Specifications
Chicago Code –
Emergency Light
70
Applications
• General purpose applications
Specifications
• Dual-voltage input 120/277 VAC,
60Hz
• 20-gauge, die-formed steel
housing
• Knockout, conduit or cord set
• Flanged for mounting in
grid-type suspended ceilings
• Single modular electrical
connector
• Line-latching, solid-state voltage
limited charger, solid-state
switching, low-voltage
disconnect, brownout circuit,
overload/short-circuit protection,
test switch/power indicator light
• Meets or exceeds all current
UL924 requirements, Life Safety
Code (NFPA 101), NEC/OSHA,
most state and local codes.
• City of Chicago approval
number 3238
• Chicago plenum mark
(CCEA - City of Chicago
Environmental Air)
Steel/Recessed/Chicago Code
Emergency Lighting
GC Series
Steel/Recessed/Chicago Code
Emergency Lighting
GC Series
5-1/8"
[130mm]
6-3/4"
[171mm]
23-1/4" [591mm]
6-3/4"
[171mm]
Ordering Information Lamp Information
Rated Wattage to 87 1/2% of Rated D.C. Voltage
Model DC Voltage 2 Hours 3 Hours 4 Hours Type Wattage Number
GC15072 6 24 18 14 Halogen 12 29-15
Energy Data
Input Current (Max.):
Model No. 120V 277V
GC15072, GC15072CL .12A .05A
Visit www.cooperlighting.com for more information on the complete Sure-Lites Stock and
Specification offering. Product availability subject to change without notice.