you wish to delete. The blue LED of the selected detector flashes. 5. Press and hold ESC for at least four seconds.
i-on160 Appendix IV: Programming a 762 or 768/769 as an Output Module Introduction Before You Begin Carry out a radio site survey. Set Up the 762 or 768 Enter Programming Mode To enter programming for the first time (while installing a new unit): 1. 2. Connect a suitable 12VDC power supply to the DC supply in connector. The display shows the version number of the software as two alternating two-digit numbers, for example: 01 00 Press Select.
Appendix IV i-on160 NOTE: If you disable infra-red learn then the receiver enables radio learn. If you enable infra-red learn then the receiver disables radio learn. Set to manual learn 7. Press Select until the display shows the manual learn command “Ln”. 8. Ln Press Set. The display shows the first available channel number, for example “C1”: Select channel 9.
i-on160 7. Appendix IV Press Y. The display shows the first in a list of the radio outputs on that expander, for example: ADD OUTPUT R1>03>01 Not Used > The bottom line of the display shows the outputs current type. 8. Press u or n until the display shows the output you wish to add, for example: 9. Press Y. The display prompts you to make sure that the receiver is in learn mode: 10. Press Y. The control unit transmits its identity to the receiver.
Appendix IV At the Control Unit 3. Press Y. The display shows: 4. Press Y . 5. Press Y. The display shows the first in a list of the available radio expanders, for example: 6. Press u or n to see other radio expanders (if any). The display shows, for example: 7. Press Y. The display shows the first in a list of the radio outputs on that expander, for example: i-on160 EDIT OUTPUT R1>03>02 Name > RADIO OUTPUTS Add Outputs > ADD OUTPUTS Exp. R1-01 (R30)> ADD OUTPUTS Exp.
i-on160 Index 24 hour alarm output type ................... 50 zone type...................... 34 762r ............................... 130 768r ............................... 130 769r ............................... 130 770r ................................ 44 Abort Delay ...................... 97 AC Fail external PSU zone type... 35 fast format .................... 75 output type ................... 47 Access code defaults .......................... 6 installer ........................ 67 user ..........
i-on160 Double knock ................... 37 Downloading ............... 72, 87 access mode ................. 88 connection type ............. 87 IP address .................... 89 mode baud rate ............. 90 port number .................. 89 telephone number .......... 89 Dynamic test call .............. 78 EN50131-1 8.8.3 ............................ 22 EN50131-3 9.1 bb .......................... 37 9.1 cc ........................... 69 9.1 gg .......................... 32 9.1 hh ......................
i-on160 Key switch latched ......................... 34 momentary ................... 34 Keypad naming ......................... 40 PA keys enable .............. 61 partitions ...................... 41 quick set keys ............... 41 radio ............................ 42 radio-deleting ......... 43, 118 radio-learning......... 42, 117 radio-naming ............... 119 radio-partitions ....... 43, 120 testing .......................... 91 Language ......................... 66 Line Fail ...............
i-on160 Phone book ARC reporting ................ 73 downloading .................. 89 SMS ............................. 84 speech dialler ................ 81 PIR set latch ..................... 50 Plug-by outputs ................ 45 Polarity wired output ................ 136 Polling IP address.............. 74 Port number web server ............... 85, 86 Proximity tag for entry code lockout .... 63 testing .......................... 94 PSU current testing ..........................
i-on160 triggers ........................ Static test call................... Status web server .................... Stray on entry delay .......... Strobe ............................. Strobe on set Part setting ................... Strobe on unset Part setting ................... Subnet mask Ethernet module ............ web server ............... 85, System options ................. Tamper allow omit ..................... fast format .................... output type ................... send as burg .......
i-on160 www.coopersecurity.co.uk Product Support (UK) Tel: +44 (0) 1594 541979 Available between: 08:15 to 12:30 and 13:00 to 17:00 Monday to Friday. Product Support Fax: (01594) 545401 email: techsupport@coopersecurity.co.