Cut Sheet

Catalog #
Project
Comments
Prepared by
Type
Date
203 Cooper Circle P: 800-553-3879
Peachtree City, GA 30269 F: 800-954-7016
www.coopercontrol.com
classrooms
conference rooms
office spaces
common areas
computer rooms
break rooms
hallways
other indoor office spaces
Specifications:
Technology: Passive Infrared (PIR) and Ultrasonic (US)
Power Requirements:
Input:
• 10-30 VDC from Greengate Switchpack or
Greengate system
• Maximum current needed is 25mA per sensor
Output:
• Open collector output to switch up to ten
Greengate Switchpacks
• BAS with Isolated Form C Relay in (-R) model
• Isolated Form C Relay Ratings: 1A 30 VDC/VAC
Time Delays: Self-adjustable, 15 seconds/test (10
minutes Auto), or Selectable 5, 15, 30 minutes, or Zero
Time Delay
Coverage: 500, 1000, and 2000 sq. ft.
Light Level Sensing (-R models): 0 to 300 foot-
candles
Operating Environment:
• Temperature: 32°F - 104°F (0°C - 40°C)
• Relative humidity: 20% to 90%, non-condensing
• For indoor use only
Housing: Durable, injection molded housing.
Polycarbonate resin complies with UL 94V-0.
Size: 4.5”H x 1.42”W (114.3mm x 36.068mm)
Mounting: Mounts directly to ceiling tile, to a 4”
square box and round mud ring or to 4” octagon box
LED Indicators:
Red LED for PIR detection; Green
LED for Ultrasonic detection.
FCC Compliant
cULus Listed
RoHS Compliant
Overview
The Dual Technology sensor’s combination of Ultrasonic and Passive Infrared
technologies offers the most complete sensing equipment available today. MicroSet
self-adjusting Dual Technology sensors drastically simplify and reduce a contractor’s
installation and adjustment time period.
Description/Operation
The MicroSet self-adjusting technology continuously monitors multiple sub-
frequencies in the event that if a continuous Doppler shift occurs, such as those
created by airflow from an air duct, the sensor will identify the noise as continuous
and then block it out of view at a select sub-frequency. It will continue to monitor
other sub-frequencies for human motion. This avoids false-activation, while still
maintaining the high level of sensitivity that is necessary for sensing minor motion in
a changing environment. Separate concurrent time delays for both Passive Infrared
and Ultrasonic technologies avoid false activations or deactivations. In Automatic
On Mode, the lights turn ON when a person enters the room. In Manual On Mode
(-R model only), the lights are turned ON by activating a momentary switch (model
# GMDS-*) that is connected to the sensor. When enabled, the daylighting feature
(-R models only) prevents lights from turning ON when the room is adequately
illuminated by natural light.
OAC-DT,
MicroSet Dual Tech
Ceiling Sensor
Low Voltage
•MicroSetself-adjustingTimeDelay
and sensitivity
•Optionalbuilt-inlightlevelsensor
•OptionalBAS/HVACisolatedrelay
•ProductstestedtoNEMAWD7-2011
Occupancy Motion Sensors Standard
•SelectableWalk-ThroughMode
•DualRelaycontrol
Applications
Ordering
Catalog #
Recommended
Room Size
Field of View Features
OAC-DT-2000-R
OAC-DT-2000
OAC-DT-1000-R
OAC-DT-1000
OAC-DT-0501-R
OAC-DT-0501
2,000 sq. ft.
2,000 sq. ft.
1,000 sq. ft.
1,000 sq. ft.
500 sq. ft.
500 sq. ft.
Two Way (360°)
Two Way (360°)
Two Way (360°)
Two Way (360°)
One Way (180°)
One Way (180°)
w/BAS Relay & Daylight Sensor
w/BAS Relay & Daylight Sensor
w/BAS Relay & Daylight Sensor
Frequency
32 kHz
32 kHz
32 kHz
32 kHz
40 kHz
40 kHz
PIR
Activated
Ultrasonic
Activated
MicroSet
Self-Adjusting
ACC131692