7: Exit the device details page to cancel the override command to the fixture under test (light may turn OFF). Use the mobile application to issue
zone commands to turn the zones back ON to 100%.
8: Calculate the ‘Daylight Factor Sensitivity’ (DFS) value using the noted measurement:
Calculation 1:
__________
÷
__________
=
__________
(M1) or (M2)
Measured
Light Level
(C)alibrated
Light Level
(Result 1)
Calculation 2:
__________
1
=
__________
(Result 1)
(Result 2)
If Result 2 = less than .20
DFS
=
20%
If M1 was used to calculate & Result 2 is greater than or equal to .20
( _________
+
.20)
X
100
=
__________%
(Result 2)
(DFS)
If M2 was used to calculate & Result 2 is greater than or equal to .20
( _________
+
.30)
X
100
=
__________%
(Result 2)
(DFS)
Exit device details
page
Command Zone to
100%
Example 2:
C = 40 lux M1 = 50 lux
Calculation 1: 50 ÷ 40 = 1.25
Calculation 2: 1.25 1 = .25
.25 >.20 so: (.25+.20) X 100 = 45%
DFS = 45%
Example 1:
C = 40 lux M = 38 lux
Calculation 1: 38 ÷ 40 = .95
Calculation 2: .951 = .05
.05 <.20 so:
DFS = 20%
Example 3:
C = 40 lux M2 = 50 lux
Calculation 1: 50 ÷ 40 = 1.25
Calculation 2: 1.25 1 = .25
.25 >.20 so: (.25+.30) X 100 = 55%
DFS = 55%