User guide

4. Special Functions
Page 14
3.
Press the number of the zone you want to
omit (for example, press 07 to omit zone
7) and then press .
The sounder gives a double "beep" and
the display shows the zone number
followed by an "o":
Omit Zone 07o
If you try to omit a zone for which this is
not allowed, the display shows an "X"
after the zone number.
Omit Zone 07X
4.
Press to exit.
Note: To include a zone that was omitted, follow the same procedure.
Pressing
toggles between omit and include.
When you set the system after omitting some types of zones, a message asks
you to confirm that you want to omit the zone. Press to set the system with
the zone omitted.
The zone types for which a message is displayed are: Normal Alarm (NA), 24-
hour (24), Final Exit (FE), and Entry Route (ER)..
The zone types for which a message is not displayed are: Hold Up Alarm
(HUA), Fire (FR), Technical (TC), AC Fail (AC), Low Battery (LB), Battery
Fault (BF) and Fault (FL).
Key 3: Requiring User Code before Installer Code
You can specify that a user code must be entered before the installer code to
access the installer menu. This enables you to supervise installer activities.
1.
Key in an access code (or present a tag).
2.
Press 3 to toggle between requiring and
not requiring a user code.
The display shows (for example):
UserCode req=OFF
When you turn user code on or off, the
keypad confirms with a double "beep".
3.
Press .