Installation Manual
ote:N If concentric neutral cable is not being used,
follow cable preparation directions in shield
adapter kit.
Equipment provided
•
DT625 T-body Kit includes:
• T-body
• Cable Adapter
• Shear Bolt Connector
• Silicone Lubricant
• Instruction Sheet
Tools required
•
Torque Wrench
•
5/16” Hex Wrench for Splice Application
•
Cable Stripping Tools
•
5 mm or 8 mm Allen Wrench
Installation of connectors
Shear bolt installation procedure
Prepare the cable
Step 1.
Train cable
•
Position cable vertically so that it is centered between
apparatus bushing and parking pocket, parallel to, and 6”
(152 mm) from apparatus frontplate.
•
Provide adequate cable slack for cable movement
between standoff bushing and apparatus bushing.
•
Support cable as needed to maintain position.
•
Cut cable to length “A” from centerline of bushing. (Refer
to Fig ure 3 and Table 1 for “A” length.
Figure 3. Line illustration for cable training.
Bushing
Cable
"A"
(See Table 1)
6"
(152 mm)
B
C
D A
Figure 2. Strip back dimensions.
IMPORTANT
Installation Instructions to be used for 600 A, 15 and 25
kV Class DT625 T-body with shear bolt connector. Please
see page 6 for installation instructions using a compression
connector.
2
600 A 15/25 kV class DT625 T-body installation and cable preparation instructions S600-46-2 July 2014 www.cooperpower.com