Installation Manual
Table 1. Shear Bolt Stripback Dimensions
Length
Variable Measurement Name Tolerance
Connector
Code S1 S3 S4
Allen Wrench
(mm) 5 8 8
Centering Ring
with or without
in (mm)
A Bushing to Cable (+/-0.25) 2.00
(50.8)
2.00
(50.8)
2.00
(50.8)
B Jacket (+/-0.25) 12.00
(304.8)
12.00
(304.8)
12.00
(304.8)
C Insulation Shield (+/-0.125) 9.38
(238.2)
9.38
(238.2)
9.38
(238.2)
D Conductor (+/-0.125) 2.75
(69.85)
3.38
(85.85)
4.00
(101.6)
E Cable Adapter Check Maximum 7.25
(184.1)
7.25
(184.1)
7.25
(184.1)
Table 2. Conductor Size and Type
Compression Connector Shear Bolt Connector Sizing
Concentric or
Compressed
Compact or
Solid
Compression
Conductor
Code
AWG or Kcmil
mm
2
Stranded &
Compressed
Shear Bolt
Conductor
Code
Shear Bolt
Catalog
Number
AWG or
kcmil mm
2
AWG or
kcmil mm
2
Concentric Compressed Compact min max
No Connector 00 3/0 3/0 3/0
95 150 S1 CDT630SB150
#2 35 1 - 11 4/0 4/0 4/0
#1 - 1/0 50 12 250 250 250
1/0 50 2/0 70 13 - - 350
2/0 70 3/0 - 14 350 350 -
185 300 S3 CDT630SB300
3/0 - 4/0 95 15 500 500 500
4/0 95 250 120 16 600 600 600
250 120 300 - 17 - - 700
300 - 350 - 18 700 700 -
400 S4 CDT630SB400
350 - 400 185 19 750 750 750
400 185 450 - 20 - 800 800
450 - 500 240 21 - - 900
3
600 A 15/26 kV class DT625 T-body installation and cable preparation instructions S600-46-2 July 2014 www.cooperpower.com