User guide
4. Programming
496929 Page 39
71: Level C Entry Route Operation
Command 71 controls how the system treats Entry Route zones during part
set Level C. When the option is set to 0 all Entry Route zones included in part
set Level C will continue to act as Entry Routes during part set Level C. When
the option is set to 1 any Entry Route zones included in part set Level C will
act as Final Exit zones during part set C.
72: Level C Exit Mode
Command 72 specifies the exit mode for Level C.
Option
0 Low Tone. Timed set with the exit tone fixed at half volume. Use
Command 75 to select the exit time.
1 Instant Set (no exit tone)
2 Silent Set. (Timed Set with no exit tone) .Use Command 75 to
program the Exit time.
3 As A. The exit mode chosen for Level A (whole system) is also
applied to this level.
Note: The keypads give a double beep confirmation tone at the end of all
setting modes.
73: Level C Alarm Response
Command 73 specifies the alarm response for Level C.
Option
0 Keypad sounders only.
1 Internal sounders and keypad sounders.
2 Local alarm (internal and external sounder only).
3 Full alarm (communication outputs and internal/external sounders).
74: Level C Entry Time
This Command sets the entry time for Level C. See “Programming
Commands” for options.
75: Level C Exit Time
This Command sets the exit time for Level C. See “Programming Commands”
for options.
76: Level D Exit Mode
Command 76 specifies the exit mode for Level D.
Option