Installation Manual
Step 10.
Check di men sions
•
Check length from end of com pres sion con nec tor to top
of cable adapter.
•
Length should be be tween 6.50-7.25” (165 - 184 mm).
Re fer to Fig ure 23.
Install BOL-T T-body with mating parts
Step 11.
Install DT625 T-body
•
Clean and lubricate outside of cable adapter with lubricant
supplied.
•
Clean and lubricate inside of T-body with lubricant
supplied.
ote:N If test point T-body is used, insure test point is
opposite front plate side of T-body.
•
Without moving the cable adapter, slide T-body onto cable
adapter until compression connector eye is centered in
600 A interfaces. Refer to Figure 24.
ote:N The end of the cable adapter must line up with
the top edge of the tape marker after T-body
assembly. Refer to Figure 21.
•
Remove tape marker from cable.
•
Go to Step 12, page 11 to complete T-body termination.
Figure 23. Line illustration for dimensional check.
6.50-7.25"
(165-184 mm)
Cable
Adapter
Concentric
Neutral Wires
Tape Marker
Compression
Connector
Figure 24. Line illustration of BOL-T T-body installation.
T-body
Cable Adapter
Tape Marker
Concentric Neutral Wires
Lubricate
600 A Interfaces
Apparatus
Bushing
Test Point on
Accessible Side
10
600 A 15/25 kV class DT625 T-body installation and cable preparation instructions S600-46-2 July 2014 www.cooperpower.com