Product Overview
Maximum Deflection
Beam
Allowable @ Maximum Allowable Load @ Deflection =
Span Part Beam Load Allowable
No.
Load Beam Load 1/240 Span 1/360 Span
in. mm Lbs. kN in. mm Lbs. kN Lbs. kN
12”
(305)
BFP42 841
(3.74)
0.104
(2.64)
403
(1.79)
269
(1.19)
BFP42A 2325
(10.34)
0.060
(1.52)
1948
(8.66)
1299
(5.78)
24”
(609)
BFP42 420
(1.87)
0.417
(10.59)
100
(0.44)
66
(0.29)
BFP42A 1
161
(5.16)
0.239
(6.07)
486
(2.16)
323
(1.43)
36”
(914)
BFP42 279
(1.24)
0.938
(23.82)
43
(0.19)
29
(0.13)
BFP42A 773
(3.44)
0.537
(13.64)
214
(0.95)
142
(0.63)
48”
(1219)
BFP42 208
(0.92)
1.667
(42.34)
23
(0.10)
15
(0.06)
BFP42A 578
(2.57)
0.955 (24.26) 119
(0.53)
78
(0.34)
60”
(1524)
BFP42 166
(0.74)
2.604
(66.14)
14
(0.06)
8
(0.03)
BFP42A 461
(2.05)
1.491
(37.87)
74
(0.33)
48
(0.21)
72”
(1829)
BFP42 137
(0.61)
3.750
(95.25)
8
(0.03)
5
(0.02)
BFP42A 383
(1.70)
2.148
(54.56)
49
(0.22)
31
(0.14)
96”
(2438)
BFP42 101
(0.45)
6.667
(169.34)
3
(0.01)
––
BFP42A 284
(1.26)
3.818
(96.98)
24
(0.10)
14
(0.04)
120”
(3048)
BFP42 79 (0.35) 10.417 (264.59) ––––
BFP42A 224 (0.99) 5.966 (151.53) 11 (0.05) 5 (0.02)
BEAM LOADING DATA FOR GLASS REINFORCED POLYESTER RESIN
Maximum Deflection
Beam Allowable @ Maximum Allowable Load @ Deflection =
Span Part Beam Load Allowable
No. Load Beam Load 1/240 Span 1/360 Span
in. mm Lbs. kN in. mm Lbs. kN Lbs. kN
12”
(305)
BFV42 988 (4.39) 0.112 (2.84) 440 (1.96) 293 (1.30)
BFV42A 2865 (12.74) 0.063 (1.60) 2278 (10.13) 1518 (6.75)
24”
(609)
BFV42 493 (2.19) 0.448 (11.38) 109 (0.48) 73 (0.32)
BFV42A 1431 (6.36) 0.252 (6.40) 568 (2.52) 378 (1.68)
36”
(914)
BFV42 328 (1.46) 1.009 (25.63) 48 (0.21) 31 (0.14)
BFV42A 953 (4.24) 0.566 (14.37) 251 (1.11) 166 (0.74)
48”
(1219)
BFV42 245 (1.09) 1.793 (45.54) 26 (0.1
1)
16 (0.07)
BFV42A 713 (3.17) 1.006 (25.55) 139 (0.62) 92 (0.41)
60”
(1524)
BFV42 195 (0.87) 2.802 (71.17) 15 (0.06) 9 (0.04)
BFV42A 569 (2.53) 1.572 (39.93) 87 (0.38) 57 (0.25)
72”
(1829)
BFV42 162 (0.72) 4.035 (102.49) 9 (0.04) 5 (0.02)
BFV42A 473 (2.10) 2.264 (57.50) 58 (0.26) 37 (0.16)
96”
(2438)
BFV42 120 (0.53) 7.173 (182.19) 3 (0.01) 1 (0.004)
BFV42A 351 (1.56) 4.025 (102.23) 29 (0.13) 17 (0.07)
120”
(3048)
BFV42 94 (0.42) 11.207 (284.66) –– ––
BFV42A 278 (1.23) 6.288 (159.71) 14 (0.06) 7 (0.03)
BEAM LOADING DATA FOR GLASS REINFORCED VINYL ESTER RESIN
Loading Information
Beam Loads:
The above charts list the total allowable uniform load for various simple spans based on a minimum safety factor of 2. If the load is
concentrated at center span, multiply the load from the above charts by 0.5 and the corresponding deflection by 0.8.
All beams should be supported in a manner to prevent rotation at supports. Long, deep beams should be tied between supports to prevent twist.
For channels with holes or slots use 90% of recommended load shown in channel loading chart.
Fiberglass Materials
Reference page 182 for general fitting specifications.
Fiberglass
187