Installation Instructions

User Manual: WaveLinx Lite (1.5)
www.cooperlighting.com
53
Calibrate a Single Sensor
It is also possible to adjust the closed loop settings for an individual sensor if settings need to be fine-tuned for a single sensor.
Identify the daylight set following the instructions on page 49 and then follow the steps below.
1: Bring the mobile device within range (within 60 feet) of any provisioned WaveLinx Lite device in the desired area.
2: Ensure that the mobile device Bluetooth is turned on, and then open the WaveLinx Lite Mobile Application.
3: In the site list, select a site.
4: In the area list, select the desired area. After a short delay, verify that the area shows that the mobile application is connected to the network.
Tap on the icon if it is necessary to refresh the connection.
5: Tap ‘Daylight’ to open the daylight set list.
6: Tap the row for the desired daylight set.
If desired, enter the
surface light level reading
on the light meter
Adjust each closed loop set to
the correct level
Review success/
failure count
Once all closed loop
sets are adjusted, tap
‘Calibrate’
Successful
Failure: Tap the retry
icon to send again
Once all sets are
calibrated successfully,
tap ‘Close’
IMPORTANT: Before calibration, review the specific device type recommendations for when daylight calibration
should be performed. See “WaveLinx Lite Device Reference Sheets” on page 5 to locate recommendations for the
device being calibrated.