Product Overview
Anchors
‡
187
Read safety/installation instruction sheets in packages before use.
Anchors
Eaton's B-Line series fasteners www.eaton.com/b-lineseries
• One-piece, all steel threaded fastener system for suspending
steel threaded rod.
• Suitable for overhead installations such as suspending cable
tray, pipe hangers, strut and conduit.
• Side Mount (SW) available for side mounting applications.
• Lower in-place cost, when compared to beam clamps, lag bolts
and drop-ins.
• Wood rapid rods can be installed with a screw gun or
hammer drill.
• Concrete Rapid Rod hangers can be installed with an adjustable
torque, battery powered screw gun or hammer drill.
• UL & FM approved.
• Made of Zinc Plated carbon steel.
Rapid Rod
™
Hangers
Wood Rapid Rod - Data
1
/4" Thread
3
/8" Thread
Forming Forming
Pre-Drill Diameter
(in.)
1
/8
1
/8
Point Style Type 17 Type 17
Wood Rapid Rod - Embedment & Load Data (lbs.)
Rod/Anchor
Size Embedment Depth Fir Pine Spruce
1
/4" 1" 170 160 160
3
/8" 2" 375 375 375
1
/2"2
1
/2" 665 775 775
Rapid Rod
™
Hangers - Wood
Concrete Rapid Rod - Data
1
/4"
3
/8"
1
/2"
ANSI Drill Bit
(in.)
1
/4
1
/4
3
/8
Thread Length (in.) 1
1
/8 1
3
/8 2
1
/2
Min. Embedment Depth (in.) 1
1
/4 1
1
/2 2
3
/4
Load Capacity Tension (lbs.) * 485 650 1510
Load Capacity Shear
(lbs.) * 610 660 1580
Rapid Rod
™
Hangers - Concrete
Minimum load ratings are based on a safety factor of 4. UL approved load
capacity for
3
/8" rod sizes and
1
/4" screw size is 260 lbs., maximum 3" pipe.
UL approved load capacity for
3
/8" rod sizes and
3
/8" screw size is 375 lbs.,
maximum 4" pipe. FM approval only applies to
3
/8" x 2
1
/2" screw size.
Approved for 365 lbs., up to 4" pipe.
‡ Not ICC-ES Certified
* Based on concrete compression strength of 4000 psi using applied
safety factor of 4.0. For additional loading information contact factory.
FM approved load capacity for
3
/8" anchor is 365 lbs., maximum 4" pipe
size. FM approved load capacity for
1
/2" anchor is 950 lbs., maximum 8"
pipe size.