Cut Sheet

F-68
www.eaton.com
www.arrowhart.com
EATON 2014 Arrow Hart Buyers Guide
SECTION
F
Posi-lok E0400 series female panels
Features
•
Designed to meet Article 520-53 Section K and
Article 530-22 Section A (NEC) standards
•
Sequential interlock system requires the user to
connect and disconnect each plug in sequence
•
Polarized panels eliminate the possibility of
cross-phasing
•
Proven cam-lok double cam principle provides
a positive, vibration-proof connection
•
No moving contact surfaces, eliminating arching
or burning of contacts
•
Recessed contacts protected by insulating jacket
that extends beyond contact ends for safety
Female panel part numbers
Receptacles per panel Female panels Cover color code
3 E0400-1685 GR, WH, BK
4 E0400-1686-NN GR, BK, RD, BU
4 E0400-1696 GR, WH, BK, RD
4 E0400-1883-NN GR, BRN, ORG, YEL
5 E0400-1687 GR, WH, BK, RD, BU
5 E0400-1702 GR, WH, BRN, ORG, YEL
6 E0400-1885 GR, WH, BK, RD, BU
Add "LS" suffix to end of part number to order panels with a limit switch.
Available on all positions. Consult factory.
Limit switch ratings are [125, 250, 480V/AC, 15A], [125V/DC, .5A], [250V/DC, .25A]
Plugs must be ordered separately.
Testing & code compliance: Listed to UL498, file no. E67181, CSA certified to C22.2, no. 182.3-M1987, file no. LR13963
Material characteristics: Panel: Steel, Temperature rating: -40º C to 105º C
Compliances, specifications and availability are subject to change without notice.
Single pole connectors
Posi-lok panels E0400 series
Product description
Cable size #2 AWG - 4/0
600V AC/DC, up to 400A continuous
Color information:
BK (Black), RD (Red), GR (Green), WH (White), BU (Blue), BRN (Brown), ORG (Orange), YEL (Yellow)
BK RD GR WH BU BRN ORG YEL
(Black) (Red) (Green) (White) (Blue) (Brown) (Orange) (Yellow)