Instruction manual

9
Contents Page
Threshold Buffer
A buffer to prevent the sensor from bouncing between standard operation and the aware state when
the assessments are very close to a threshold. E.g., if a minimum value is set to 32°, a maximum
value is set for 41° and the buffer is set to 1°, when a sensor takes an assessment below 32° or
above 41° it enters and remains in the Aware State until the temperature reading returns to within 1°
of the preset limits (i.e., 33° and 40° respectively).
Synchronize
In large sensor networks, offset is used to prevent all sensors from transmitting simultaneously thus
reducing communication disruption.
Failed Transmissions
The number of transmissions the sensor sends without response from a gateway before entering
battery-saving link mode. In link mode the sensor will scan for another gateway on the same network
and use that to send information. If none are found, the sensor will sleep for 2 hours before trying to
scan again.
Configuring Multiple Sensors Simultaneously
Once you’ve set the conguration for one sensor, you can then congure multiple sensors
simultaneously with the same settings.One sensor must already be congured to use this feature.
Click on the “Overview” tab in the main navigation bar. You can make certain congurations to
multiple sensors by clicking on “Congure Multiple Sensors” at the bottom of the Sensor List Window.
In the “Congure Multiple Sensors” pane, you can choose which sensor to use for the desired
conguration. Click the “Check All” or “Uncheck All” button to select which sensors will be updated
with the sensor conguration you identied above.
Note: Settings congured through this window will overwrite any custom settings currently set for the selected sensors.
Setting Notifications
Automated notications can be set up to alert you via SMS text or email if a wireless sensor meets a
set threshold or condition. To create a new notication or edit/delete an existing notication, click on
the “Notications” link in the main menu area of the site.
1. The Notification List Window
?
Threshold B
uffer
1 °
Below: 32 ° or Above: 41 °
33° 40°
Enable / Disable
a Notication
Edit an Existing
Notication
View / Edit / Delete
Notication
Create a New
Notication
Notications
Tab