Cut Sheet
3
April 2015
CEPC – Emergency Power Control
www.coopercontrol.com
Wiring Diagrams
Wiring Diagram for 2-Wire
Non-Dimming Loads (w/ Relay Panel)
2 - Wire Non Dimmed
CEPC
Wire #
Description iLumin Connection
Yellow
Blue
Black/Orange
White
Blue/White
Red
Emergency Hot
Emergency Switchleg
Emergency Neutral
Regular Hot (Sensing)
Switchleg
Regular Neutral
Transformer Neutral wire
Relay Load Terminal Block
Transformer Power
Emergency
Panel
20A
Emergency
Lighting Load
Wiring Diagram for 2-Wire Non Dimmed Loads
Greengate
Relay Card Connection
Blue
Blue/
White
Regular Line Hot
Regular Neutral
Emergency
Power
Utility
Power
Test Test
CEPC
Red
White
Black/
Orange
Line
Load
Switchleg
Blue/
White
Yellow
Normal Panel
20A
2-Wire Non-Dimmed
CEPC Wire # Description iLumin Connection
Blue Emergency Hot
Yellow Emergency Switchleg
Blue/White Emergency Neutral
Black/Orange Regular Hot (Sensing) Transformer Power
Red Switchleg Relay Load Terminal Block
White Regular Neutral Transformer Neutral Wire
Wiring Diagram for 2-Wire
Non-Dimming Loads (w/ Switchpack)
2 - Wired Non Dimmed
CEPC
Wire #
Description Greengate Switchpack Connection
Yellow
Blue
Black/Orange
White
Blue/White
Red
Emergency Hot
Emergency Switchleg
Emergency Neutral
Regular Hot (Sensing)
Switchleg
Regular Neutral
Regular Hot
Regular Neutral
Switchpack Load Terminal Block
Emergency
Panel
20A
Emergency
Lighting Load
Wiring Diagram for 2-Wire Non Dimmed Loads
Greengate
Switchpack Connection
Blue
Blue/
White
Emergency
Power
Utility
Power
Test Te st
CEPC
Red
White
Black/
Orange
Switchleg - Blue
Blue/
White
Yellow
Normal Panel
20A
*Hot
Neutral
Hot - Blue
*Use Black lead for 120 VAC,
Use Orange lead for 277 VAC
2-Wire Non-Dimmed
CEPC Wire # Description
Greengate Switchpack
Connection
Blue Emergency Hot
Yellow Emergency Switchleg
Blue/White Emergency Neutral
Black/Orange Regular Hot (Sensing) Regular Hot
Red Switchleg
Switchpack Load Terminal
Block
White Regular Neutral Regular Neutral
Wiring Diagram for 4-Wire
Dimming Loads
1
Regular Neutral
Regular Line Hot (Sensing Circuit)
Load
Line
20A
VIO
GRY
1
CK4A or Room Controller
Relay
CEPC-1-D
TestTest
Utility
Power
Emergency
Power
RED
(Violet 0-10V)
5 EM Hot
7 EM
Neutral
Blue
(Violet 0-10V)
3
1 or 2
4
Emergency
Lighting Load
Emergency
Panel
CK4A or Room Controller
0-10V outputs
0-10V
Gray wire
6 EM Load
4-Wire Dimming
CEPC-1-D
Wire #
Color Description
Greengate
Connection
1 Black Regular Hot (120V)
Constant Hot and
Relay Line
2 Orange Regular Hot (277V)
Constant Hot and
Relay Line
3 Red Switched Hot Relay Load
4 White Regular Neutral
5 Blue Emergency Hot
6 Yellow Emergency Load Hot
7 White/Blue Emergency Neutral
Blue Dimmer Violet (0-10V +)
Panel Dimmer
Output Violet
Red To Load Violet (0-10V +)
Black Cap Off