Product Overview
Maximum Deflection
Beam Allowable @ Maximum Allowable Load @ Deflection =
Span Part Beam Load Allowable
No.
Load Beam Load 1/240 Span 1/360 Span
in. mm Lbs. kN in. mm Lbs. kN Lbs. kN
12”
(305)
BFP22 1781 (7.92) 0.064 (1.62) 1392 (6.19) 928 (4.13)
BFP22A 2259 (10.05) 0.037 (.94) 2259 (10.05) 2051 (9.12)
24”
(609)
BFP22 890 (3.96) 0.256 (6.50) 347 (1.54) 231 (1.03)
BFP22A 1127 (5.01) 0.147 (3.73) 767 (3.41) 511 (2.27)
36”
(914)
BFP22 592 (2.63) 0.576 (14.63) 153 (0.68) 101 (0.45)
BFP22A 750 (3.33) 0.330 (8.38) 338 (1.50) 224 (0.99)
48”
(1219)
BFP22 443 (1.97) 1.024 (26.01) 85 (0.38) 55 (0.24)
BFP22A 560 (2.49) 0.587 (14.91) 188 (0.83) 123 (0.55)
60”
(1524)
BFP22 353 (1.57) 1.600 (40.64) 53 (0.23) 34 (0.15)
BFP22A 446 (1.98) 0.918 (23.32) 117 (0.52) 76 (0.34)
72”
(1829)
BFP22 293 (1.30) 2.303 (58.49) 35 (0.15) 22 (0.10)
BFP22A 370 (1.64) 1.322 (33.58) 78 (0.34) 50 (0.22)
96”
(2438)
BFP22 218 (0.97) 4.095 (104.01) 17 (0.07) 9 (0.04)
BFP22A 273 (1.21) 2.350 (59.69) 39 (0.17) 23 (0.10)
120”
(3048)
BFP22 172 (0.76) 6.398 (162.51) 8 (0.03) 3 (0.01)
BFP22A 214 (0.95) 3.671 (93.24) 19 (0.08) 9 (0.04)
BEAM LOADING DATA FOR GLASS REINFORCED POLYESTER RESIN
Maximum Deflection
Beam Allowable @ Maximum Allowable Load @ Deflection =
Span Part Beam Load Allowable
No. Load Beam Load 1/240 Span 1/360 Span
in. mm Lbs. kN in. mm Lbs. kN Lbs. kN
12”
(305)
BFV22 2220 (9.87) 0.071 (1.80) 1568 (6.97) 1045 (4.65)
BFV22A 6442 (28.65) 0.039 (0.99) 6442 (29.65) 5549 (24.68)
24”
(609)
BFV22 1109 (4.93) 0.283 (7.19) 391 (1.74) 260 (1.15)
BFV22A 3219 (14.32) 0.155 (3.94) 2079 (9.25) 1385 (6.16)
36”
(914)
BFV22 738 (3.28) 0.637 (16.18) 172 (0.76) 114 (0.51)
BFV22A 2144 (9.53) 0.348 (8.84) 922 (4.10) 613 (2.72)
48”
(1219)
BFV22 553 (2.46) 1.133 (28.78) 96 (0.43) 63 (0.28)
BFV22A 1606 (7.14) 0.619 (15.72) 516 (2.29) 342 (1.52)
60”
(1524)
BFV22 441 (1.96) 1.770 (44.96) 60 (0.26) 39 (0.17)
BFV22A 1283 (5.70) 0.967 (24.56) 327 (1.45) 216 (0.96)
72”
(1829)
BFV22 366 (1.63) 2.549 (64.74) 40 (0.18) 25 (0.11)
BFV22A 1067 (4.74) 1.393 (35.38) 224 (0.99) 147 (0.65)
96”
(2438)
BFV22 273 (1.21) 4.531 (1
15.09)
19 (0.08) 1
1
(0.05)
BFV22A 796 (3.54) 2.477 (62.91) 121 (0.54) 78 (0.34)
120”
(3048)
BFV22 216 (0.96) 7.079 (179.80) 9 (0.04) 7 (0.02)
BFV22A 633 (2.81) 3.870 (98.30) 72 (0.32) 44 (0.19)
BEAM LOADING DATA FOR GLASS REINFORCED VINYL ESTER RESIN
Loading Information
Beam Loads:
The above charts list the total allowable uniform load for various simple spans based on a minimum safety factor of 2. If the load is
concentrated at center span, multiply the load from the above charts by 0.5 and the corresponding deflection by 0.8.
All beams should be supported in a manner to prevent rotation at supports. Long, deep beams should be tied between supports to prevent twist.
For channels with holes or slots use 90% of recommended load shown in channel loading chart.
Fiberglass Materials
Reference page 182 for general fitting specifications.
Fiberglass
185