Cut Sheet

Catalog #
Project
Comments
Prepared by
Type
Date
203 Cooper Circle P: 800-553-3879
Peachtree City, GA 30269 F: 800-954-7016
www.coopercontrol.com
• Air-gapswitchensuresnoleakage
currenttoload
•Selectablebuilt-inlightlevelsensor
•NEMAWD7Guideroboticmethod
utilizedtoverifycoveragepatterns
Specications:
Technology: Passive Infrared (PIR) and Ultrasonic (US)
ElectricalRatings:(PerRelay)
120 VAC: Incandescent/Tungsten –
Max. load: 6.7 amps, 800W, 50/60 Hz
Fluorescent/Ballast –
Max. load:10 amps, 1200W, 50/60 Hz
MotorLoad: ¼ HP @ 125 VAC
277 VAC: Fluorescent/Ballast –
Max. load: 9.8 amps, 2700W, 50/60 Hz
347 VAC: Fluorescent/Ballast –
Max. load: 4.3 amps, 1500W, 50/60 Hz
BallastCompatibility: Compatible with magnetic and
electronic ballasts
TimeDelays: Self-Adjusting, 15 seconds/test (10 min.
Auto), Selectable 5, 15, 30 minutes
Coverage: Major motion - 36’ x 30’
Minor motion - 20’ x 16’
LightLevelSensing: 0 to 200 foot-candles
OperatingEnvironment:
• Temperature: 32°F - 104°F (0°C - 40°C)
• Relative humidity: 20% to 90%, non-condensing
• For indoor use only
Housing: Durable, injection molded housing. ABS
resin complies with UL 94V-0.
Size:
• Mounting Plate/Strap Dimensions: 4.195”H x
1.732”W (106.55mm x 44mm)
• Mounting Plate/Strap Dimensions: (ONW-D-1001-
347): 4.35”H x 1.732”W (110.49mm x 44mm)
• Product Housing Dimensions: 2.618”H x
1.752”W x 1.9”D (66.5mm x 44.5mm x 48.26mm)
LEDIndicators:Red LED for PIR detection; Green
LED for Ultrasonic detection.
PIR
Activated
Ultrasonic
Activated
Self-Adjusting
ONW-D,NeoSwitch
DualTech/Single
LevelWallSwitch
Sensor(GroundRequired)
FCC Compliant
cULusListed
RoHSCompliant
Overview
The Dual Technology Single Level Occupancy Sensing Wall Switch is a motion
sensing lighting control and conventional wall switch all-in-one that is used to for
energy savings and convenience. It does not require a neutral wire for installation
making it ideal for retrofit applications.
Description/Operation
The ONW-D-1001-MV combines Ultrasonic (US) and Passive Infrared (PIR) sensor
technologies to monitor a room for occupancy to deliver maximum energy savings
and ensure the greatest sensitivity and coverage for tough applications without the
threat of false triggers. PIR is used to turn the lights ON and then either or both
technologies are used to keep the lights ON. In Automatic On Mode, the lights turn
ON automatically when a person enters the room. In Manual On Mode, the lights
are turned ON by pressing the universally recognized light icon pushbutton. The
sensor includes self-adaptive technology that continuously self-adjusts sensitivity
and time delay in real-time, maximizing the potential energy savings that are
available in the particular application.
Applications
private offices
small conference rooms
lunch/break rooms
small classrooms
small restrooms (1-2 stalls)
small lounges
small waiting rooms
small closets
small storage areas
Ordering
One single gang wallplate included. Wallplate not included with 347 VAC model.
Catalog # Ratings
ONW-D-1001-MV-*
(* - W, V, LA, G, B)
Incandescent: 0-800W @ 120V
Fluorescent: 0-1200W @ 120V
Fluorescent: 0-2700W @ 277V
Max Load/Relay
Coverage
180°; 1000 sq. ft.
Voltage
120/277 VAC,
50/60 Hz
* White, Ivory, Light Almond, Gray, Black
ONW-D-1001-347-*
(* - W, V, LA, G, B)
Incandescent: 0-1500W @ 347V
Fluorescent: 0-1500W @ 347V
Max Load/Relay
180°; 1000 sq. ft. 347 VAC,
50/60 Hz
NOTE: Not all colors are available in stock and some color options may have extended lead times.