User guide
4. Programming
Page 42 496929
output for 3 seconds when the system is reset after any alarm has
occurred.
10 Siren Test. - This output becomes active when the Installer performs a
sounder test using Command 91.
11 Strobe Set. - This output is active for 10 seconds after the system has
set. The output can be used to operate the strobe to give a visual
indication that the system has completed setting.
12 Pulse Set o/p 1. - This output becomes active for a programmable
time period between 1 – 12 seconds (in command 170) & when the
assigned level(s) (ABCD) (in command 171) is set.
13 Pulse Unset o/p 1. - This output becomes active for a programmable
time period between 1 – 12 seconds (in command 172) & when the
assigned level (ABCD) (in command 173) is set.
26 Pulse Set o/p 1. - This output becomes active for a programmable
time period between 1 – 12 seconds (in command 170) & when the
assigned level (ABCD) (in command 171) is set.
27 Pulse Set o/p 2. - This output becomes active for a programmable
time period between 1 – 12 seconds (in command 170) & when the
assigned level (ABCD) (in command 171) is set.
28 Pulse Set o/p 3. - This output becomes active for a programmable
time period between 1 – 12 seconds (in command 170) & when the
assigned level (ABCD) (in command 171) is set.
29 Pulse Set o/p 4. - This output becomes active for a programmable
time period between 1 – 12 seconds (in command 172) when
someone unsets the A or B or C or D levels (in command 171), or
during a fire or PA alarm (if the function is selected in commands 174
or 175).
30 Pulse Unset o/p 1. - This output becomes active for a programmable
time period between 1 – 12 seconds (command 172) when someone
unsets the A or B or C or D levels, or during a fire or PA alarm (if the
function is selected in commands 174 or 175).
31 Pulse Unset o/p 2. - This output becomes active for a programmable
time period between 1 – 12 seconds (command 172) when someone
unsets the A or B or C or D levels, or during a fire or PA alarm (if the
function is selected in commands 174 or 175).
32 Pulse Unset o/p 3. - This output becomes active for a programmable
time period between 1 – 12 seconds (command 172) when someone
unsets the A or B or C or D levels, or during a fire or PA alarm (if the
function is selected in commands 174 or 175).