Specifications
Steel/Chicago Code
Emergency Lighting
XR Series
69
Applications
• General purpose applications
Specifications
• Dual-voltage input 120/277 VAC,
60Hz
• 22-gauge, die-formed steel
• Two fully-adjustable metal
heads with die-cast swivel -
top mounted
• Sealed lead calcium batteries
• Knockout, conduit or cord set
• Universal J-box mounting
pattern with keyhole slots
• Remote capability
• Line-latching, solid-state voltage
limited charger, solid-state
switching, low-voltage
disconnect, brownout circuit,
overload/short-circuit protection,
test switch/power indicator light
• Meets or exceeds all current
UL924 requirements, Life Safety
Code (NFPA 101), NEC/OSHA,
most state and local codes.
• City of Chicago approval
number 3238
Steel/Chicago Code
Emergency Lighting
XR Series
Figure 2
Figure 1
11-1/4"
[286mm]
4-1/2"
[114mm]
12-1/4" [311mm]
12-1/4" [311mm]
14-1/2"
[368mm]
7-3/4"
[197mm]
2-1/2"
[64mm]
2-1/4"
[57mm]
2-1/4"
[57mm]
6-1/8" [156mm]
6-1/8" [156mm]
1-7/8"
[48mm]
Model Type DC Voltage 1 1/2 Hours Lamp Watts Remote Watts Figure
XR6C SLC 6 27 24 3 1
XR9C* SLC 6 54 24 30 2
Ordering Information
Rated Wattage to 87 1/2% of Rated D.C. Voltage
Lamp Information
Type Wattage Number
Halogen 12 29-66
Halogen 12 29-66
*XR9C is UL Listed for 4 hours with 24 watt lamp load only – No remote load
SLC=Sealed Lead Calcium