INSTALLATION AND PROGRAMMING GUIDE HARDWIRED CONTROL PANELS
9751 9752 Hardwired Control Panel Installation and Programming Guide. © Cooper Security Limited. 2002 Every effort has been made to ensure that the contents of this book are correct, errors and omissions excepted. However, neither the authors nor Cooper Security Limited accept any liability for loss or damage caused or alleged to be caused directly or indirectly by this book. The contents of this book are subject to change without notice. Printed and published in the U.K.
Contents Contents 1. INTRODUCTION ....................................................................................... 1 Operator Controls and Displays - 9930 ......................................................................................... 3 System Features ............................................................................................................................ 4 Detectors ........................................................................................................
Contents 4. Programming ......................................................................................... 33 Entering Programming Mode ...................................................................................................... 33 Programming Commands ............................................................................................................ 33 Communications Programming ......................................................................................................
Contents Level C Exit Mode (Command 72) ........................................................................................................... Level C Alarm Response (Command 73) ................................................................................................. Level C Entry Time (Command 74) .......................................................................................................... Level C Exit Time (Command 75) ............................................................
Contents iv 496792
1. Introduction 1. INTRODUCTION The 9751 and 9752 control units are designed to be fully programmable to suit individual site requirements and user needs. The system comprises a control unit in a shielded case, up to four separate keypads and one keyswitch interface (see Figure 1 on the next page). You should always fit at least one keypad. The control unit provides: ° A four-wire bus connection for keypads, keyswitches and hardwired or wireless zone expanders.
1. Introduction ° Dual key PA, medical assistance and fire alarms from the keypads. ° Remote telecommand set/unset when using 9955 RF Expander. To reduce the possibility of false alarms the system also provides Alarm Abort and Alarm Confirmation communications output. Before attempting to program the system, make sure you are completely familiar with the functions of the system and its programmable options.
1. Introduction Operator Controls and Displays - 9930 Figure 2. 9930 Remote Keypad. The 9930 keypad has a single line 16 character LCD display that shows first to alarm information, level status, and programming commands. In addition there are three LEDs with the following functions: Glows steadily when mains power is present. Flashes when the system is working from battery backup. Glows steadily if a telephone line fault is present.
1. Introduction System Features Detectors The control unit provides connections for up to eight separate detector zones. Each zone can be connected as a two wire Fully Supervised Loop (FSL) or a four wire Closed Circuit Loop with global tamper. See "4. Programming - Programming Commands" for the factory default settings and instructions on how to change the zone types and attributes. 9954 Hardwired Expanders Each 9954 Expander provides an extra eight hardwired zones.
1. Introduction The 868MHz operating frequency is a European standard reserved specifically for alarm installations. By using this frequency all wireless zones are free of interference from other wireless systems. See the separate "9955 RFX Installation and Programming" manual for more details. User Control The control unit provides 16 independent user access codes and a separate Duress code. The user can change these codes at any time, but cannot program the system with these codes.
1.
2. Technical Description 2. Technical Description Specification Operating temp. -10° to +55°C Humidity 96% RH Note: some versions of the 9752 use the Euro combi box. Dimensions Junior combi box: 243mm W, 234mm H, 87mm D Euro combi box: 310mm W, 385mm H, 95mm D Weight Junior combi box: 2.45 kg (without stand-by battery) Euro combi box: 4.4 kg (without stand-by battery) Internal Clock = ±10 minutes over one year (depending on the accuracy of the mains supply frequency).
2. Technical Description Control Unit PCB Figures 3 and 4 show the layout of the 9751 and 9752 PCBs. 12V AUX F-1A 12V Aux fuse 21VAC from transformer Kick start pins BATT F-2A Outputs Battery fuses Battery connector Aux Power NVM Reset pins Communications connector (for plug-by communicator) Tamper switch Zone Connectors Telephone line terminals for built-in communicator Telephone connector for built-in communicator Keypad and expander bus Figure 3.
2. Technical Description 12V AUX F-1A 12V Aux fuse 21VAC from transformer Outputs Kick start pins BATT F-2A Battery fuses Battery connector Aux Power NVM Reset pins Communications connector (for plug-by communicator) Tamper switch Connector Zone Connectors Local Download connector Telephone line terminals for built-in communicator Telephone connector for built-in communicator Keypad and expander bus Figure 4.
2. Technical Description 9954 Expander The 9954 Expander provides connectors for either eight four-wire CC loop zones, FSL or EOL zones. Figure 5 shows the layout of the PCB. CC/FSL/EOL Jumpers Lid Tamper switch AT6 EOL AT5 CCT2 FSL Zone Connectors CCT1 AT1 CCT5 AT2 CCT6 CCT3 AT7 CCT4 AT8 AT3 CCT7 AT4 CCT8 2 3 4 Spare Connectors (Not connected) Zone Connectors Addressing pins Keypad bus 0V 12V CLK DATA Figure 5.
2. Technical Description Compatible Equipment 715rEUR-00 719rEUR-00 725rEUR-55 726rEUR-00 735rEUR-00 746rEUR-00 747rEUR-00 9928EUR-00 9930EUR-00 9954EUR-00 9955EUR-50 958EUR-00 Radio PIR. Radio Smoke Detector. Radio Remote Setting Device. Radio PA. Universal Transmitter. 868MHz Test transmitter. 868MHz Go/No Go test receiver. Keyswitch interface. LCD Keypad. Hardwired eight zone expander. 868MHz "Class VI" radio expander. Downloader.
2.
3. Installation 3. INSTALLATION Caution: Always remove mains power before opening the case lid. Do not work inside the control unit with mains power present. Overview A typical installation comprises the following main steps: 1. Survey the site and decide on positions for wired detectors, 9954 wired expanders, control unit, keypads, external and internal sounders. As part of the survey ask the user what facilities they need. 2.
3. Installation Cabling Keypads and Expanders Cooper Security recommend that you use 8-core 7/0.2 or 16/0.2 alarm cable for wiring keypads and expanders. You can connect the keypads and expanders in either a star or bus configuration (see Figure 6). If you are intending to use long cable runs then Cooper Security recommend that you use star wiring. Control Unit 200m 200m 200m 200m 200m Distribute devices along cable for better performance. Keypads or expanders Figure 6.
3. Installation 2. Make sure that the voltage between 0V and 12V of the keypad bus at the furthest point from the control unit is at least 12.0VDC when all the keypad backlights are on. Note: The following instructions assume that you have already run the necessary cabling. Fitting the System Fitting the Control unit Case 1. 2. 3. 4. Remove the control unit case from the packing. Remove the front screws and slide off the case lid. The upper part of the case back provides a central keyway.
3. Installation Cooper Security recommend that you mount the keypad using No 8 or 6 screws (M4/M3.5) as follows: 1. Select which cable entry you are going to use and break out the appropriate plastic sections. 2. Hold the backplate in place against the wall and mark the position of the centre hole in the adjustable cam (see Figure 7). 3. Drill and plug the hole, and screw the backplate to the wall through the adjustable cam. Do not tighten the screw completely home. 4.
3. Installation To Control Panel Transformer L N 230V ~50Hz 200mA T 250mA 250V Figure 8. Mains Connection Connect the 21VAC lead from the mains transformer to the main pcb. See Figure 3 or 4 for the location of the 21VAC connector. Caution: Do not apply mains power at this point. Do not work inside the control unit case when mains power is present. Remote Keypads Keypad Addressing The control unit is supplied with one remote keypad.
3. Installation Keypad Backlight When supplied from the factory the control unit is configured with the keypad backlight ON. To turn the keypad backlight OFF remove the jumper from the "ON BACKLIGHT" link, shown in Figure 9. Connecting Keypads, Exit Terminate Buttons, Lock Switches and Sounders Figure 10 shows the connections for any of the remote keypads. To connect an exit terminate button use the "ET" terminals on the keypad PCB. See Figure 10. Use the "ET" terminals to connect a Lock Switch.
3. Installation Typical Internal Sounder 16 Ohm Loudspeaker (2 Max.
3. Installation Detector Circuit Connections The left hand edge of the main PCB provides 14 connectors that can be used for up to 8 FSL zones, or 8 Closed Circuit zones. During programming use command 21 to configure these connectors as either CC zones, or two wire FSL zones. Closed Circuit Zones Figure 11 shows how to connect Closed Circuit zones. Note that there is one tamper loop that serves all zones. The control panel provides enough connectors for eight circuits.
3. Installation 4K7 Alarm contacts Zone 1 2K2 EOL Tamper contacts 1 2 4K7 Zone 2 Note: You can leave the global anti tamper connectors unlinked if you are using FSL wiring. Alarm contacts 2K2 EOL Tamper contacts Yellow Violet Red 4k7 Red Red Red 2k2 Gold Gold Figure 12. FSL Connections Connecting Expanders Figure 13 shows how to wire 9954 and 9955 Expanders to the control unit. Control Unit 0V 12V CLK DATA Expander 0V 12V CLK DATA To other keypads and expanders. EOL FSL Figure 13.
3. Installation Once you have connected an expander refer to the instructions supplied in order to connect detectors. Once you have connected a 9955 expander then refer to the instructions supplied in order to "learn" radio detectors to the expander. Using Programmable Outputs In the 9751 OP1, 2 and 3 are "pull down type" outputs that provide negative applied control signals. The system adjusts the output polarity when you select the output type.
3. Installation Wiring Keyswitches Figure 16 shows the connections for a 9928 Keyswitch Interface. Note: You can fit only one keyswitch interface per system. Momentary or Continuous Keyswitches The 9928 keyswitch interface can be connected to either momentary or continuous keyswitches, see Figure 16. When using a momentary keyswitch remove the jumper from link M/C. When using continuous keyswitches fit a jumper to link M/C.
3. Installation To use this facility, the local exchange must provide the Three Way Calling service on the customer's line. Line Monitoring The 9751 and 9752 provide a Line Monitor function programmed by command 106 to ensure that the telephone line is connected and working, and to indicate a line failure. While enabled Line Monitor continually checks the line voltage to ensure that the line is connected.
3. Installation In the event of problems you should contact your equipment supplier in the first instance. The built in communicator has been approved for the following usage: (a) Automatic call initialisation. (b) Operation in absence of proceed indication. (c) Automatic Dialling. (d) Modem. (e) Serial Connection. (f) Multiple Repeat Attempts. (g) Line Status Monitoring.
3. Installation 21VAC from Transformer S.E.L.V. cct + LS 12V AUX 12V AUX Battery Connector S.E.L.V. cct 0V 0V A/T CCT1 Main Connector S.E.L.V. cct Wire-in comms Connector S.E.L.V. cct CCT2 CCT3 Tamper switch Connector (9752 only) S.E.L.V. cct CCT4 CCT5 CCT6 CCT7 CCT8 Local Download Connector (9752 only) S.E.L.V. cct 0V 12V CLK DATA RJ11 Connector T.N.V. cct. Telephone Line Connections T.N.V. cct. Keypad Connector S.E.L.V. cct Figure 17.
3. Installation b) If the wiring is not owned by British Telecom, either: (i) British Telecom (ii) The authorised maintainer (iii) A professional installer after 14 days written notice to the authorised maintainer. Connect the telephone line as follows: If the telephone line is already terminated with a suitable lead and plug then insert the plug into the RJ11 connector (see Figure 17). Otherwise (see Figure 18): 1.
3. Installation Fitting a Plug-by Communicator The 9751 or 9752 can be fitted with a communicator or speech dialler (for example the Scantronic 8400, 8440, 660 or RedCare STU). To fit a communicator, follow the instructions below. Caution: Follow the instructions in the order shown, or you may damage the control unit and/or communicator. 1. 2. Disconnect mains power, remove case lid and disconnect battery power from the control unit, if the system has already been installed.
3. Installation Com Connector Cable, Part No.
3. Installation If the system has already been installed: 5. Re-connect the battery. 6. Fit the case lid. 7. Apply mains power. 8. Test communicator operation (see programming commands 151 to 158). Fitting a Battery Fit a rechargeable battery into the back of the case. If using a Junior Combi Box the case provides space for a 12V 7AH battery. Make sure the battery terminals are oriented in the position shown in Figure 22. 7AH Figure 22.
3. Installation Initial Start Up Before applying power to the control unit, ensure that: • All remote keypads and expanders have been addressed and connected. • All external and internal sounder are connected. • All wired zone circuits are connected. • All wireless zones have been learned to their expanders. Then: 1. Connect the battery to the control unit PCB. 2. Briefly short the kick start pins together (they are located above battery fuse, see Figures 3 or 4).
3.
4. Programming 4. Programming Entering Programming Mode “3. Installation - Initial Power Up” describes how to enter programming mode for the first time in a new installation. If you wish to enter programming mode at any other time: 1. Make sure the system is unset. Note: If you have selected defaults for Norway, Sweden or Denmark then you must enter a valid user code at this point. 2. Press 0, then key in the Engineer’s code (default 7890). Installer The display shows: You are now in programming mode.
4. Programming To change: Key-in: Notes Y Y Default Country Selection 0 nn nn = country, one of: 0 = UK (Y) 5 = France X1 = Ireland X6 = Denmark 1 = Italy 6 = Belgium X2 = OEM 1 X7 = Sweden 2 = Spain 7 = Germany X3 = OEM 2 3 = Portugal 8 = Switzerland X4 = OEM 3 4 = Netherlands 9 = Austria X5 = Norway Note: If you carry out this Command then the system will load all defaults for the selected country. To change language displayed on keypad see Command 126.
4.
4. Programming To change: Key-in: Level A Exit Mode 39 Y System Auto Re-Arm 40 Y Bell Delay 41 Y Bell Duration 42 Y Level A Entry Time 43 Y Level A Exit Time 44 Y Entry/Exit Volume 45 Y Tamper Alarm Response 46 Y Lockout Kpds During Entry 48 Y CSID Code Y 36 50 Notes Default 0 1 2 3 Timed Terminated Final door set Lock Set Y 0 1 2 3 4 Rearm Never Rearm 1 Rearm 2 Rearm 3 Rearm Always Y 0 1 2 3 4 5 6 No delay 1.
4. Programming To change: Key-in: Set Time and Date Omit Tamper Allowed Abort reset Notes Y .....
4.
4.
4. Programming To change: Key-in: Notes Test Internal Sounder 94 Y Test Keypad Sounder 95 Y Engineer Walk Test* * See “5. Testing” 97 Y Load Defaults 98 1 Leave Programming Default Internal sounders operate, press X or end test. Keypad sounders operate, press X or end test.
4.
4.
4. Programming To change: Key-in: Notes Default Note: The following Commands are available if you select option 1 for Command 89. Y Confirm Timer 160 nnn nnn is a time in the range 001 to 999 minutes. Default 030 minutes.
4. Programming Restoring the Access Codes (1st stage reset) If the user and/or engineer codes are lost, then: 1. First remove mains power and then open the case and disconnect the battery. 2. Identify the NVM Reset pins and Kick Start pins on the main pcb (see Figure 4). 3. Short the NVM Reset pins together using a small wire link, and short the Kick Start pins together using another small wire link. 4 Reconnect the battery. 5. Remove the short from the NVM Reset pins and Kick Start pins.
4. Programming Zone Programming (Commands 01 to 24 (32 on 9752)) The zone programming Commands 01 to 32 take three or more digits. The first two digits describe the zone type, subsequent digits describe the zone attributes. The format for a zone Command number changes, depending on whether the zone is connected to the control unit or to an expander. For the first 16 zones key “01” to “16” and press .
4. Programming Zone Types The following types are available: Not Used (NU) The system ignores Zones with this type. Key in 00 for a zone that will not be used. Note: If a zone is programmed as ‘Not Used’, it is not necessary to link the circuit or anti-tamper connections. Panic Alarm (PA) (Key in 01) Operating a device programmed as ‘Panic Alarm’ will start either a silent alarm transmission to the ARC, or an audible alarm, depending on how you have programmed PA Response, (see Command 30).
4. Programming Technical (TC) (Key in 08). Use this zone type when you want to monitor equipment, for example a freezer, without raising a full alarm. If a technical alarm zone is activated while the system is set, the system makes no audible alarm. However, when a user unsets the system the keypad indicates a fault.If a technical alarm zone is activated while the system is unset then the system starts a pulsed tone from the keypad. If programmed, the control unit also starts communication.
4. Programming To set Level A do not assign a Keyswitch zone to levels B, C or D. To set any other level assign the Keyswitch zone to a single level. Momentary - KM (Key in 11). Use this zone type to connect a momentary keyswitch to a single zone. Fixed - KF (Key in 12). Use this zone type to connect a fixed position keyswitch to a single zone. Anti-Mask Zone (AM) (Key in 13). This zone type is for use in Scandinavia only.
4. Programming days after you return the control unit to user mode. If the zone is opened while the system is set then the Service LED glows and the control unit logs the event as a “Soak Test Fail Zn” (n is the zone number) without sounding any bells or starting signalling. The Service LED stays alight until the Engineer resets the system. After midnight on the 14th day the control unit returns the zone to normal use.
4. Programming Change Engineer Code (Command 20) To change the Engineer access code: 1. Make sure you are in programming mode. 2. Key in 20 and press . The display shows: Y 3. Key in a new four digit Engineer access code. The display shows: 4. Press 20:Code 20:Code **** Y. Zone Configuration (Command 21) This Command allows you to select the wiring type of the zone connectors on the main PCB. The options available are: Option 0 Closed Circuit four wire with global anti tamper.
4. Programming Continuous Sounder (Command 25) Option 0 of this Command makes the internal sounder follow the external bell delay and duration times. Option 1 makes the internal sounder continue after the external bell times out. Local Sounder Delay on Entry (Command 26) This Command controls the time at which local sounders operate in response to an entry alarm. Option 1 (default) introduces a delay to allow silent communications when an entry alarm is triggered (required by some police forces).
4. Programming This Command determines what the system will do if a user strays from an entry route during entry. (This Command is available to provide compliance with EN 50131-1.) Use option 0 to make the system give an alarm immediately if the user strays from an entry route during entry. If you use option 1 and the user strays from an entry route zone during entry then the system waits 30 seconds before raising a full alarm. The system also gives an internal alarm during the 30 second wait.
4. Programming PA Reset (Command 34) If you wish to make the system engineer reset after a PA alarm then use option 1. For user reset use option 0. First Circuit Response (Command 35) If you select option 0 (Lock out) then the complete system rearms at the end of the programmed bell run time, but excludes the first zone to activate during the set cycle.
4. Programming select option 1 (engineer) then you must enter the engineer access code at a keypad to reset the system after a system tamper alarm. Level A Exit Mode (Command 39) Use this Command to select the exit mode for Level A (full set): Option 0 Timed. Use this option EITHER if the user completes setting the system by pushing an exit terminate button connected to a keypad OR if no exit terminate button is connected, and the system sets after a delay selected using Command 44. Option 1 Terminate.
4. Programming Note that the keypads give a double beep confirmation tone at the end of all setting modes. If you select Timed (options 0), Terminate (option 1), or Final Door (option 2) exit modes the system allows a seven second settling time after pressing an exit terminate button or closing a final door. System Auto Re-Arm (Command 40) This Command lets you program the number of times that the system will rearm when the bell delay expires. The system re-arms all closed zones.
4. Programming Entry/Exit Tone Volume (Command 45) Use this Command to set the volume of entry/exit tones from the internal sounder. If you select option 0 then the internal sounder gives no entry/exit tones. If you select option 1 then the internal sounder gives quiet entry/exit tones, while option 9 gives the loudest entry/exit tones. The internal sounder demonstrates the volume of the tone when you enter the digit.
4. Programming displays it on the keypad. The user calls the ARC and tells them the number shown on the keypad display. The ARC verifies the user's identity, then enters the code number into a special programmer. The programmer generates an ‘Anti Code’, which the ARC gives back to the user. The user then enters the ‘Anti Code’ at the keypad to reset the system. Note: To delete a CSID code key in “0000” over the existing code.
4. Programming contact with the control unit for more than 15 minutes. If a detector loses contact for more than two hours the control unit raises an alarm (see Command 128). If you select option 0 the control unit will report supervision failure as described for Command 128. Number of Digits in Access Codes (Command 56 (9752 only) ) The 9752 control unit can use either four-digit or six-digit access codes. To select four digit access codes choose option 0. Select option 1 for six digit access codes.
4. Programming Level B Final Exit Operation (Command 60) Command 60 controls how the system will treat Final Exit zones in Part Set Level B. When the Command option is set to 0 any Final Exit zones included in Part Set B will continue to act as Final Exit zones during Part Set B. When the option is set to 1 any Final Exit zones included in Part Set B will act as Normal Alarm zones during Part Set B.
4. Programming Level B Exit Time (Command 65) This Command sets the exit time for Level B. See “Programming Commands” for options. Level C Final Exit Operation (Command 70) Command 70 controls how the system will treat Final Exit zones in Part Set Level C. When the Command option is set to 0 any Final Exit zones included in Part Set Level C will continue to act as Final Exit zones during Part Set Level C.
4. Programming Level C Entry Time (Command 74) This Command sets the entry time for Level C. See “Programming Commands” for options. Level C Exit Time (Command 75) This Command sets the exit time for Level C. See “Programming Commands” for options. Level D Exit Mode (Command 76 (9752 only)) Command 76 specifies the exit mode for Level D. Option 0 The keypad sounders and any internal sounders give a low tone when entering Part Set Level D. Use Command 79 to select the exit time.
4. Programming Output Type Bell EE Follow Armed lamp PIR Set Latch Shock Reset Walk Test Ready Lamp 24 Hour alarm 62 (Key in 00) The control unit operates this output during an alarm. Use Command 41 to control bell delay and 42 to control bell duration. If you enable Alarm Confirmation (Command 89) then use Command 162 to select whether the control unit activates the bell on a first or a confirmed alarm.
4. Programming Strobe Smoke Reset Siren Test Strobe Set Pulse Set Pulse Unset Alarm Confirm Set Complete Unset Complete (Key in 08) In an alarm the system operates the output. The output remains active until the user disarms the system. (Key in 09) This output is designed to be connected to low voltage smoke detector reset terminals. The control unit operates the output for 3 seconds when the system is reset after any alarm has occurred.
4. Programming 3. If Alarm Abort is enabled (Command 36 1) Channel 3 restores if the user unsets the system. Dual Ply Entry Warning (Command 86) Note: Disable Alarm Confirmation (Command 89) to gain access to this Command. If users habitually exceed the entry time use option 1 to add a 30 second extension during which the internal sounders give a warning tone. The extension applies to both Full and Part setting.
4. Programming 3. 4. X Press 1. (You can press to stop the procedure if you change your mind at this stage.) Press . The system loads the factory default Command values, erasing all previously programmed values. Y Notes:The log is protected and cannot be erased by the Installer. Leave Programming Mode (Command 99) To leave programming mode: 1. Key in 99 at the keypad. The display shows: Y 2. Exit Eng? Y Press .
4. Programming Dual (3) Reports to two different receiver numbers (see Commands 115 and 116). Operation: The communicator dials the first telephone number and attempts to connect to the first ARC. If received and acknowledged, the communicator dials the second number and attempts to transmit to the second ARC. If received and acknowledged by the second number, the communicator will close down and the alarm transmission will be complete.
4. Programming Line Fail Response (Command 106) This Command lets you program the system to respond with either audible or silent alarms when the system detects a fault on an attached telephone line. The exact response depends on whether the system is set or unset, as follows: Disabled (0) The control unit does not monitor the telephone line. Audible (1) If the system is unset then the system logs the event. The keypad produces a short audible tone every minute.
4. Programming (which represents the “R” or Recall button on a telephone) which is detected by the exchange as a request for a new clean line. With the new line available, the communicator then attempts to connect to the pre programmed receiver number. Engineer Download (Command 110) The control unit can be programmed from a PC using software. You can connect the PC to both the 9751 and 9752 control units over the telephone network.
4. Programming alarm system now knows to expect a call within the next 10 to 90 seconds. then rings the alarm system again, within 10 to 90 seconds. The alarm system answers after the first ring. Note: When using "Answer on 1 Ring" set the number of rings in "Rings to Answer" (C112) to a higher number than that used by the equipment sharing the telephone line with the alarm system. If you do not, then the other equipment will never answer any incoming calls.
4. Programming Communicator Telephone Numbers (Command 115/116) Use this Command to store the telephone numbers that the communicator will use to report alarms. The system will accept one telephone number if you choose Single call mode in Command 101, or two telephone numbers if you select Alternate or Dual call mode. The system can store telephone numbers up to 31 digits long. You can use the A key to insert a pause (four seconds). To enter a number: 1.
4. Programming Downloader Telephone Numbers (Commands 118/119) Use this option to program up to two separate, 31-digit telephone numbers that the system will use during downloading. When a connection has been made, the remote PC operator selects the telephone number which the control unit will call back to (for example home or office). You can use the A key to insert a pause (four seconds). To enter a number: 1. Enter programming mode (if you are not already there). 2. Key in 118 (or 119) at the keypad.
4. Programming Notes:1. 13 Open and 14 Close provide the same functions as 4 Open/Close, but on two separate channels. 2. 15 Zone omitted - the control unit sends this signal for five seconds when a user omits a zone. 3. The control unit sends 08 RF Low Battery when the radio detector with a low battery causes an alarm or sends a supervision signal. To enable this facility in day mode set Menu 37 to option 1. 4.
4. Programming No Closing Signal if More Than One Circuit Omitted (Command 125 (9752 only)) Note: This Command is required for Belgian BVVO approval. This option is only available if you have selected Scancom Fast format. When this option is enabled the control unit will NOT transmit a Close signal if a user has omitted two or more zones. Select Language (Command 126) The control unit can display messages on the keypads in one of several different languages.
4. Programming Report Mode (Command 131) SIA reports are called ‘Telegrams’. Each telegram contains the site identification number (normally six digits long) and relevant event information. The amount of information reported depends on the SIA mode you select: Basic, Summary, Intermediate, or Full. Figure 24 shows the types of report for each mode. Use the table to decide which mode is appropriate for the installation.
4.
4. Programming If the keypad display shows “Custom” when you enter Command 143 then has been used to program this Command. Plug by Communicator Outputs (Commands 151 to 158) The main circuit board of the control unit provides eight programmable outputs that can be used to control a plug-by communicator. The outputs can be connected to the communicator by an twelve-way wiring harness provided with the control unit. See “3.
4. Programming Internal Sounder (Command 161) Note: Enable Alarm Confirmation (Command 89) to access this Command. This Command selects whether the control unit will operate the internal sounder for a confirmed alarm of for an unconfirmed alarm. Option 0 The control unit operates the internal sounder for an unconfirmed alarm. Option 1 The control unit operates the internal sounder for a confirmed alarm. External Sounder (Command 162) Note: Enable Alarm Confirmation (Command 89) to access this Command.
4. Programming Option 2 ensures that if the user unsets the system by means of a proximity reader or telecommand, they cannot cause a confirmed alarm by wandering from the entry route. However, if an intruder goes through the front door, they will eventually cause a confirmed alarm if they are still wondering around the premises after the entry time has expired. User Reset After Confirmed Alarm (Command 164) Note: Enable Alarm Confirmation (Command 89) to access this Command.
4. Programming ACPO DD243: 2002 Compliance Please study this section If you are installing an intruder alarm system in England, Wales and Northern Ireland which has remote signalling, requires the local Police Authority to issue a URN (Unique Reference Number) and you have chosen to use “Sequential Alarm Confirmation” to comply with DD243: 2002.
4. Programming Confirm After Entry = 2 = The control unit starts a confirmed alarm if an intruder activates two separate zones after the entry timer expires. Use this option to comply with section 6.4.5. Command 164 – User Reset After Confirmed Alarm = 1 = enabled to allow users to reset the system after a confirmed alarm. The table opposite summarises which options to select on various Commands in order to comply with paras 6.4.2 to 6.4.6 DD243: 2002 Para: Set/unset method 6.4.
5. Testing 5. Testing Reading the Log (Command 90) The control unit keeps a 250 event log of recent events. Each event is represented by a short text message, shown below and on the next page. To review the event log, make sure the system is in programming mode, then: 1. Key in 90y. The display shows the most recent event in the log. For a list of the log messages see below. 2. Key in 1 to show earlier events or 3 to see more recent events. 3. Press y to toggle between the event message and the event time.
5.
5. Testing Telecmmd PA Unn Change Unn Unn Delete Unn Unn Off-Site Unn On-Site Bypass Supr.
5.
Index Index Chime ...................................................... 48 Command 0 (zero) .................................................................. 44 01 to 32 ................................................................. 45 101 ........................................................................ 65 103 ........................................................................ 66 105 ........................................................................ 66 106 .........................
Index 61 .......................................................................... 59 62 .......................................................................... 59 63 .......................................................................... 59 64 .......................................................................... 59 65 .......................................................................... 60 70 .......................................................................... 60 71 .................
Index H M Humidity .................................................... 7 Mains connection .................................... 16 I N Inputs ........................................................ 7 Installation overview ............................... 13 Internal sounder No close if.. ............................................. 73 Normal alarm .......................................... 46 Not used ................................................. 46 confirmed alarm ............................
Index Report mode ........................................... 74 contact ID .............................................................. 75 fast format ............................................................. 71 SIA ........................................................................ 74 Report restorals ...................................... 72 Contact ID ............................................................. 75 Reporting type ........................................
Notes
DECLARATION OF CONFORMA NCE Cooper Security Ltd issues this certificate to certify that the equipment known as: 9751 or 9752 Complies with the following directive: 1995/5/EC R&TTE Directive Signed Mr S. Taylor, Technical Director Date: 4 September 2002 Cooper Security Ltd Security House Vantage Point Business Village Mitcheldean Gloucestershire GL17 0SZ Product Support (UK) Tel: (09068) 616343. Hours: 08:15 to 17:00 Monday to Thursday, 08:15 to 12:45 Friday. 12:45 to 17:00 Friday emergency service only.