Heartbeat Interval
How often the sensor transmits to the online system via the gateway. It is recommended to set the
Heartbeat Interval to 120 minutes (2 hours) to preserve battery life.
Heartbeat Interval Battery Life
30 mins Up to 6 months
60 mins Up to 1 year
120 mins Up to 3 years
Assessments per Heartbeat
How many times between heartbeats a sensor will compare its readings against the measurement
limits. An average of assessment readings is transmitted on the heartbeat.
Aware State Heartbeat
If outside of measurement limit during assessment/reading puts the sensor into “High Alert” or Aware
State. Now assessment frequency is determined by the Aware State Heartbeat.
A Notication Alert will not automatically happen unless parameters are set-up in the Notications
window.
Sensor is On
The time of day the sensor is actively working. No communication will be sent while sensor is
hibernating. If you select “Between”, you will need to indicate the time-frame the sensor should be on.
This is useful to monitor conditions only during daytime or nightime hours.
Use Aware State (also known as Threshold)
Any assessments below the minimum value or above the maximum value will cause the sensor to
enter an Aware State. Minimum (left slider) any assessments below this will cause sensor to go into
Aware State. Maximum (right slider) any assessments above this will cause the sensor to enter Aware
State.
If you have a question about any elds
in this window, mouse over the next
to the right of the eld and it will
give you a brief denition
You can also type in the numbers as
well as using the sliders to
change them
Below: 32 ° or Above: 41 °
Use Aware State
Sensor is operating
within limits
Sensor is operating
outside limits
(enters Aware State)
?