Alarm configuration is used to select or setup:
• The Active Zone for each alarm point (SP3 or AL1, SP4 or AL2) to above or below the setting with "Act IVE"
submenu.
• Independent or ganged operation for SP3 / AL1 or SP4 / AL2 whether or not they should latch once triggered,
"LAtCH" submenu.
• Whether the normal state of Output Collector or Relay is opened or closed with "N.StAtE" submenu.
• Following Alarm modes: process (no deviation), high-deviation, low-deviation and band deviation with "AL.MOdE"
submenu.
• The amount of hysteresis or Deadband for the Setpoint3/Alarm1 or Setpoint4/Alarm2 with "AL db" submenu.
• Delays in Alarm Action with "NUM.dLy" submenu.
• Enable or disable Alarm points with "RSt AL" submenu.
AL.CNFG
ENTER ALARM CONFIGURATION MENU:
Press ‘MENU’ 1) 7 times, Display shows "AL.CNFG" Alarm Configuration Menu.
Press ‘RESET/ENTER’ 2) Display flashes "dISAbL" (default) or previous selection.
Press ‘▲/MAX’ 3) Select "ENAbLE" to configure Alarm1 (SP3) and Alarm2 (SP4).
24.1. AL 1.CNF Enter ALARM 1 CONFIGURATION Menu:
Press ‘RESET/ENTER’ 4) Display shows "StOREd" stored message momentarily and then advance to "AL
1.CNF" Alarm1 configuration submenu.
If necessary, Press ‘MENU’ to enter the other available following submenu: "AL 2.CNF"
Alarm2 Configuration, "AL db" Alarm Deadband Configuration, "NUM.dLy" Number of
display/reading configuration, "RSt AL" Alarm Reset Submenu. Refer to Steps 19
through 30 for details.