Installation Manual
Table Of Contents
11
1 Liquid pipe
2 Gas pipe
3 Insulation for liquid pipe fitting
4 Insulation for gas pipe fitting
5 Clamps
 (use 2 clamps per insulation)
6 Indoor unit
Be sure to insulate local piping all the way into the 
pipe connections inside the unit. Exposed piping may 
facilitate condensation or may cause burns when 
touched. 
Make sure that no oil remains on the plastic parts of 
the decoration panel (optional equipment). Oil may 
damage and cause degradation to plastic parts.
3) Insulate as shown in the figure below
1 
2 
3 
4 
5 
6 
A 
B 
C 
Piping insulation material (field supply)
Flare nut connection
Insulation for fitting (field supply)
Piping insulation material (main unit)
Indoor unit
Clamp (field supply)
Turn seams up
Attach to the base
Tighten the part other than the piping insulation material
Piping insulation procedure
Gas piping Liquid piping
1
3
5
2
4
1
1
6
6
6
6
4
4
5
5
3
3
2
2
A
A
C
C
B
B
3.5 Additional refrigerant charge
CAUTION
Refrigerant should only be charged after the leak test and 
vacuum pumping are performed.
Check the type of refrigerant to be used on the machine 
nameplate. Charging with an unsuitable refrigerant may 
cause explosions and accidents, so always ensure that the 
appropriate refrigerant is charged.
Refrigerant containers must be opened slowly.
 The outdoor unit is factory charged with refrigerant. Calculate 
 the added refrigerant necessary according to the diameter and 
 length of the liquid pipe of the outdoor/indoor unit connection. 
3.6 Refrigerant piping work
1) Caution on pipe handling
Protect the open end of the pipe against dust and moisture.
All pipe bends should be done as gently as possible with a
pipe bender.
2) Be sure to insulate both the gas and liquid piping. Use
separate thermal insulation for each. See the figure
below.
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
Pipe length
Up to 15 m (49.2 ft) More than 15 m (49.2 ft)
Not less than 15 min
Not less than 10 min
Run time
*2. If the compound pressure gauge pointer swings back,
the refrigerant may contain water content or a pipe joint may be
loose. Check all pipe joints and retighten nuts as needed, then 
repeat steps 2 through 4.
Be sure to 
use a cap.
If no flare cap is 
available, cover the 
flare mouth with 
tape to keep dirt and 
water out.
Inter-unit wire
Liquid pipe
Liquid pipe 
insulation
Drain hose
Finishing tape
Gas pipe 
insulation
Gas pipe
Wall
Rain
6
Pipe length and refrigerant amount:
Connective
pipe length
Less 
than 7.5 m
More 
than 7.5 m
Air purging
method
Use a vacuum
pump
. 
Use a vacuum
pump 
Additional amount of refrigerant to be charged
Liquid side:   6.35 mm (1/4 in)
R410A: (Pipe length: 7.5(25))x15g/m(0.16oz/ft) 
 Liquid side:  9.52 mm (3/8 in)
R410A: (Pipe length: 7.5(25))x30g/m(0.32oz/ft) 










