Spec Sheet
This warranty should be registered on our web-site
www.cooperandhunter.us within 60 days of installation.
The warranty is only valid when installed by a Licensed HVAC
Technician. A warranty period of Seven (7) years on compressor
to the original registered end-user. A warranty period of Five (5)
years on all parts to the original registered end user. Warranty
applies only to products remaining in their original installation
location.
GENERAL FEATURES
• Golden n and indoor
• Heat pump units can heat & cool up to 5 zones
• Turbo Operation
• Auto-Restart
• Self Diagnosis Function
• Multi speed fan
• Auto protection
COMPATIBILITY
Connect 3 multiple style indoor units:
Wall mounted: 9K/12K/18K
Cassette: 9K/12K/18K
Console: 9K/12K/18K
Floor & Ceiling: 9K/12K/18K
OUTDOOR SPECIFICATION
Air ow 2130 CFM
Noise Level 62.3 dB(A)
Dimension (W*D*H) 37.24x16.14x31.89 in
Net/Gross weight 156.53/167.55 lb
Refrigerant type R410A/105.8 oz
Refrigerant precharge 75 ft
Additional charge for each ft 0.16 oz
PERFORMANCE AND EFFICIENCY
Cooling Heating
28,000 Btu/h 28,000 Btu/h
SEER 22 HSPF4/HSPF5 10.4/9
EER 13 COP 3.5
OPERATION TEMPERATURE RANGE
Ambient temperature
cooling heating
-22~122 -22~86
ELECTRICAL
Power supply 208-230V/ 60Hz, 1Ph
MCA 30 A
MFA 45 A
MCA: Minimum Circuit Ampacity MFA: Max. fuse A
PIPING
Refrigerant piping Liquid/Gas side 3x1/4"/2x3/8"+1x1/2"
Max. length for all rooms 197 ft
Max. length for one indoor unit 98 ft
Max. height dierence between indoor and outdoor unit 49 ft
Max. height dierence between indoor units 33 ft
WIRING
Connection wiring 16AWG*4 Stranded, unshielded
SUBMITTAL DATA SHEET CH-HYP28MSPH-230VO (OUTDOOR UNIT)
Job Name: ................................................................................................................................... Date: ...........................................................................................................................................
Lacation: ..................................................................................................................................... Approval: ....................................................................................................................................
Engineer:..................................................................................................................................... Construction: ...............................................................................................................................
Submitted to: .............................................................................................................................. Unit #: .........................................................................................................................................
Submitted by: ............................................................................................................................. Drawing #: ..................................................................................................................................
Reference: ...................................................................................................................................
SOPHIA Hyper