Product Overview

TABLE 2: MAXIMUM NUMBER OF WIRES
Also suitable for the number of wires in table below when installed to support and supply electric discharge type
lighting fixtures when raceway wiring is suitable for at least 70°C and clearance between fixture and raceway is at
least
1
/8”. In all cases, a snap-in cover is required to complete the raceway enclosure.
TABLE 3: MAXIMUM NUMBER OF WIRES
Also suitable for the number of wires in table below when installed to support and supply electric discharge type
lighting fixtures
when raceway wiring is suitable for 75°C, or wiring suitable for 60°C if a minimum clearance
between fixture and raceway is at least
1
/2”. In all cases, a snap-in cover is required to complete the raceway
enclosure.
When using B217-24 snap-in cover, the number of wires is limited to 7 or fewer conductors no larger than #12 AWG.
When using B217-24 snap-in cover, the number of wires is limited to 7 or fewer conductors no larger than #12 AWG.
Raceway Catalog Wires
W
ire Size
B11 B12 B22 B24 B26 B32 B56
B11K06
B12K06 B22K06 B24K06 B26K06 B32K06 B56K06
Type Insulation: FEP, FEPB, RH, RHH, RHW, RUH, THHN, THWN, THW, XHHW
14
13 10 10 10 10 10 6
12 13 10 10 10 10 10 6
10 13 10 8 8 8 6
8108 6664
6 8 6 4443
Raceway Catalog Wires
Wire Size
B11 B12 B22 B24 B26 B32 B56
B11K06 B12K06 B22K06 B24K06 B26K06 B32K06 B56K06
Type Insulation: FEP, FEPB, RH, RHH, RHW, RUH, THHN, THWN, THW, XHHW
14 10 10 10 10 10 10 4
12 10 10 10 10 10 10 3
10 8 5 5555
8 6 4 4444
6 4 4 4 444
Reference Data
Reference Data
231