Troubleshooting Sheet
1.3.9 High temperature protection of IPM module or compressor top diagnosis and 
solution(P2) 
Error Code 
P2
Malfunction decision 
conditions 
If the sampling voltage is not 5V, the LED will display the failure. 
Supposed causes 
● 
Installation mistake 
●  Power supply problems. 
●  System leakage or block 
● 
PCB faulty 
Trouble shooting: 
For 18K,24K, 
Yes
Tighten the screws and apply 
silicon grease.
Tighten the screws and apply 
silicon grease.
Replace the outdoor control PCB.
Replace the outdoor control PCB.
No
Check if the Fastening screws 
on the PCB and IPM radiator 
are fixed tightly.
For other models, 
Check if the air flow system 
of indoor and outdoor units 
are obstructed?
Clear up the air inlet and outlet or the heat 
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Turn off the power supply and turn 
it on 10 minutes later.
Check if the temperature 
of compressor Top
Is 
more than 90
℃?
No
Check if the refrigerant 
system
 is normal?
Repair the refrigerant 
system .
Replace the outdoor control PCB.
Yes
Check if all the connection, especially 
the connection of OLP (Over Load 
Protector) sensor is good.
Correct the connection.No
Measure the resistance 
between the two ports of 
the OLP. Is it zero?
Yes
Replace the OLP.No
Replace the outdoor control PCB.Yes
No