Spec Sheet
Table Of Contents
Submittal Data Sheet
CH-24LCDTU/I (INDOOR UNIT) CH-24LCU/O (OUTDOOR UNIT)
Job Name:_________________________________________________________________________
Location:______________________________________________________ __________________
Engineer:______________________________________________________________________
Submitted to:_____________________________________________________________________
Submitted by:_____________________________________________________________________
Reference:_________________________________________________________________________
Date:______________________________________________________________________________
Approval:__________________________________________________________________________
Сonstruction:______________________________________________________________________
Unit #:_____________________________________________________________________________
Drawing #:_________________________________________________________________________
OPERATION TEMPERATURE RANGE
ELECTRICAL
PIPING
Cooling
PERFORMANCE
AND
EFFICIENCY
Capacity
SEER
EER
Capacity
COP
HSPF4
HSPF5
cooling
heating
Indoor Outdoor
62〜90 ℉ 32〜86 ℉
cooling heating
-22〜122 ℉ -22〜86 ℉
24000
3.81
12.5
10.6
24000
20.5
12.5
Btu/h
Btu/h
W/W
Btu
Input 1920
W
Heating at 47F
Duct Light Commercial Series
Duct Air Conditioners
• Flexible Installation
• Fresh Air Function
• Wired Control & Wi-Fi Connection
• Multi-Channel Air Distribution
• Built-In Water Pump
• Golden fin for outdoor and indoor
• Lower Noise
• Higher Pipe Limits
• Slim Design
Sound Preassure level (Hi/Mi/Lo)
Design pressure
Dimension (W*D*H)
Net/Gross weight
44/41/34 dB(A)
550/340 PSIG
43x30x10 in
87/103 Lbs
Refrigerant piping/Gas side in (3/8"5/8")
Max. pipe length ft 164
Max. difference in level ft 82
MCA: Minimum Circuit Ampacity; MFA: Max.fuse amps; RLA: Rated load amps
Power supply V/Hz/Ph 208-230V/ 60Hz/ 1Ph
MCA A 20
MFA A 30
Indoor fan motor
Outdoor fan motor
Compressor
Input
RLA
W 90
A 1.5
Input
RLA
W 150
A 0.5
Capacity
Input
Btu/h 24345
W 1970
RLA A 14.0
GENERAL FEATURES
INDOOR SPECIFICATION
Air flow
Noise level
Dimension (W*D*H)
Net/Gross weight
2354
61.0
37.24x16.14x31.89
135.58/148.81
Refrigerant Type
Refrigerant precharge
Additional charge for each ft
R410/91.7
25
0.32
CFM
dB(A)
in
Lbs
ft
oz
OUTDOOR SPECIFICATION
This warranty should be registered on our web-site www.cooperandhunter.us
within 60 days of installation. The warranty is only valid when installed by
a Licensed HVAC Technician. A warranty period of Seven (7) years on compres-
sor to the original registered end-user. A warranty period of Five (5) years on all
parts to the original registered end user. Warranty applies only to products
remaining in their original installation location.